background image

29

English

 NOTE

•  If the power of some units is turned off, the charging procedure can-

not be finished properly.

• 

In case of a multiple outdoor system, turn on the power of all out

-

door units.

•  Make sure to turn ON the power 6 hours before starting the opera-

tion. This is necessary to warm the crankcase by the electric heater.

•  If operation is performed within 12 minutes after the indoor and 

outdoor units are turned on, the compressor will not operate before 
the communication is established in a correct way between outdoor 
unit(s) and indoor units.

• 

Before starting charging procedures, check if the segment display 
indication of the main printed circuit board (A1P) is as normal (see 
functions of the push button switches which are located on the main 
printed circuit board (A1P) on page 24). If a malfunction code is 
present, see 15.5. Malfunction code list on page 40.

• 

Make sure all connected indoor units are recognized (see 

 

15.2. Monitoring function and field settings on page 31).

• 

Close the front panel before any refrigerant charge operation is 
executed. Without the front panel attached the unit cannot judge 
correctly whether it is operating properly or not.

14.3.2.  Charging method

As explained during vacuum drying method, once vacuum drying is 
finished, additional refrigerant charging can start. 

A flow chart is available which gives an overview of the possibilities 
and actions to be taken (see 14.3.1. Flow chart on page 28).

To speed up the process of pre-charging refrigerant for large systems, 
it is recommended to first charge a portion of the refrigerant before 
performing refrigerant charging operation of outdoor unit. This step is 
included in below procedure. This step can be skipped, but charging 
will take longer in such a case.

Follow the steps as described below.

Calculate the additional amount of refrigerant to be added using 
the formula mentioned in 14.2. Calculating the additional refriger

-

ant charge on page 26.

The first 22 lbs. (10 kg) of additional refrigerant can be charged 
without outdoor unit operation.
If the additional refrigerant amount is smaller than 22 lbs. (10 kg), 
perform the pre-charging procedure as explained in step 3 and 4a 
below.
If the additional refrigerant charge is larger than 22 lbs. (10 kg), 
perform step 3 till the end of the procedure.

Pre-charging can be done without compressor running by con

-

necting the refrigerant tank only to the liquid stop valve service port 
(open valve C). Make sure that all outdoor unit stop valves, as well 
as valves A and C are closed.

1

2

3

4

5

6

B
C

9

8

10

10

11

13

12

14

15

A

7

Pressure reducing valve

2  Nitrogen

Measuring instrument

Refrigerant R410A tank (siphon system)

5  Vacuum pump
6  Charge hose
7  Refrigerant charge port

8  Gas pipe stop valve

Liquid pipe stop valve

10

Outdoor unit

11

To indoor unit

12 

Stop valve

13  Field piping

14 

Gas flow

15 

Stop valve service port

Valve A

Valve B

Valve C

a)  If the calculated additional refrigerant amount is reached by 

above pre-charging procedure, close valve B.

b)  If the total amount of refrigerant could not be charged by pre

-

charging, then close valve B and go to step 5. 

 INFORMATION

If the total additional refrigerant amount was reached in step 4 (by 
pre-charging only), record the amount of refrigerant that was added 
on the additional refrigerant charge label provided with the unit and 
attach it on the back side of the front panel. Perform the test procedure 
as described in 15.4. Test operation on page 39.

After pre-charging, perform the refrigerant charge operation as 

shown below and charge the remaining refrigerant of the additional 
charging amount through valve A.
Open all outdoor units stop valves. Valves A, B and C must remain 
closed!

 NOTE

• 

The refrigerant charging port is connected to the piping inside the 
unit. The unit’s internal piping is already factory charged with refrig

-

erant, so be careful when connecting the charge hose.

• 

After adding the refrigerant, do not forget to close the cover of the 
refrigerant charging port. The tightening torque for the cover is 8.48 
to 10.3 ft

lbf (11.5 to 13.9 N

m).

• 

In order to ensure uniform refrigerant distribution, it may take the 
compressor ±10 minutes to start up after the unit has started opera

-

tion. This is not a malfunction.

The remaining additional refrigerant charge can be charged by 
operating the outdoor unit by means of the refrigerant charge 

operation mode:

• 

Turn on the power of the indoor units and outdoor unit.

• 

Take all the precautions mentioned in 

start-up and configura

-

tion

 into account.

• 

Activate outdoor unit setting [2-20]=1 to start refrigerant charge 
mode. Refer to page 32 for details.

