•  When piping work is complete, it is necessary to perform a pressure test 

and evacuate system with a vacuum pump.

•  If using additional refrigerant, purge the air from the refrigerant pipes and 

indoor unit using a vacuum pump, then charge additional refrigerant.

• 

Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.

•  All refrigerant pipe joints should be tightened with a torque wrench to the 

specified tightening torque.

Compound 
pressure gauge

Pressure 
meter

High-pressure 
valve

Low-pressure 
valve

Vacuum pump

Service port

Liquid 
stop 
valve

Valve caps

Gas stop valve

Charging 
hoses

Gauge 
manifold

1) Pressurize the liquid pipe and gas pipe from the service ports of each stop valve to 604psi (4.17MPa) (do not pressurize 

more than 604psi (4.17MPa)) for 1 hour minimum, 24 hours recommended. If there is a pressure drop, check for leaks, 
make repairs and perform the pressure test again.

2) Connect the gauge manifold’s charging hose to the gas stop valve’s service port.
3) Fully open the low-pressure valve (Lo) on the gauge manifold and fully close the high-pressure valve (Hi).                      

 (High-pressure valve will require no further operation.)

4) 

Evacuate system using vacuum pump to below 500 microns for 1 hour minimum.

5) Close the low-pressure valve (Lo) on the gauge manifold and stop vacuum pumping. 

(Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing 
back.)*

1

6) Remove the valve caps from the liquid stop valve and gas stop valve.
7) 

To open the liquid stop valve, turn the rod of the valve 90° counter-clockwise using a hexagonal wrench.

 

Close it after 5 seconds, and check for gas leakage. 

Using soapy water, check for gas leakage from the indoor unit’s flare and outdoor unit’s flare and valve rods.

 

After the check is complete, wipe all soapy water off.

8) Disconnect the charging hoses from the service port for the gas stop valve, then fully open the liquid and gas stop valves. 

(Do not attempt to turn the valve rods further than they can go.)

9) 

Tighten the valve caps and service port caps for the liquid and gas stop valves with a torque wrench to the specified 

torques. 
Refer to 

“4. Refrigerant piping” on page 6 for details.

*

1

  If the compound pressure gauge pointer swings back, the refrigerant may have water content or there may be a loose 

pipe joint. 
Check all pipe joints and retighten nuts as needed, then repeat steps 3) through 5).

6. 

Refilling refrigerant

Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.

R410A is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal 

operation.

• 

Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon 

attached” displayed on it.)

Filling a cylinder with an attached siphon

Stand the cylinder upright when filling.

There is a siphon pipe inside, so the cylinder 

need not be upside-down to fill with liquid.

Filling other cylinders

Turn the cylinder 

upside-down when filling.

•  Be sure to use the R410A tools to ensure pressure and to prevent foreign objects from entering.

English

01_EN_3P686855-1.indd   8

2022/05/16   9:29:38

Summary of Contents for RX09WMVJU9

Page 1: ...ODELS RX09WMVJU9 RX12WMVJU9 RXL09WMVJU9 RXL12WMVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel d installation Manual de instalaci n 00_CV_3P686855 1...

Page 2: ...severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death If refrigerant gas leaks duri...

Page 3: ...UNISO oil or moisture should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again har...

Page 4: ...w from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at least 6 5 8ft 2m from propane...

Page 5: ...nt in which it is used Foot bolt hole centers 18 1 2 470 From unit s side 3 13 16 97 Footbolt hole centers 12 1 8 308 O D 3 8 inch 9 5mm Gas pipe Liquid pipe O D 1 4 inch 6 4mm 0 21oz ft 20g m Max all...

Page 6: ...tion of the outdoor unit outlet side or use the air direction adjustment grille sold separately More than 3 15 16 100 More than 13 3 4 150 Outdoor Unit Installation 1 Installing the outdoor unit When...

Page 7: ...igid type 0 059 0 079 inch 1 5 2 0mm Wing nut type Imperial type Conventional are tool Cut exactly at right angles Remove burrs 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit Th...

Page 8: ...16 13 32 inch 8 10mm 13 32 inch 10mm Min Minimum bend radius Piping thickness Thermal insulation size Thermal insulation thickness Liquid side Use separate thermal insulation pipes for gas and liquid...

Page 9: ...id stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage from the indoor unit s...

Page 10: ...for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat wash...

Page 11: ...Conduit Lock nut Conduit mounting plate L1 L2 Ground This air conditioner must be grounded For grounding follow all local and state electrical codes Facility Setting cooling at low outdoor temperature...

Page 12: ...is level 1 Remove the top plate of the outdoor unit 4 screws 2 Remove the front plate 5 screws 3 Cut the jumper J6 of the PCB inside Cut the jumper J6 For RX09 12 RXL09 Cut the jumper J6 For RXL12 J6...

Page 13: ...nd FVX models 1 Press and at the same time 2 Press select and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automaticall...

Page 14: ...ncomplete cooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated Water leakage Draining line is properly installed Water leakage System is pr...

Page 15: ...14 English MEMO English 01_EN_3P686855 1 indd 14 2022 05 16 9 29 40...

Page 16: ...Two dimensional bar code is a manufacturing code 3P686855 1 M21B526 2205 HT 00_CV_3P686855 1 indd 2 2022 02 16 15 37 40...

Reviews: