CAUTION

When connecting the connection wires to the terminal board 

• 

using a single core wire, be sure to perform curling. 
Problems with the work may cause heat and 

fi

 res. 

Strip wire end 
to this point.

Excessive strip length 

may cause electrical 

shock or leakage.

Good

Wrong

Pull the wire and make sure that it does not disconnect. Then 

fi

 x the wire in place with a wire stop. 

3) 

Facility Setting 
(cooling at low outdoor temperature)

This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). 
Never use it in a residence or of

fi

 ce (the space where there is a human).

Cutting jumper 6 (J6)

 

„

 on the circuit board will expand the operation range down to 5°F (–15°C). However it will stop if the 

outdoor temperature drops below –4°F (–20°C) and start back up once the temperature rises again.

Remove the 3 screws on the side and remove the top plate of the outdoor unit. 

1) 

Remove the drip proof cover. 

2) 

Cut the jumper (J6) of the PCB inside. 

3) 

J5

J7

J8

J6

GND

Top plate

PCB

Drip proof cover

1) Remove the 

3 screws.

2) Remove the drip 

proof cover.

3) Cut jumper J6.

  

CAUTION

If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.

• 

Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.

• 

Do not place humidi

fi

 ers or other items which might raise the humidity in rooms where facility settings are being used. 

• 

A humidi

fi

 er might cause dew jumping from the indoor unit outlet vent.

Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.

• 

Stripping wire at terminal block

01_EN_3P273470-2.indd   11

01_EN_3P273470-2.indd   11

1/6/2011   12:04:49 PM

1/6/2011   12:04:49 PM

Summary of Contents for RXN15KEVJU

Page 1: ...nstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXN15KEVJU RKN15KEVJU RXN18KEVJU RKN18KEVJU RXN24KEVJU RKN24KEVJU 00_CV_3P273470 2 i...

Page 2: ...not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk of explosion resulting i...

Page 3: ...nd fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open flames If the gas l...

Page 4: ...10ft 3m away depending on radio wave conditions In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 8 Since drain flows out of t...

Page 5: ...height Min allowable length Max allowable length 98 4ft 30m 4 92ft 1 5m 65 6ft 20m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 1 2 inch 12 7mm 0 21oz ft 20g m Additional refrigerant required for refr...

Page 6: ...urely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their leng...

Page 7: ...damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 1 2 inch 12 7mm 36 5 44 5ft lbf 49 5 60 3N m Valve cap tightening...

Page 8: ...1MPa 1 3 Close gauge manifold s low pressure valve Lo and stop vacuum pump 4 Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back 2 Remove caps...

Page 9: ...ending Selection of copper and heat insulation materials 7 2 When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam 1 Heat transfer rate 0 041 to 0...

Page 10: ...operation to stop press the indoor unit ON OFF switch Using the indoor unit s remote controller Press MODE button and select the cooling mode 1 Press ON OFF button to turn on the system 2 Press both o...

Page 11: ...o tighten the screws Work before wiring A protection plate is fixed for protection from the high voltage section Before staring wiring work dismount the protection plate by removing the 2 screws and d...

Page 12: ...start back up once the temperature rises again Remove the 3 screws on the side and remove the top plate of the outdoor unit 1 Remove the drip proof cover 2 Cut the jumper J6 of the PCB inside 3 J5 J7...

Page 13: ...ion in accordance with the operation manual to ensure that all functions and parts 1 3 such as fin movement are working properly The air conditioner requires a small amount of power in its standby mod...

Page 14: ...3P273470 2 M10B141 1102 HT Two dimensional bar code is a code for manufacturing 00_CV_3P273470 2 indd 2 00_CV_3P273470 2 indd 2 12 15 2010 2 29 23 PM 12 15 2010 2 29 23 PM...

Reviews: