background image

Daikin Europe N.V. Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

Daikin Europe N.V. participates in the Eurovent Certifica-
tion programme for Liquid Chilling Packages (LCP), Air
handling units (AHU), Fan coil units (FCU) and variable
refrigerant flow systems (VRF) Check ongoing validity of
certificate online: www.eurovent-certification.com or us-
ing: www.certiflash.com

EEDEN

XXX-07/16

The present leaflet is drawn up by way of information only and does not constitute an offer binding
upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fit-
ness for particular purpose of its content and the products and services presented therein. Specifica-
tions are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or related to the use and/or inter-
pretation of this leaflet. All content is copyrighted by Daikin Europe N.V.

Summary of Contents for RXG-L

Page 1: ...Split Air Conditioning Technical Data RXG L...

Page 2: ......

Page 3: ...4 Capacity and Power input 5 Technical Specifications 5 Electrical Specifications 7 3 Electrical data 8 4 Capacity tables 10 Cooling Heating Capacity Tables 10 5 Dimensional drawings 17 6 Centre of g...

Page 4: ...tdoor units for pair application Outdoor units are fitted with a swing compressor renowned for its low noise and high energy efficiency Daikin outdoor units are neat sturdy and can easily be mounted o...

Page 5: ...0 1 Max kW 4 3 1 4 5 1 5 0 1 6 5 1 Btu h 14 600 1 15 400 1 17 100 1 22 200 1 kcal h 3 700 1 3 870 1 4 300 1 5 590 1 Power input Cooling Min kW 0 320 1 0 350 1 0 370 1 Nom kW 0 501 1 0 523 1 0 882 1 1...

Page 6: ...1 Max kW 4 5 1 4 3 1 5 0 1 6 5 1 Btu h 15 400 1 14 600 1 17 100 1 22 200 1 kcal h 3 870 1 3 700 1 4 300 1 5 590 1 Power input Cooling Min kW 0 320 1 0 350 1 0 370 1 Nom kW 0 523 1 0 501 1 0 882 1 1 3...

Page 7: ...3 4 2 4 5 2 5 8 2 Btu h 11 600 2 15 400 2 19 800 2 Max kW 4 5 5 0 8 1 Btu h 15 400 17 100 27 600 Power input Cooling Min kW 0 30 0 31 4 50 Nom kW 0 54 0 94 1 51 Max kW 0 79 1 15 2 00 Heating Min kW 0...

Page 8: ...38 3 cfm 932 1 352 Fan motor Model D23H 28 KFD 380 50 8C Output W 23 53 Speed Cooling High rpm 860 920 780 Super low rpm 780 670 Heating High rpm 860 720 Super low rpm 740 670 Sound power level Cooli...

Page 9: ...0L Power supply Name V1 Phase 1 Frequency Hz 50 Voltage V 220 240 Current 50Hz Maximum fuse amps MFA A 16 20 Current Nominal running current RLA Cooling A 2 68 2 2 58 3 2 48 4 2 78 2 2 68 3 2 58 4 4 8...

Page 10: ...Outdoor Unit RXG L 3 Split Sky Air RXG L 8 3 Electrical data 3 1 Electrical Data...

Page 11: ...3 3 Split Sky Air RXG L 9 Outdoor Unit RXG L 3 Electrical data 3 1 Electrical Data...

Page 12: ...Outdoor Unit RXG L 4 Split Sky Air RXG L 10 4 Capacity tables 4 1 Cooling Heating Capacity Tables dy s t Zy s dy s Zy s K K t s s E t t d t t W t d E...

Page 13: ...3 4 Split Sky Air RXG L 11 Outdoor Unit RXG L 4 Capacity tables 4 1 Cooling Heating Capacity Tables dy s t Zy s dy s Zy s K t K s s E t t d t t W t d E...

Page 14: ...Outdoor Unit RXG L 4 Split Sky Air RXG L 12 4 Capacity tables 4 1 Cooling Heating Capacity Tables dy s t Zy s dy s Zy s K t K s s E t t d t t W t d E...

Page 15: ...3 4 Split Sky Air RXG L 13 Outdoor Unit RXG L 4 Capacity tables 4 1 Cooling Heating Capacity Tables dy s t Zy s dy s Zy s K K t s s E t t d t t W t d E d d d...

Page 16: ...Outdoor Unit RXG L 4 Split Sky Air RXG L 14 4 Capacity tables 4 1 Cooling Heating Capacity Tables...

Page 17: ...3 4 Split Sky Air RXG L 15 Outdoor Unit RXG L 4 Capacity tables 4 1 Cooling Heating Capacity Tables...

Page 18: ...Outdoor Unit RXG L 4 Split Sky Air RXG L 16 4 Capacity tables 4 1 Cooling Heating Capacity Tables...

Page 19: ...3 5 Split Sky Air RXG L 17 Outdoor Unit RXG L 5 Dimensional drawings 5 1 Dimensional Drawings...

Page 20: ...Outdoor Unit RXG L 6 Split Sky Air RXG L 18 6 Centre of gravity 6 1 Centre of Gravity...

Page 21: ...3 7 Split Sky Air RXG L 19 Outdoor Unit RXG L 7 Piping diagrams 7 1 Piping Diagrams...

Page 22: ...Outdoor Unit RXG L 8 Split Sky Air RXG L 20 8 Wiring diagrams 8 1 Wiring Diagrams Single Phase...

Page 23: ...dB Sound pressure level dB Heating mode Legend Octave band centre frequency Hz Notes Cooling Heating Operating noise varies depending on operation and ambient conditions dBA A B dBA A B The operation...

Page 24: ...60 Hz JIS standard Background noise already taken into account Total dB Total dB Background noise already taken into account RXG35L 3D086901A 48 48 Location of microphone Measuring location anechoic...

Page 25: ...3 10 Split Sky Air RXG L 23 Outdoor Unit RXG L 10 Operation range 10 1 Operation Range Zy K t E W K t d...

Page 26: ......

Page 27: ...is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N V Daikin Europe N V has compiled the content of this leaflet to the best of its knowledge No expres...

Reviews: