SiBE041401E
Troubleshooting
Service Diagnosis
68
Troubleshooting
Correct the power supply.
Replace the outdoor
unit PCB.
Check for such factors for a
long term.
(R19955)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
YES
YES
NO
YES
YES
Reconnect the harness.
Check the power supply voltage.
Check the connection of the
compressor harness.
Disturbance factors
∗
Noise
∗
Power supply distortion
(Precaution before turning on the power again)
Make sure the power has been off for at
least 30 seconds.
Replace the indoor
unit PCB.
Turn on
the power. System
restarted? (Repeat a few
times.)
Error
again
within
3 minutes
after turning on the
power?
Loose or
disconnected?
NO
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB.
Does the
outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the
rated value?
Summary of Contents for RXG20L2V1B
Page 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50 ...
Page 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944 ...
Page 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition ...