Installation Guidelines 

• Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.

More than 

3-15/16 (100)

More than 

13-3/4 (350)

Side view

47-1/4

(1200)

or less

More than 

1-15/16 (50)

More than 

1-15/16 (50)

More than 

13-3/4 (350)

Top view

More than 

3-15/16 (100)

unit: inch (mm)

Wall facing one side

Walls facing two sides

Top view

More than 

3-15/16 (100)
More than 

13-3/4 (350)

More than 

1-15/16 (50)

Walls facing three sides

Outdoor Unit Installation

1. 

Installing outdoor unit

1)  When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Drawings”.
2)  If drain work is necessary, follow the procedures below.

2. 

Drain work

• Use drain plug for drainage.
• If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least 3-15/16 inch 

(100mm) in height under the outdoor unit’s feet.

• In cold areas, do not use a drain socket (A), drain caps (B) and a drain hose with the outdoor unit.  

(Otherwise, drain water may freeze, impairing heating performance.)

1)  Insert drain receiver (C) onto drain socket (A) and drain cap (B) beyond 4 

projections around drain socket and drain cap.

2)  Insert drain socket and drain caps into their matching drain hole; Drain socket 

(A) into drain hole 

I

 and drain caps (B) into drain hole 

II

 and 

III

. After insertion, 

turn them about 40° clockwise.

Projections

Projections

(C) Drain receiver

(A) Drain socket

(B) Drain cap

I

II

III

(Be sure not to insert them into wrong drain 
holes, or there causes water leakage.)

(View from bottom)

NOTE

Check that the drain receiver (C) is correctly engaged with the projections of the drain socket (A) and drain cap (B). 
Otherwise, water leakage may result.

Projections 
(4 points)

Projections 
(4 points)

3)   Connect vinyl hose on the market (internal diameter of 1 inch (25mm)) to drain socket (A). 

(If the hose is too long and hangs down, fix it carefully to prevent the kinks.)

4)  Make sure that there is no water leakage from portion 

I

II

, or 

III

.

NOTE

If the drain holes of the outdoor unit are covered with the mounting bracket or the floor, raise the unit to provide the space of 
more than 3-15/16 inch (100mm) under the leg of the outdoor unit.

01_EN_3P300674-2.indd   5

10/5/2011   2:41:55 PM

Summary of Contents for RXS24LVJU

Page 1: ...lish Installation manual R410A Split series Fran ais Espa ol Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Model RXS24LVJU 00_CV_3P300674 2 indd 1 10 18 2011 10 38 43...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk...

Page 3: ...aker Failure to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be expos...

Page 4: ...under the unit which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to...

Page 5: ...ace below the ceiling surface 9 7 8 250 from wall Allow space for piping and electrical servicing Right side plate 13 3 4 350 Clamping material Insulation tube Bottom frame Tape Also insulate the conn...

Page 6: ...socket A drain caps B and a drain hose with the outdoor unit Otherwise drain water may freeze impairing heating performance 1 Insert drain receiver C onto drain socket A and drain cap B beyond 4 proj...

Page 7: ...e flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 5 8 inch 15 9mm 45 6 55 6ft lbf 61 8 75 4N...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not sw...

Page 9: ...e as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethyle...

Page 10: ...cooling operation switch SW1 Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally pu...

Page 11: ...ing the binding band as shown in the gure Secure rmly making sure no outside pressure is exerted on the terminals Power supply terminal block L1 L2 1 2 3 Use the speci ed wires and connect them secure...

Page 12: ...s designed for facilities such as equipment or computer rooms It is never to be used in a residence or office where people occupy the space 1 You can expand the operation range to 14 F 10 C by turning...

Page 13: ...uires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circui...

Page 14: ...3P300674 2 M11B135 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P300674 2 indd 2 10 18 2011 10 38 43 AM...

Reviews: