Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a hexagonal wrench.
4) After two to three minutes, close the gas stop valve and stop forced cooling operation.

Forced cooling operation

Using the indoor unit ON/OFF button 

Press the indoor unit ON/OFF button for at least 5 seconds. (Operation will start.)

• Forced cooling operation will stop automatically after about 15 minutes. 

 

To force a trial operation to stop, press the indoor unit ON/OFF button.

Using the main unit’s remote controller

1) Press the “ON/OFF” button. (Operation will start.)
2) Press the “TEMP” button and the “MODE” button at the same time.
3) Press the “MODE” button twice.

 

(“

” will be displayed and the unit will enter trial operation.)

4) Press the “MODE” button to return the operation mode to cooling.

• Trial operation will stop automatically after about 30 minutes. To force a trial 

operation to stop, press the “ON/OFF” button.

Using the outdoor unit forced cooling operation switch (with standby 
electricity saving function turned OFF)

1) Push on “

” with a screwdriver. The unit will start operating.

2) The forced cooling mode is selected, and terminates in approx. 15 minutes.

 CAUTION

1) When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
2) After closing the liquid stop valve, close the gas stop valve within three minutes, then stop the forced operation.

Facility Setting 

(RXL25/RXL20/RXL35K2V1B only)

 

(cooling at low outdoor temperature)

This function is designed for facilities such as equipment or computer rooms. It is never to be used in a residence or 
office where people occupy the space.

1) Cutting jumper 4 (J4) on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor 

temperature drops below –20°C and start back up once the temperature rises again.

 CAUTION

1) If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
2) Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
3) Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used. 

 

A humidifier might cause dew jumping from the indoor unit outlet vent.

4) Cutting jumper 4 (J4) sets the indoor fan tap to the highest position. Notify the user about this.

Gas 
stop valve

Valve cap

Hexagonal 
wrench

Close

Liquid 
stop valve

1

2

3

The selective connector for standby electricity 
saving in use (with standby electricity saving 
function turned OFF)

Push here

Screwdriver

Power supply
terminal block

1

2

3

S70

S40

S2

S90

J5

J4

J3

Cut J4 with nippers 
or a similar tools.

Summary of Contents for RXLG25L2V1B RXLG35L2V1B

Page 1: ...INSTALLATION MANUAL R410A Split Series MODEL RXLG25L2V1B RXLG35L2V1B RXL35K2V1B RXL25J3V1B RXL35J3V1B RXL20K3V1B RXL25K3V1B RXLG25K3V1B RXLG35K3V1B...

Page 2: ...y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo l Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o par...

Page 3: ...A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo l Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o p...

Page 4: ...o positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo l Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positiv...

Page 5: ...abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Impr...

Page 6: ...not place under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient tem...

Page 7: ...top valve cover into the outdoor unit to install Tighten the screws Stop valve cover O D 9 5mm Gas pipe Liquid pipe O D 6 4mm 20g m 15m 20m Max allowable length Max allowable height Additional refrige...

Page 8: ...fix the unit securely by means of the foundation bolts Prepare four sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bol...

Page 9: ...orque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them ful...

Page 10: ...n side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressu...

Page 11: ...id piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insu...

Page 12: ...n 1 Check that the main power supply is turned OFF Turn it OFF if has not been turned OFF 2 Remove the stop valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn ON th...

Page 13: ...AUTION 1 When pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock 2 After closing the liquid stop valve close the gas stop valve within three...

Page 14: ...notes mentioned below when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply terminal board...

Page 15: ...5 C6 C119 Capacitor DB1 DB2 DB3 Diode bridge E1H Heater FU1 FU2 FU3 FU4 FU5 Fuse FU6 Field fuse IPM1 IPM2 Intelligent power module L Live L1 Coil L1R Reactor M1C Compressor motor M1F Fan motor MRCW MR...

Page 16: ...requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the ci...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P291651 8R 2013 12 Copyright 2013 Daikin...

Reviews: