background image

8

English

Outdoor Unit Installation

6. 

Refilling the refrigerant

Check the type of refrigerant to be used on the machine nameplate.

Precautions when adding R410A

Fill from the gas pipe in liquid form.

It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
1)  Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon 

attached” displayed on it.)

Filling a cylinder with an attached siphon

Stand the cylinder upright when 

filling.

There is a siphon pipe inside, so the 
cylinder need not be upside-down to 

fill with liquid.

Filling other cylinders

Turn the cylinder upside-down 

when filling.

• Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

7. 

Refrigerant piping work

7-1 Caution on pipe handling 

1)  Protect the open end of the pipe against dust and moisture.
2)  All pipe bends should be as gentle as possible. Use a pipe bender for  

bending.

7-2 Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:
1)  Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 0.045kcal/mh°C)) 
Be sure to use insulation that is designed for use with HVAC Systems.

2)  Be sure to insulate both the gas and liquid piping and to provide insulation  

dimensions as below. 

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 5/8 inch 

(15.9mm)

O.D. 3/8 inch 

(9.5mm)

I.D. 5/8-25/32 inch 

(16-20mm)

I.D. 15/32-19/32 inch 

(12-15mm)

Minimum bend radius

Thickness 13/32 inch (10mm) Min.

1-15/16 inch (50mm) 

or more

1-3/16 inch (30mm)

or more

Thickness  

0.039 inch (1.0mm) 

(C1220T-O)

Thickness  

0.031 inch (0.8mm) 

(C1220T-O)

• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Wall

If no flare cap is 

available, cover the 

flare mouth with 

tape to keep dirt or 

water out.

Be sure to 

place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wire

01_EN_3P300674-3.indd   8

10/13/2011   2:23:53 PM

Summary of Contents for RXS30LVJU

Page 1: ...it series Fran ais Espa ol Manuel dinstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS30LVJU RXS36LVJU RKS30LVJU RKS36LVJU 00_CV_3P...

Page 2: ...s so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk o...

Page 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Page 4: ...ything under the unit which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be...

Page 5: ...e below the ceiling surface 9 7 8 250 from wall Allow space for piping and electrical servicing Right side plate 13 3 4 350 Clamping material Insulation tube Bottom frame Tape Also insulate the connec...

Page 6: ...ain socket A drain caps B and a drain hose with the outdoor unit Otherwise drain water may freeze impairing heating performance 1 Insert drain receiver C onto drain socket A and drain cap B beyond 4 p...

Page 7: ...flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 3 8 inch 9 5mm 24 1 29 4ft lbf 32 7 39 9N m Gas side 5 8 inch 15 9mm 45 6 55 6ft lbf 61 8 75 4N...

Page 8: ...e gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swi...

Page 9: ...as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethylen...

Page 10: ...cooling operation switch SW1 Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally pu...

Page 11: ...ng the binding band as shown in the gure Secure rmly making sure no outside pressure is exerted on the terminals Power supply terminal block L1 L2 1 2 3 Use the speci ed wires and connect them securel...

Page 12: ...s designed for facilities such as equipment or computer rooms It is never to be used in a residence or office where people occupy the space 1 You can expand the operation range to 14 F 10 C by turning...

Page 13: ...Carry out the test operation in accordance with the operation manual to ensure that all functions and parts such as fin movement are working properly The air conditioner requires a small amount of po...

Page 14: ...3P300674 3 M11B136 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P300674 3 indd 2 10 21 2011 1 32 12 PM...

Reviews: