■
English
4
En
gl
is
h
Installation Guidelines
• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Precautions on Installation
• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare four sets of M8 or M10
foundation bolts, nuts and washers each which are available on the market.)
• It is best to screw in the foundation bolts until their length are 20mm from the foundation surface.
Outdoor Unit Installation
1.
Installing outdoor unit.
1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Draw-
ings.”
More than 50
More than 100
Side view
1200
or less
More than 50
More than 50
Top view
More
than 100
Top view
Unit: mm
More than 150
More than 300
More than 50
Wall facing one side
Walls facing two sides
Walls facing three sides
More than 150
20
01_EN_3P232550-11C.fm Page 4 Thursday, September 16, 2010 11:39 AM