(2) To avoid the risk of oil detention in the stopping unit, always connect the shutoff valve
and the piping between outdoor units as shown in the figure A or figure B.
(3) If the piping length between the outdoor units exceeds 2 m, create a rise of 200 mm or
more in the gas line under a length of 2 m from the outdoor unit multi connection piping
kit.
A
B
A
B
Front connections
Side (bottom) connections
Prohibited pattern
Oil remains in the stopping outdoor unit.
Change to pattern 1 or pattern 2
Front connections
Side (bottom) connections
to indoor unit
to indoor unit
Unit A
Unit B
Unit A
Unit B
to indoor unit
to indoor unit
to indoor unit
Oil remains in the outdoor unit B when the system stops.
Change as shown in the figure below.
Rising height:
200 mm or more
to indoor
unit
to indoor unit
to indoor unit
If less than 2m
If 2 m or more
2m or more
less than 2m
less than 2m
Outdoor unit gas pipe
Outdoor unit gas pipe
Rising height:
200 mm or more