6 Commissioning

Installation manual

17

RXS50+60 + RX50+60 + ARXS50~71
R410A split series
3P360062-1H – 2016.09

5

Turn ON the power supply

5.6.4

Cooling equipment and computer rooms
at low outdoor temperatures

About the facility mode

This  mode  is  especially  for  cooling  applications  like  equipment  or
computer  rooms.  NEVER  use  in  residence  or  office  applications
where people occupy.

To set the facility mode

When  cutting  the  jumper  J6  on  the  PCB,  the  operation  range  will
expand  to  –15°C.  The  facility  mode  will  stop  if  the  outdoor
temperature  goes  below  –18°C  and  restarts  when  the  temperature
rises again.

1

Remove the screws of the top plate.

2

Remove the drip proof cover.

3

Cut jumper J6 on the PCB.

b

c

a

a

Top plate

b

Drip proof cover

c

PCB

INFORMATION

▪ Intermittent noises may be produced by the indoor unit

due  to  the  fan  of  the  outdoor  unit  that  is  turning  ON
and/or OFF.

▪ Do  NOT  place  humidifiers  or  other  items  which  might

raise  the  humidity  in  rooms  when  you  use  the  facility
mode.

▪ Cutting jumper J6 results in highest speed of the indoor

unit fan.

5.7

Finishing the outdoor unit
installation

5.7.1

To finish the outdoor unit installation

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

f

b

a

e

d

c

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

2

Install the service cover.

6

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

6.1

Precautions when commissioning

INFORMATION

During  the  first  running  period  of  the  unit,  the  required
power may be higher than stated on the nameplate of the
unit.  This  phenomenon  is  caused  by  the  compressor,  that
needs  a  continuous  run  time  of  50  hours  before  reaching
smooth operation and stable power consumption.

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

6.2

Checklist before commissioning

Do NOT operate the system before the following checks are OK:

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed  according  to  this  document,  and  have  not  been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

The following 

field wiring

 has been carried out according

to  this  document  and  the  applicable  legislation  between
the outdoor unit and the indoor unit.

Summary of Contents for RXS50K2V1B

Page 1: ...tion manual R410A split series English Installation manual R410A split series RXS50K2V1B RXS60F4V1B RXG50K3V1B RX50G3V1B RX60G3V1B RXS50L2V1B RXS60L2V1B RX60G4V1B ARXS50G3V1B ARXS50L2V1B ARXS60L2V1B ARXS71L2V1B ...

Page 2: ...nstrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nu...

Page 3: ...cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemia...

Page 4: ...ile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus st...

Page 5: ...ucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurody...

Page 6: ...it installation 17 5 7 1 To finish the outdoor unit installation 17 6 Commissioning 17 6 1 Precautions when commissioning 17 6 2 Checklist before commissioning 17 6 3 To perform a test run 18 6 4 To start and stop forced cooling 18 6 5 Starting up the outdoor unit 18 7 Disposal 18 7 1 To pump down 18 8 Technical data 19 8 1 Wiring diagram 19 1 About this document Target audience Authorised install...

Page 7: ...in the unit such animals can cause malfunctions smoke or fire when making contact with electrical parts INFORMATION The sound pressure level is less than 70 dBA WARNING Do not modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your dealer In case of accidental refrigerant leaks make sure there are no ...

Page 8: ...d air discharged from the unit or the operation noise will NOT disturb anyone Sound sensitive areas e g near a bedroom and the like so that the operation noise will cause no trouble Provide sufficient space around the unit for servicing and air circulation Avoid areas where flammable gas or product might leak Install power cables at least 1 metre away from televisions or radios to prevent interfer...

Page 9: ...otect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up a b c c d a Snow cover or shed b Pedestal c Prevailing wind direction d Air outlet In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow See 5 2 Mounting the outdoor unit on page 10 fo...

Page 10: ...CTROCUTION DANGER RISK OF BURNING 1 1 2 2 5 2 Mounting the outdoor unit 5 2 1 To provide the installation structure 1 Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation 2 Prepare 4 sets of M8 or M10 anchor bolts nuts and washers each field supply 3 Fix the unit securely with anchor bolts 20 mm 330 5 8 0 2 4 0 ...

Page 11: ...water surrounding the unit Avoid drain water flowing over the footpath so that it does not become slippery in case of ambient freezing temperatures If you install the unit on a frame install a waterproof plate within 150 mm of the bottom side of the unit in order to prevent the invasion of water in the unit and to avoid the drain water dripping see the following illustration Use a drain plug for d...

Page 12: ... open the refrigerant stop valve before checking the refrigerant piping When you need to charge additional refrigerant it is recommended to open the refrigerant stop valve after charging 5 3 2 Guidelines when connecting the refrigerant piping Take the following guidelines into account when connecting pipes Coat the flare inner surface with ether oil or ester oil when connecting a flare nut Tighten...

Page 13: ... valve on the gas line with silicon sealant to prevent freezing Silicon sealant make sure there is no gap To open close the stop valve 1 Remove the valve cover 2 Insert a hexagon wrench liquid side 4 mm gas side 6 mm into the valve stem and turn the valve stem Counterclockwise to open Clockwise to close 3 When the valve stem cannot be turned any further stop turning The valve is now opened closed ...

Page 14: ...pressure If the pressure Then Does not change There is no moisture in the system This procedure is finished If the pressure Then Increases There is moisture in the system Go to the next step 3 Evacuate for at least 2 hours to a pressure on the manifold of 0 1 MPa 1 bar 4 After turning OFF the pump check the pressure for at least 1 hour 5 If you do NOT reach the target vacuum or cannot maintain the...

Page 15: ...ectrical work confirm that each electrical component and terminal inside the electrical components box is connected securely Make sure all covers are closed before starting up the unit WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause...

Page 16: ...ge circuit breaker Must comply with applicable legislation 5 6 2 To connect the electrical wiring on the outdoor unit 1 Remove the outside panel 2 Remove the switch box cover 1 2 3 3 Open the wire clamp 4 Connect the interconnection cable and power supply as follows 3 1 23 5 Tighten the terminal screws securely We recommend to use a Philips screwdriver 6 Install the switch box cover 7 Install the ...

Page 17: ...mmissioning NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor might result 6 1 Precautions when commissioning INFORMATION During the first running period of the unit the required power may be higher than stated on the nameplate of the unit This phenomenon is caused by the compressor that needs a continuous run time of 50 hours before reach...

Page 18: ...nit Turn ON the outdoor unit Push the forced cooling switch SW1 in less then 3 minutes after turning the power ON Result Operation starts Forced cooling will stop automatically after 15 minutes To stop operation press the switch SW1 SW 1 6 5 Starting up the outdoor unit See the indoor unit installation manual for configuration and commissioning of the system 7 Disposal 7 1 To pump down Example To ...

Page 19: ...OR Q DI EARTHLEAKCIRCUITBREAKER AC CN E HA HE HL HN HR MR _A MR _B S U V W X A CONNECTION CONNECTOR Q L OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG CONNECTOR FRAMEGROUND S L FLOATSWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOTLAMP L...

Page 20: ...3P360062 1H 2016 09 Copyright 2016 Daikin ...

Reviews: