Outdoor Unit Installation

5.

Purging air and checking gas leakage.

• When piping work is completed, it is necessary to purge the air and check for gas leakage.

 WARNING

1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.

2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.

3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.

4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum

pump or the unit.

• If using additional refrigerant, perform air purging from the refrigerant pipes and

indoor unit using a vacuum pump, then charge additional refrigerant.

• Use a hexagonal wrench (4mm) to operate the stop valve rod.

• All refrigerant pipe joints should be tightened with a torque wrench at the specified

tightening torque.

*1. Pipe length vs. vacuum pump run time. 

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists. Check 

all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).

(High-pressure valve subsequently requires no operation.)

3) Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg)*1.

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.

5) Remove caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve.

Close it after 5 seconds, and check for gas leakage.

Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.

After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

Pipe length

Up to 15 metres

Run time

Not less than 10 min.

Compound 
pressure gauge

Pressure 
meter

High-
pressure 
valve

Low-pressure 
valve

Vacuum pump

Service port

Liquid 
stop 
valve

Valve caps

Gas stop valve

Charging 
hoses

Gauge 
manifold

3P291651-9T.book  Page 6  Tuesday, December 9, 2014  2:55 PM

Summary of Contents for RXB25B6V19

Page 1: ...INSTALLATION MANUAL R410A Split Series Installation manual R410A Split series English Models RXB25B6V19 RXB35B6V19 Tan tma ve Kullanma K lavuzu T rk e R410A R410A Split serisi...

Page 2: ...3P291651 9T book Page 2 Tuesday December 9 2014 2 55 PM...

Page 3: ...ificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C...

Page 4: ...receive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do no...

Page 5: ...t anything which must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to fol...

Page 6: ...nal refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shortes...

Page 7: ...nit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary fo...

Page 8: ...en tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torqu...

Page 9: ...es from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no...

Page 10: ...al Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand thi...

Page 11: ...ss the operation select button to return the operation mode to cooling Test run mode will stop automatically after around 30 minutes To force a test run to stop press the operation stop button CAUTION...

Page 12: ...atch Tighten the terminal screws securely We recommend a flathead screwdriver be used to tighten the screws The screws are packed with the terminal board Observe the notes mentioned below when wiring...

Page 13: ...te OUTDOOR CONDENSER DISCHARGE Discharge Strip wire end to this point Excessive strip length may cause electrical shock or leakage Good Wrong Stripping wire at terminal block C1 C2 C400 C405 Capacitor...

Page 14: ...l to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some...

Page 15: ...R410A 3P291651 9T book Page 1 Tuesday December 9 2014 2 55 PM 1...

Page 16: ...70 A A 1 B 1 3P291651 9T book Page 2 Tuesday December 9 2014 2 55 PM 2...

Page 17: ...1 2 3 4 5 6 7 3 3 8 9 1 2 3 4 3P291651 9T book Page 3 Tuesday December 9 2014 2 55 PM 3...

Page 18: ...250 4 1 5 15 9 5 6 4 20 12 15 10 1 5 1 5 470 96 300...

Page 19: ...1200 8 10 20 1 1 2 2 1 2 30 3 50 100 1200 50 50 100 150 300 50 150 20 16 3P291651 9T book Page 5 Tuesday December 9 2014 2 55 PM 5...

Page 20: ...A 5 6 4 1 2 R410A 3 3 4 A A 0 0 5 R410A 1 0 1 5 1 5 2 0 Imperial 3 8 1 4 32 7 39 9 14 2 17 2 333 407 144 175 3 8 1 4 21 6 27 4 21 6 27 4 220 280 220 280 10 8 14 7 110 150 3P291651 9T book Page 6 Tuesd...

Page 21: ...7 5 1 R410A 2 3 R410A 4 R410A 4 1 2 Lo Hi 3 0 1 76 1 4 Lo 2 5 6 90 5 7 8 3P291651 9T book Page 7 Tuesday December 9 2014 2 55 PM...

Page 22: ...8 1 2 2 4 6 R410A 1 R410A 15 10 3P291651 9T book Page 8 Tuesday December 9 2014 2 55 PM 7 7 1 1 2 7 2 1 0 041 0 052 0 035 0 045 C 110 C 2 3 9 5 6 4 12 15 8 10 10 30 0 8 C1220T O...

Page 23: ...9 1 2 3 4 15 1 2 3 4 30 1 2 3P291651 9T book Page 9 Tuesday December 9 2014 2 55 PM WARNING 1 2 3 4 5 1 ISO 7010 W001 2 ISO 7010 W002 3 ISO 7000 0790 4 ISO 7000 1641 5 ISO 7000 1659 RU...

Page 24: ...10 1 2 3 4 3 5 1 20 2 1 2 3 1 2 3 L N 16 10 2 0 H05RN 50 220 240 2 0 1 2 3 1 2 3 1 3 A B A B 3P291651 9T book Page 10 Tuesday December 9 2014 2 55 PM...

Page 25: ...ENSER DISCHARGE C1 C2 C400 C405 V1R E1 E2 HL1 HN1 S HR1 HR2 FU2 FU3 IPM1 IPM2 L L1R M1C M1F K30R K10R MR4 N A1P PS Q1M R1T R2T R3T PTC S20 S30 S40 S71 S80 S90 F1S V2 V3 X1M Y1E Y1S Z1C Z2C Z3C 3P29165...

Page 26: ...12 1 1 1 1 2 1 2 26 C 28 C 20 C 24 C 3 3 1 2 26 C 28 C 3 3 1 3 2 3P291651 9T book Page 12 Tuesday December 9 2014 2 55 PM...

Page 27: ...nmaya elektrik arpmas na veya yang na yol a abilir ve d niteler aras ndaki elektrik ba lant lar i in belirtilen tipte kablolar kullan n Ara ba lant kablolar n u lar zerine harici bir kuvvet etki etmey...

Page 28: ...kilde monte edin 2 D niteyi kesinlikle emi taraf n n do rudan r zgara bakaca bir yere monte etmeyin 3 R zgara maruziyeti engellemek i in d nitenin hava de arj taraf na bir oluklu plaka tak n 4 A r kar...

Page 29: ...k Uzunlu u 10 m yi ge en so utucu ak kan borular i in gerekli ilave so utucu ak kan miktar Uygun miktarda ilave so utucu ak kan ekledi inizden emin olun Aksi takdirde performans d meydana gelebilir D...

Page 30: ...ken Konumun Se ilmesine li kin nlemler ve D nite Montaj izimleri b l mlerine bak n 2 Tahliye al mas gerekiyorsa a a daki prosed rleri takip edin 2 Tahliye al mas Is pompas modelleri 1 Tahliye i in bir...

Page 31: ...nlemek i in konik somunlar s karken tork anahtar kullan n Her iki koni in merkezini hizalay n ve konik somunlar elinizle 3 veya 4 tam tur evirerek s k n Ard ndan bunlar tork anahtarlar yla tamamen s...

Page 32: ...vanas n n servis portuna ba lay n 2 G sterge manifoldunun al ak bas n vanas n Lo sonuna kadar a n ve y ksek bas n taraf n Hi sonuna kadar kapat n Y ksek bas n vanas i in daha sonra bir i lem yap lmas...

Page 33: ...aksa u hususlara dikkat edin 1 Yal t m malzemesi Polietilen k p k Is transfer h z 0 041 0 052W mK 0 035 0 045kcal mh C So utucu gaz borusunun y zey s cakl maksimum 110 C ye ula r Bu s cakl a dayanabil...

Page 34: ...duna getirmek i in al t rma se imi d mesine bas n Test i letimi modu yakla k 30 dakika sonra otomatik olarak durur Bir test i letimini zorlamal durdurmak i in al t rma durdurma d mesine bas n KAZ 1 D...

Page 35: ...idalar n sa lam ekilde s k n Vidalar n s k lmas i in d z u lu bir tornavida kullan lmas nerilir Vidalar terminal kart yla birlikte gelir G kayna terminal kart nda kablolama yaparken a a daki notlara d...

Page 36: ...n OUTDOOR CONDENSER DISCHARGE De arj Kablo ucunu bu noktaya kadar s y r n A r uzunlukta s yr l rsa elektrik arpmas na veya ka a a neden olabilir Do ru Yanl Telin terminal blo unda s yr lmas C1 C2 C400...

Page 37: ...ar n do ru ekilde al t ndan emin olmak i in test al t rmas n kullan m k lavuzuna uygun olarak ger ekle tirin Klima bekleme modunda az miktarda g gerektirir Sistem montaj sonras bir s re kullan lmayaca...

Page 38: ...3P291651 9T book Page 1 Tuesday December 9 2014 2 55 PM...

Page 39: ......

Page 40: ...pyright 2018 Daikin DAIKIN ISITMA VE SO UTMA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir ISTANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0...

Reviews: