Appendix
SiEN34-705
186
General Information
RXYQ14PY1, RXYQ16PY1, RXYQ18PY1
RXYQ14PYL, RXYQ16PYL, RXYQ18PYL
3D050456H
NOTE)4
NOTE)5
Printed circuit board (Main)
Printed circuit board (Noise filter)
Printed circuit board (INV)
Printed circuit board (FAN)
Printed circuit board (ABC I/P)
Printed circuit board (Current sensor)
Push button switch
(Mode, set, return, test, reset)
Capacitor
Capacitor
DIP switch
Crankcase heater
Fuse (8A, DC650V) (A4P,A8P)
Fuse (T, 3.15A, 250V) (A1P)
Fuse (T, 6.3A, 250V) (A2P)
Pilotlamp (Service monitor-orange)
[H2P] Prepare, test ------------------Flickering
Malfunction detection---------Light up
Pilotlamp (Service monitor-green)
Magnetic relay
Magnetic contactor (M1C)
Magnetic contactor (M2C)
Magnetic relay (K2M, K3M)
Magnetic relay (Y1S)
Magnetic relay (Y2S)
Magnetic relay (Y3S)
Magnetic relay (E1HC)
Magnetic relay (E2HC)
Magnetic relay (E3HC)
Reactor
Motor (Compressor)
Motor (Fan)
Switching power supply (A1P,A3P)
Phase reversal detect circuit
Resistor (Current sensor) (A4P, A8P)
Resistor
Resistor (Current limiting)
Thermistor (Air) (A1P)
Thermistor (Fin) (A3P)
Thermistor (Suction)
Thermistor (M1C~3C Discharge)
Thermistor (Heat exc. deicer)
Thermistor (Heat exc. outlet)
Thermistor (Liq. pipe)
Thermistor (Accumulator)
Pressure sensor (high)
Pressure sensor (low)
Pressure switch (high)
Current sensor (A6P, A7P)
Safety devices input
Power module (A3P,A4P,A8P)
Diode bridge (A3P)
Connector (M1F, M2F)
Terminal strip (Power supply)
Terminal strip (Control) (A1P)
Terminal strip (ABC I/P) (A5P)
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
Solenoid valve (Hot gas)
Solenoid valve (Oil)
Solenoid valve (4 way valve)
Noise filter (Ferrite core)
Noise filter (With surge absorber)
Selector switch (Fan/Cool • Heat)
Selector switch (Cool/Heat)
A1P
A2P
A3P
A4P,A8P
A5P
A6P, A7P
BS1~5
C1
C63,C66
DS1,DS2
E1HC~E3H
F1U
F1U,F2U
F400U
H1P~8P
HAP
K1,K3
K2,K4
K2M, K3M
K1R, K2R
K3R
K4R
K5R
K7R
K8R
K9R
L1R
M1C~M3C
M1F,M2F
PS
Q1RP
R10
R50, R59
R95
R1T
R1T
R2T
R31T,R32T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
S1PH3~PH
T1A
V1CP
V1R
V2R
X1A~4A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~7C, Z9C
Z1F
Cool/Heat selector
S1S
S2S
L3-BLK
L2-WHT
L1-RED
N-BLU
Outdoor (F1) (F2)
Outdoor (Q1) (Q2)
Is connector color for printed circuit
board.
Is connector color for component.
Is discrimination color for component
lead wire.
(BACK)
(FRONT)
C/H SELECTOR
COOL
HEAT
COOL HEAT
FAN
EL.COMPO.BOX
EL.COMPO.BOX
TO IN/D UNIT
TO OUT/D UNIT
TO MULTI UNIT
POWER SUPPLY
Y1: 380-415V 3N~50Hz
YL: 380V
3N~60Hz
TERMINAL OF M1C, M1F
LAYOUT OF M1C~M3C, M1F, M2F
OUTER SHELL
Indoor (F1) (F2)
Cool/Heat Selector (Optional accessory)
C/H SELECTOR
Notes
1. This wiring diagram is applied only to the outdoor unit.
2. :
Field
wiring.
3. :
Terminal strip,
: Connector
:Terminal
:Protective earth (screw)
4. When using the optional adapter, refer to the installation manual of the optional adapter.
5. For connection wiring to indoor-outdoor transmission F1 • F2, outdoor-outdoor transmission F1 • F2, Outdoor-Multi transmissi
on Q1 • Q2 ,
refer to the installation manual.
6. How to use BS1~5 and DS1~3 switch, refer to “service precaution” label on EL. COMPO. BOX COVER.
7. When operating, don’t shortcircuit the protection device (S1PH~S3PH).
8. Colors (BLK: Black, RED: red, BLU: blue, WHT: white, PNK:Pink, YLW: Yellow, BRN: brown, GRY: gray, GRN: green, ORG: 0range.