![background image](http://html1.mh-extra.com/html/daikin/rxmq4pve/rxmq4pve_service-manual_2459928022.webp)
Procedure to Remove Compressor
Si341211
20
Removal Procedure
7. Procedure to Remove Compressor
Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
Remove the outside
panels, electrical
component, and
compressor fixing panel,
according to the
"Procedure to Remove
Outside Panels"
1. Pull off the lead wire of
compressor.
1
Open upward the sound
insulation for the
terminal cover.
2
Remove the terminal
cover with a minus
driver, etc.
3
Remove the terminals
for the compressor with
a round nose chain
pliers with side cutters,
etc.
Terminal cover
Sound insulation for the terminal cover
Red color: S
White color: Blank
Blue color: N
Lead wire to the compressor