background image

RX(Y)Q RXQ8+1 RXYQ8~1 
RXYQ18~4 RXQ5~1 RXYQ5~4 
REYQ8~4 RXYSQ4~6M7V3B
VRVII and VRVII-S system air conditioner
4PW16234-1C

 

Operation manual

5

6.3.

Adjusting the air flow direction

Refer to the operation manual of the remote controller.

Movement of the air flow flap 

(See figure 7)

For the following conditions, a micro computer controls the air flow
direction which may be different from the display.

The air flow direction can be adjusted in one of the following ways.

The air flow flap itself adjusts its position.

The air flow direction can be fixed by the user.

Automatic "

" and desired position "

".

6.4.

Setting the master remote controller 

(for RXYQ, RXYSQ and REYQ series)

When the system is installed as shown in 

figure 8

 and 

figure 9

, it is

necessary to designate one of the remote controllers as the master
remote controller.

For RXYQ+RXYSQ series 

(See figure 8)

When one outdoor unit is connected with several indoor units.

For REYQ series 

(See figure 9)

When one BS unit is connected with several indoor units.

Only the master remote controller can select heating, cooling or
automatic (only REYQ series) operation.

The displays of slave remote controllers show 

 (change-

over under centralized control) and they automatically follow the
operation mode directed by the master remote controller.

However, it is possible to changeover to program dry with slave
remote controllers if the system is in cooling operation set by the
master remote controller.

How to designate the master remote controller

Press the operation mode selector button of the current master

remote controller for 4 seconds.

The display showing 

 (change-over under centralized

control) of all slave remote controllers connected to the same
outdoor unit or BS unit flash.

Press the operation mode selector button of the controller that
you wish to designate as the master remote controller. Then
designation is completed. This remote controller is designated
as the master remote controller and the display showing 
(change-over under centralized control) vanishes.

The displays of other remote controllers show 

 (change-

over under centralized control).

6.5.

Precautions for group control system or two 
remote controller control system

This system provides two other control systems beside individual
control (one remote controller controls one indoor unit) system.
Confirm the following if your unit is of the following control system
type.

Group control system
One remote controller controls up to 16 indoor units. All indoor
units are equally set.

Two remote controller control system
Two remote controllers control one indoor unit (in case of group
control system, one group of indoor units). The unit is
individually operated.

7.

E

NERGY

 

SAVING

 

AND

 

OPTIMUM

 

OPERATION

Observe the following precautions to ensure the system operates
properly.

Adjust the air outlet properly and avoid direct air flow to room
inhabitants.

Adjust the room temperature properly for a comfortable environ-
ment. Avoid excessive heating or cooling.

Prevent direct sunlight from entering a room during cooling
operation by using curtains or blinds.

Ventilate often.
Extended use requires special attention to ventilation.

Keep doors and windows closed. If the doors and windows
remain open, air will flow out of your room causing a decrease in
the cooling or heating effect.

Be careful not to cool or heat too much. To save energy, keep
the temperature setting at a moderate level.

Never place objects near the air inlet or the air outlet of the unit.
It may cause deterioration in the effect or stop the operation.

Turn off the main power supply switch to the unit when the unit is
not used for longer periods of time. If the switch is on, it uses
electricity. Before restarting the unit, turn on the main power
supply switch 6 hours before operation to ensure smooth
running. (Refer to "Maintenance" in the indoor unit manual.)

When the display shows 

 (time to clean the air filter), ask a

qualified service person to clean the filters. (Refer to
"Maintenance" in the indoor unit manual.)

Keep the indoor unit and remote control at least 1 m away from
televisions, radios, stereos, and other similar equipment.
Failing to do so may cause static or distorted pictures.

Do not place items under the indoor unit which may be damaged
by water.
Condensation may form if the humidity is above 80% or if the
drain outlet gets blocked.

COOLING

HEATING

• When the room temperature is lower than 

the set temperature.

• When starting operation.

• When the room temperature is higher 

than the set temperature.

• At defrost operation.

• When operating continuously at horizontal air flow direction.
• When continuous operation with downward air flow is performed at the time of cooling with a 

ceiling-suspended or a wall-mounted unit, the microcomputer may control the flow direction, 
and then the remote control indication also will change.

NOTE

The movable limit of the flap is changeable.
Contact your dealer for details. (Only for Double-
flow, Multi-flow, Corner, Ceiling-suspended and
Wall-mounted.)

Avoid operating in the horizontal direction
"

". It may cause dew or dust to settle on the

ceiling.

1

2

NOTE

Contact your dealer in case of changing the
combination or setting of group control and two remote
controller control systems.

Recommended temperature setting

For cooling

26~28°C

For heating

20~24°C

Summary of Contents for RXQ5M7W1B

Page 1: ...9W1B RXYQ10M9W1B RXYQ12M9W1B RXYQ14M9W1B RXYQ16M9W1B RXYQ18M9W1B RXYQ20M9W1B RXYQ22M9W1B RXYQ24M9W1B RXYQ26M9W1B RXYQ28M9W1B RXYQ30M9W1B RXYQ32M9W1B RXYQ34M9W1B RXYQ36M9W1B RXYQ38M9W1B RXYQ40M9W1B RXY...

Page 2: ...2 3 1 1 4 3 2 3 1 3 1 2 1 1 5 3 5 2 4 6 UNIT NO 1 2 3 4 2 1 2 7 Ceiling Suspended Wall Mounted Double flow Multi flow Corner 8 RXYSQ RXYQ 1 1 4 4 3 2 6 7 5 5 REYQ 1 RXYSQ RXYQ 1 5 5 4 3 2 4 7 1 5 5 4...

Page 3: ...y for future reference WARNING Improper handling can lead to such serious consequences as death severe injury or damage to the equipment NOTE These instructions will ensure proper use of the equipment...

Page 4: ...door unit It may cause incomplete combustion or deformation of the unit due to the heat Do not allow a child to mount on the outdoor unit or avoid placing any object on it Falling or tumbling may resu...

Page 5: ...rt automatically after the power turns back on again 6 1 Cooling heating fan only and automatic operation See figure 3 and figure 4 1 Changeover cannot be made with a remote controller whose display s...

Page 6: ...dry operation Press the on off button The operation lamp lights up and the system starts operation Press the air flow direction adjust button Only for Double flow Multi flow Corner Ceiling suspended a...

Page 7: ...ller control system Two remote controllers control one indoor unit in case of group control system one group of indoor units The unit is individually operated 7 ENERGY SAVING AND OPTIMUM OPERATION Obs...

Page 8: ...he power is turned on The micro computer is getting ready to operate Wait 10 minutes Symptom 4 The fan strength does not correspond to the setting The fan strength does no change even if the fan stren...

Page 9: ...e power If the display the unit number and the operation lamp flash and the malfunction code appears See figure 6 Measure Notify your dealer and report the malfunction code If the system does not prop...

Page 10: ...ong sites with 24 hour air conditioning Recommended replacement cycle of wear parts Table 2 Replacement Cycle list Contact your dealer for details Moving and discarding the unit Contact your dealer fo...

Page 11: ...NOTES NOTES...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN16234 1C...

Reviews: