SiAF341904E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
111
1.2 List of Field Settings for Indoor Unit
: Factory setting
Mode
No.
(
2
)
First
Code
No.
Description
Second Code No.
01
02
03
04
10 (20)
0
Filter cleaning
sign interval
Long life filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Ultra long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard filter
Approx.
200
hrs.
Approx.
100
hrs.
1
Filter type
Long life filter
Ultra long life
filter
—
—
2
Remote controller thermistor
Remote
controller
ther
Suction air
thermistor
Only suction air
thermistor
Only remote
controller
thermistor
—
3
Filter cleaning sign
Displayed
Not displayed
—
—
6
Remote controller thermistor
control during group control
Not permitted
Permitted
—
—
7 (
6) Time for absence area detection
30 minutes
60 minutes
—
—
10 (
7)
Dry operation time during Eco
mode
30 minutes
60 minutes
90 minutes
Continuous (not
returning to
cooling)
11
Low airflow setting when
thermostat OFF during Eco mode
Disabled
Enabled
—
—
11 (21)
6 (
6)
Setting the rate of human
detection
High sensitivity
Low sensitivity
Standard
sensitivity
Infrared
presence sensor
disabled
7
Airflow adjustment
OFF
Completion of
airflow
adjustment
Start of airflow
adjustment
—
8 (
6)
Compensating the temperature
around people
Suction air
temperature only
Priority given on
the suction air
temperature
Standard
Priority given on
the floor
temperature
12 (22)
0
Optional accessories output
selection (field selection of output
for adaptor for wiring)
Indoor unit
turned ON by
thermostat
—
Operation output
Error output
1
External ON/OFF input (Set when
ON/OFF is to be controlled from
outside.)
Forced OFF
ON/OFF control
External
protection device
input
—
2
Thermostat differential
changeover (Set when remote
sensor is to be used.)
1°C
0.5°C
—
—
5
Auto restart after power failure
reset
Not equipped
Equipped
—
—
6
Airflow setting when cooling
thermostat is OFF
LL tap
Set fan speed
—
—
11 (
6) Compensating the floor
temperature
4°C
2°C
0°C
–2°C
13 (23)
0
Ceiling height setting, Setting of
normal airflow
Refer to page 120.
1
Airflow direction setting (Set when
a sealing material kit has been
installed)
F (4 directions)
T (3 directions)
W (2 directions)
—
2 (
6)
Swing pattern settings
All direction
synchronized
swing
—
Facing swing
—
4
Airflow direction adjustment range
Refer to page 122.
6
External static pressure settings
Refer to page 122.
7
Setting of swing patterns when
cooling thermostat is OFF
Refer to page 123.
13
Setting of circulation airflow
Disabled
Enabled
—
—
14
Circulation airflow patterns
Pattern 1
Pattern 2
Pattern 3
Pattern 4
15
Switching panel type
Standard panel
Designer panel
—
—