Result: 

The unit will start operation. Valve A can be opened.

Charging of remaining additional refrigerant can be done.
When the remaining calculated additional refrigerant amount is 
added, close valve A and push BS3 to stop the refrigerant charg

-

ing procedure.

01_EN_03_3P734038-3.indd   28

01_EN_03_3P734038-3.indd   28

2023/05/29   15:39:23

2023/05/29   15:39:23

Summary of Contents for RXLQ72TBTJ Series

Page 1: ...the event of conflicting information the online instructions are to be used Veuillez visiter http www daikinac com content resources manuals pour obtenir la version la plus r cente des instructions d...

Page 2: ...manual Improper installation could result in water leakage electric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allow abl...

Page 3: ...ation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist...

Page 4: ...17 9 Field wiring 18 9 1 Power circuit safety device and cable requirements 19 9 2 Wiring connection example for whole system 19 9 3 Leading wire procedure 19 9 4 Transmission wiring connection proce...

Page 5: ...d 72 96 120 RXLQ72TBTJ TBYD TBYC 1 RXLQ96TBTJ TBYD TBYC 1 RXLQ120TBTJ TBYD TBYC 1 RXLQ144TBTJ TBYD TBYC 2 RXLQ192TBTJ TBYD TBYC 2 RXLQ240TBTJ TBYD TBYC 2 To install the outdoor unit the following acce...

Page 6: ...0TBYC 144TBYC 192TBYC 240TBYC Max Number of Connectable Indoor Units 12 16 20 25 33 41 Note Values inside brackets are based on connection of indoor units rated at maximum capacity 200 for single outd...

Page 7: ...he unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance and servic ing refer to 5 2 Serv...

Page 8: ...lt in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will disturb the operation of the unit...

Page 9: ...the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A B 1 a 3 8 10 b 11 3 4 300 c...

Page 10: ...ngineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carrier s claims agent 6 2 Han...

Page 11: ...gth remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the case of the multi system Se...

Page 12: ...ng work is complete do not under any circumstances open the stop valve until 9 Field wiring on page 18 and 12 Checking of device and installation conditions on page 24 are complete Do not use flux whe...

Page 13: ...72 3 4 in 19 1 mm 72 111 7 8 in 22 2 mm 111 162 1 1 8 in 28 6 mm 1 2 in 12 7 mm 162 230 5 8 in 15 9 mm 230 300 1 3 8 in 34 9 mm 3 4 in 19 1 mm 300 1 5 8 in 41 3 mm Example Downstream capacity for C ca...

Page 14: ...erning REFNET headers choose from the following table in accordance with the total capacity of all the indoor units connected after the REFNET header Indoor unit capacity index Kit name 72 KHRP26M22H9...

Page 15: ...623 ft 2 190 m Total piping length 1640 ft 500 m Example 1 1 a b c d e f g h i j k l m n p 1640 ft 500 m Example 2 1 a b c d e f g h i j k l m n p 1640 ft 500 m Example 1 2 a b c d e f g h i j k 1640...

Page 16: ...n the pipe size of the main pipe then the pipe size of the main pipe has to be increased as well Increase the pipe size as follows f3 8 f1 2 f1 2 f5 8 f5 8 f3 4 f3 4 f7 8 f7 8 f1 3 f1 1 8 f1 1 4 3 f1...

Page 17: ...m ad versely affects valves and compressors in the refrigerating system and prevents proper operation The Dry Nitrogen pressure should be set to 2 9 psi 0 02 MPa i e just enough so it can be felt on t...

Page 18: ...alve Protective plate Stop valves mounting plate 5 Cut off the lower part of the smaller pinched piping with an ap propriate tool such as pipe cutters Let the remaining oil drip out in case the recove...

Page 19: ...ping between outdoor units multiple outdoor units system To connect the piping between outdoor units an optional multi connection piping kit BHFP22P100U BHFP22P100UA is always required When installing...

Page 20: ...eader so that it branches horizontally 2 Installation of the multi connection piping kit 1 B 1 C D 15 15 A C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the joints horizontally so that the caution la...

Page 21: ...e Check for refrigerant leaks after tightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec trician and must comply with relevant loc...

Page 22: ...8 16 AWG18 16 RXLQ72TBYD RXLQ96TBYD RXLQ120TBYD RXLQ144TBYD RXLQ192TBYD RXLQ240TBYD f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 460V 460V 460V 460V 460V 460V 28 1 39 8 43 4 28 1 28 1 39 8 39 8 43...

Page 23: ...erating the printed circuit board A1P of Master unit NOTE Do not connect the power wiring to terminals for the transmission wiring Doing so would destroy the entire system Wiring to the indoor unit sh...

Page 24: ...use crimp style terminal with insulating sleeves for con nections See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated power wire and connect firmly th...

Page 25: ...nd vacuum drying After finished piping work carry out air tight test and vacuum drying NOTE Always use nitrogen gas for the air tightness test Absolutely do not open the stop valve until the main powe...

Page 26: ...00 microns vacuum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to 500 microns within 2...

Page 27: ...ccess you can remove the service window cover see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven segment displays and DIP switch...

Page 28: ...cted to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will return to the default situation...

Page 29: ...t charge the refrigerant more than the specified amount This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths systems require additional charg ing of refri...

Page 30: ...Q120TBYC RXLQ120TBYC Indoor units FXMQ type 18 1 24 1 30 1 36 2 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft e f1 4 15 ft i f3 8 20 ft m f3 8 15 ft r f1 2 10 ft b f5 8 20 ft f f3 8 10 ft j f3...

Page 31: ...use the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not If a siphon tube is equipped change t...

Page 32: ...liquid stop valve service port open valve C Make sure that all outdoor unit stop valves as well as valves A and C are closed 1 2 3 4 5 6 B C 9 8 10 10 11 13 12 14 15 A 7 1 Pressure reducing valve 2 N...

Page 33: ...the refrigerant Operating with the stop valves closed will damage the compressor 15 Start up and configuration INFORMATION It is important that all information in this chapter is read sequentially by...

Page 34: ...low noise operation based on an external input For this operation an optional acces sory is required 1 2 shows the status of power consumption limitation operation 1 unit is currently operating under...

Page 35: ...nal external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increase the static pressure the outdoo...

Page 36: ...tions this setting activates and defines the level power consumption limitation that will be applied continuously The level is according to the table Default value 0 OFF Value 2 32 Restriction referen...

Page 37: ...demand Note The setting of 2 86 2 saves energy but may increase the time required to reach set point 2 89 Intermittent fan operation Default value 0 Value 2 89 Intermittent fan operation 0 OFF 1 30 m...

Page 38: ...ut door unit coil sensor VRV IV HR VRV S and VRV Aurora series HR can also be programed to automatically switch to emergency heat if there is a system fault Item Description Min Max Increments Heat Pu...

Page 39: ...l automatically be set This will allow the auxiliary or secondary heat source to be automatically energized in the event of a system failure Error codes capable of auto backup are listed in the table...

Page 40: ...feeling for the customer The selection method of indoor units is important and has to be considered as the available capacity is not the same as under basic operation For details concerning to Hi sens...

Page 41: ...t from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up condition is different from the po...

Page 42: ...ectrical wiring air purge etc See installation manual of the indoor units for details CAUTION Do not insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high...

Page 43: ...buttons and DIP switches on the printed circuit board on page 24 Push BS2 for 5 seconds or more The unit will start test operation The test operation is automatically carried out the outdoor unit dis...

Page 44: ...actuator 31 36 Electronic expansion valve malfunction 208 230 460V Y6E A6P X10A 575V Y6E A7P X10A Check connection on printed circuit board or actuator 32 37 Electronic expansion valve malfunction 208...

Page 45: ...ck connection on printed circuit board or actuator LC 14 15 Transmission trouble 208 230 460V A3P X6A A1P X28A 575V A4P X6A A1P X28A Check connection 19 20 Transmission trouble 208 230 460V A5P X3A A3...

Page 46: ...smission wired unit amount matches with powered unit amount by monitor mode or wait till initialization is finished UF 01 Auto address malfunction inconsistency Check if transmission wired unit amount...

Page 47: ...s due to strong wind it may store electricity in the capacitor or in the main circuit and cause electric shock 5 After the service is finished plug the junction connector back in Otherwise the malfunc...

Page 48: ...system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant and the calculation of the maxi mum concentration of refr...

Page 49: ...3P734038 3 EM23A009 2311 SP Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P734038 3 indd 2 00_CV_3P734038 3 indd 2 2023 05 29 15 36 59 2023 05 29 15 36 59...

Reviews: