Introduction
SiE33-003
126
Installation Manual
1.3
Combination
The combination with indoor units is as follows:
The possible combination of the outdoor unit with indoor units is in function of the total capacity index of
these indoor units and must be within the range as specified below:
Up to 20 indoor units can be connected to 1 outdoor unit RSXYP16,18 and 20.
Up to 32 indoor units can be connected to 1 outdoor unit RSXYP24,26,28 and 30.
Make sure to connect indoor units designed exclusively for R-407C.(FXY--P--series)
Refer to the catalogue and/or engineering data book for model numbers of indoor units which can be
connected.
Outdoor Unit
RSXYP16 < RXYP8 + RXEP8 >...................................................................................... 200 - 520
RSXYP18 < RXEP8 >.................................................................................... 225 - 585
RSXYP20 < RXEP10 >.................................................................................. 250 - 650
RSXYP24 < RXEP8 >.................................................................................... 300 - 780
RSXYP26 < RXEP10 >.................................................................................. 325 - 845
RSXYP28 < RXEP8 >.................................................................................... 350 - 910
RSXYP30 < RXEP10 >.................................................................................. 375 - 975
Si33-003.book Page 126 Monday, June 25, 2001 9:06 AM