English

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

Forced cooling operation

Using the indoor unit ON/OFF switch

Press the indoor unit ON/OFF switch for at least 5 seconds. (Operation will start.)

• Forced cooling operation will stop automatically after about 15 minutes. 

 

To stop the operation, press the indoor unit ON/OFF switch.

Using the indoor unit’s remote controller

1) Press “MODE” button and select the cooling mode. 
2) Press “ON/OFF” button to turn on the system.
3) Press both the “TEMP” button and “MODE” button at the same time. 
4) Press “MODE” button twice. ( 

 will be displayed and the unit will 

enter forced cooling operation.) 

• Forced cooling operation will stop automatically after about 

30 minutes. To stop operation, press “ON/OFF” button.

Using the outdoor unit forced cooling operation switch 

Forced cooling operation can be performed when the outdoor unit forced 
cooling operation switch is pressed within 3 minutes after power is 
supplied.

 

Push on the area marked “

” (SW1) with a screwdriver and the 

operation will start.

• Forced cooling operation will stop automatically after approximately 

15 minutes.

 

To stop the operation, press the switch (SW1).

Wiring

 WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical 

shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leak detector. (One that can handle higher harmonics.)

 

(This unit uses an inverter, which means that an earth leak detector capable of handling higher harmonics must be used, 
in order to prevent malfunctioning of the earth leak detector itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Equipment complying with EN61000-3-12

(1)

• Do not turn ON the power supply until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the 

indoor and outdoor units so that the terminal 
numbers match. Tighten the terminal screws 
securely. We recommend a flathead 
screwdriver be used to tighten the screws. 

*DV VWRS YDOYH

9DOYH FDS

+H[DJRQDO ZUHQFK

&ORVH

/LTXLG VWRS YDOYH

6HUYLFH SRUW

1

2

3

Forced cooling operation switch (SW1)

Push

1
2
3

1 2 3

L N

Fuse
20 A

Earth leakage 
circuit breaker

Earth

When wire length exceeds 
10m, use 2.0mm diameter wires.

H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power
supply
50Hz 220-240V 

Firmly fix the wires with 
the terminal screws.

Use 2.0mm diameter wires.

Summary of Contents for RXLG50L2V1B

Page 1: ...INSTALLATION MANUAL R410A Split Series MODEL RXLG50L2V1B RXL50K2V1B RXL50J3V1B RXLG50K3V1B...

Page 2: ...y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo l Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pa...

Page 3: ...A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo l Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o p...

Page 4: ...blece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo l Certificato C 07 A B C 08 Nota tal como estabelecido em A...

Page 5: ...abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Impr...

Page 6: ...ot place under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temp...

Page 7: ...leveled Otherwise water leakage or pooling of water may occur Foot bolt hole centres 580mm 120mm From unit s side Max allowable height Min allowable length Max allowable length 20m 1 5m 15m Liquid pi...

Page 8: ...fix the unit securely by means of the foundation bolts Prepare four sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bol...

Page 9: ...torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fu...

Page 10: ...n side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressu...

Page 11: ...ng and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation...

Page 12: ...imately 15 minutes To stop the operation press the switch SW1 Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical sh...

Page 13: ...terminals on the wires up to the covered part and secure in place Ground terminal installation Use the following method when installing the round crimp style terminal CAUTION When connecting the conne...

Page 14: ...PAN HEATER Drain pan heater C7 C8 Capacitor DB1 DB3 Diode bridge FU1 FU2 FU3 FU4 FU5 Fuse FU6 Field fuse IPM Intelligent power module L Live L803 L804 Reactor M1C Compressor motor M1F Fan motor MRCW...

Page 15: ...1 3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amoun...

Page 16: ...3P327449 5H 2013 12 Copyright 2013 Daikin...

Reviews: