Precautions on Installation

•  Check the strength and level of the installation surface so that the unit does not cause 

any operating vibrations or noise after installation.

• 

Fix the unit in place securely using foundation bolts, as in the figure. (Prepare 4 

sets of 5/16 inch (M8) or 3/8 inch (M10) foundation bolts, nuts and washers; all sold 
separately.)

•  It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm) from the 

foundation surface.

3/4” (20mm)

Outdoor Unit Installation Diagram

Refrigerant piping must be protected 

from physical damage.

Install a plastic cover or equivalent.

In sites with poor drainage, 

use block bases for the 

outdoor unit.  

Adjust foot height until the unit 

is level. Otherwise, water 

leakage or pooling of water 

may occur.

unit: inch (mm)

Refrigerant piping must be kept to a minimum.

   *Be sure to add the proper amount of additional refrigerant.

Failure to do so may result in reduced performance.  

**The suggested shortest pipe length is 10ft (3m), in order to avoid 

noise from the outdoor unit and vibration.

(Mechanical noise and vibration may occur depending on how 

the unit is installed and the environment in which it is used.)

(Foot bolt-hole centers)

18-1/2 (470)

(From unit’s side)

3-13/16 (97)

(Foot bolt-hole 

centers)

12-1/8 (308)

O.D. 3/8 inch (9.5mm)

Gas pipe

Liquid pipe

O.D. 1/4 inch (6.4mm)

0.21oz/ft (20g/m)

Max. allowable piping length

49-1/4ft (15m)

65-5/8ft (20m)

Max. allowable piping height
Additional refrigerant required for refrigerant 

pipe exceeding 32-3/4ft (10m) in length.

10ft (3m)

Min. allowable piping length

**

*

Allow 11-13/16 (300) 

of work space below the 

ceiling surface.

CAUTION

Keep the piping length between 

10ft (3m) and 65-5/8ft (20m) 

9-13/16 (250) from wall

How to remove the stop 

valve cover

1) Remove the screw on the 

stop valve cover.

2) Slide the stop valve cover 

downward to remove it.

1) Insert the upper part of 

the stop valve cover into  

the outdoor unit.

2) Tighten the screw.

How to attach the stop 

valve cover

Stop valve cover

Allow space for piping 

and electrical servicing.

Wrap the insulation pipe with 

finishing tape from bottom to top.

If strong wind blows into the air discharge 

side from the front and there is a danger 

that the fan may be damaged, change the 

orientation of the air discharge side of the 

outdoor unit or use an air direction 

adjustment grille (sold separately).

If there is a danger of the unit falling or 

overturning, fix the unit with foundation bolts, 

or with wire or other means.

English

01_EN_3P686855-1.indd   4

2022/05/16   9:29:37

Summary of Contents for RX09WMVJU9

Page 1: ...ODELS RX09WMVJU9 RX12WMVJU9 RXL09WMVJU9 RXL12WMVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel d installation Manual de instalaci n 00_CV_3P686855 1...

Page 2: ...severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death If refrigerant gas leaks duri...

Page 3: ...UNISO oil or moisture should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again har...

Page 4: ...w from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at least 6 5 8ft 2m from propane...

Page 5: ...nt in which it is used Foot bolt hole centers 18 1 2 470 From unit s side 3 13 16 97 Footbolt hole centers 12 1 8 308 O D 3 8 inch 9 5mm Gas pipe Liquid pipe O D 1 4 inch 6 4mm 0 21oz ft 20g m Max all...

Page 6: ...tion of the outdoor unit outlet side or use the air direction adjustment grille sold separately More than 3 15 16 100 More than 13 3 4 150 Outdoor Unit Installation 1 Installing the outdoor unit When...

Page 7: ...igid type 0 059 0 079 inch 1 5 2 0mm Wing nut type Imperial type Conventional are tool Cut exactly at right angles Remove burrs 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit Th...

Page 8: ...16 13 32 inch 8 10mm 13 32 inch 10mm Min Minimum bend radius Piping thickness Thermal insulation size Thermal insulation thickness Liquid side Use separate thermal insulation pipes for gas and liquid...

Page 9: ...id stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage from the indoor unit s...

Page 10: ...for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat wash...

Page 11: ...Conduit Lock nut Conduit mounting plate L1 L2 Ground This air conditioner must be grounded For grounding follow all local and state electrical codes Facility Setting cooling at low outdoor temperature...

Page 12: ...is level 1 Remove the top plate of the outdoor unit 4 screws 2 Remove the front plate 5 screws 3 Cut the jumper J6 of the PCB inside Cut the jumper J6 For RX09 12 RXL09 Cut the jumper J6 For RXL12 J6...

Page 13: ...nd FVX models 1 Press and at the same time 2 Press select and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automaticall...

Page 14: ...ncomplete cooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated Water leakage Draining line is properly installed Water leakage System is pr...

Page 15: ...14 English MEMO English 01_EN_3P686855 1 indd 14 2022 05 16 9 29 40...

Page 16: ...Two dimensional bar code is a manufacturing code 3P686855 1 M21B526 2205 HT 00_CV_3P686855 1 indd 2 2022 02 16 15 37 40...

Reviews: