Installation manual

1

RR+RQ71+10 RR+RQ7 RR+RQ71~12

RR+RQ71B2W1B

Split System air conditioners

4PW23689-1C

C

ONTENTS

Page

Safety considerations ........................................................................ 1

Before installation.............................................................................. 2

Selecting installation site................................................................... 3

Precautions on installation ................................................................ 3

Installation servicing space ............................................................... 4

Refrigerant pipe size and allowable pipe length ................................ 4

Precautions on refrigerant piping ...................................................... 5

Refrigerant piping.............................................................................. 6

Evacuating......................................................................................... 8

Charging refrigerant .......................................................................... 8

Electrical wiring work....................................................................... 10

Test operation.................................................................................. 12

Disposal requirements .................................................................... 12

Wiring diagram ................................................................................ 13

S

AFETY

 

CONSIDERATIONS

The precautions listed here are divided into the following two types.
Both cover very important topics, so be sure to follow them carefully.

Warning

The equipment is not intended for use in a potentially explosive
atmosphere.

Ask your dealer or qualified personnel to carry out installation
work. Do not install the machine by yourself.
Improper installation may result in water leakage, electric shocks
or fire.

Perform installation  work in accordance with this installation
manual.
Improper installation may lead to water leakage, electric shocks
or fire.

When a unit is installed in a small room, it is necessary to take
measures so that the leaked refrigerant amount does not
exceed the limit even if it leaks. As for the measures to prevent
the leak from not exceeding the limit, please consult with your
distributor.
If the leaked amount exceeds the limit, it may cause an oxygen
deficiency accident.

Be sure to use only the specified accessories and parts for
installation work.
Failure to use the specified parts may result in water leakage,
electric shocks, fire, or the unit falling.

Install the air conditioner on a foundation that can withstand its
weight.
Insufficient strength may result in the fall of equipment and
causing injury.

Carry out the specified installation work in consideration of
strong winds, typhoons, or earthquakes.
Improper installation work may result in accidents due to falling
of equipment.

Make certain that all electrical work is carried out by qualified
personnel according to the local laws and regulations and this
installation manual, using a separate circuit.
Insufficient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or fire.

Make sure that all wiring is secure, using the specified wires and
ensuring that external forces do not act on the terminal
connections or wires.
Incomplete connection or fixing may cause a fire.

When wiring between the indoor and outdoor units, and wiring
the power supply, form the wires so that the frontside panel can
be securely fastened.
If the frontside panel is not in place, overheat of the terminals,
electric shocks or a fire may be caused.

If refrigerant gas leaks during installation work, ventilate the
area immediately.
Toxic gas may be produced if refrigerant gas comes into contact
with fire.

After completing the installation work, check to make sure that
there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the room
and comes into contact with a source of fire, such as a fan
heater, stove or cooker.

Before touching electric terminal parts, turn off the power switch.

Live parts can be easily touched by accident.
Do never leave the unit unattended during installation or
servicing when the service panel is removed.

When planning to relocate former installed units, you must first
recover the refrigerant after the pumping-down operation. Refer
to chapter 

"Precaution for pumping-down operation" on page 10

.

Do never directly touch any accidental leaking refrigerant. This
could result in severe wounds caused by frostbite.

RR71B8V3B

RR71B8W1B

RQ71B8V3B

RQ71B8W1B

RR71B2V3B

RR71B2W1B

RQ71B2V3B

RQ71B2W1B

RR100B8V3B

RR100B8W1B

RQ100B8V3B

RQ100B8W1B

RR125B8W1B

RQ125B8W1B

Split System air conditioners

Installation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

WARNING

If the warning is not observed, it may cause serious casualties.

CAUTION

If the caution is not observed, it may cause injury or damage to the 
equipment.

Summary of Contents for RR71B8V3B

Page 1: ...INSTALLATION MANUAL RR71B8V3B RR71B2V3B RR100B8V3B RR71B8W1B RR71B2W1B RR100B8W1B RR125B8W1B RQ71B8V3B RQ71B2V3B RQ100B8V3B RQ71B8W1B RQ71B2W1B RQ100B8W1B RQ125B8W1B Split System air conditioners...

Page 2: ...1 2 4 5 2 4 5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1...

Page 3: ...ttaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 vastavalt n uetele 21 22 laika...

Page 4: ...the power supply circuit or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secure using the specified wires and ensuring that external forces do not...

Page 5: ...contains high levels of salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present BEFORE INSTALLATION...

Page 6: ...e please install a waterproof plate within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction 6 When installing the unit in a place frequently expos...

Page 7: ...ld comply with relevant local and national regulations The minimal pipe thickness for R410A piping must be in accordance with the table below O Annealed 1 2H Half hard Suction side obstacle Obstacle i...

Page 8: ...piping kit Install the branch pipes horizontally with a maximum inclination of 15 or vertically Length of branch pipe to the indoor unit should be as short as possible Try to keep lengths of both bra...

Page 9: ...e deformed if only a torque wrench is used when loosening or tightening flare nuts always lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do...

Page 10: ...t coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly After completing the installation carry out a gas leak inspection of the...

Page 11: ...rs and bring the system to 100 7 kPa After keeping the system under that condition for more than one hour check if the vacuum gauge rises or not If it rises the system may either contain moisture insi...

Page 12: ...mount R R1 R2 1 00 0 30 1 30 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54 2 Over 30 m a G1 5 m R1 0 0 kg b G1 G2 30 5 54 30 29 6 4 R2 0 90 kg 3 Refrigerant charge amount R R1 R2 0 0 0 9 0 9 kg Tot...

Page 13: ...ground wire to the shut off valve attachment plate so that it does not slide 2 Secure the ground wire to the shut off valve attachment plate one more time along with the electric wiring and the inter...

Page 14: ...d wiring components Point for attention regarding quality of the public electric power supply This equipment complies with EN IEC 61000 3 11 1 provided that the system impedance Zsys is less than or e...

Page 15: ...For a missing phase in case of W1 units E0 or E6 will be displayed on the remote controller of the indoor unit Operation will be impossible with either one of these phenomena If this happens turn off...

Page 16: ...Q2M Thermo switch M1F M2F Q1RP Phase reverse circuit R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge RC Signal receiver circuit S1PH Pressure switch HIGH S1PL Pressure switch LOW SD S...

Page 17: ...NOTES NOTES...

Page 18: ...4PW23689 1C Copyright Daikin...

Reviews: