Field Settings for Indoor Unit
SiAF341904E
122
Part 5 Field Settings and Test Operation
Note(s)
1.4.19 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
1. Some indoor unit models are not equipped with draft prevention (upward) function.
2. When the model FXFSQ is attached with a closing member kit, set the Second Code No. to
02
or
03
.
1.4.20 External Static Pressure Settings
FXMQ-PB
: Factory setting
1 FXMQ40PB cannot be set to 180 or 200 Pa.
2 FXMQ50/63/80/100/125PB cannot be set to 30 Pa.
3 FXMQ140PB cannot be set to 30 Pa and 150-200 Pa.
FXFSQ-AR, FXAQ-P
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
4
01
Draft prevention (upward)
02
Standard
03
Ceiling soiling prevention (downward)
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
6
01
30 Pa (
2) (
3)
02
50 Pa
03
60 Pa
04
70 Pa
05
80 Pa
06
90 Pa
07
100 Pa
08
110 Pa
09
120 Pa
10
130 Pa
11
140 Pa
12
150 Pa (
3)
13
160 Pa (
3)
14
180 Pa (
1) (
3)
15
200 Pa (
1) (
3)