background image

 

Installation manual

 

2

 

R(Y)P71~W1

Split System air conditioners

4PW14486-1B

 

B

 

EFORE

 

 

 

INSTALLATION

 

Precautions for R-407C 

 

 

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
-

Clean and dry

Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
-

Tight

Read 

"Precautions on refrigerant piping" on page 5

 carefully and

follow these procedures correctly.

 

 

Since R-407C is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant is
in state of gas, its composition changes and the system will not
work properly).

 

 

The connected indoor units must be indoor units designed
exclusively for R-407C.

 

Installation

 

 

For installation of the indoor unit(s), refer to the indoor unit
installation manual.

 

 

Illustrations show class 125 outdoor unit type. Other types also
follow this installation manual.

 

 

This outdoor unit requires the pipe branching kit (optional) when
used as the outdoor unit for the simultaneous operation system.
Refer to catalogues for details.

 

 

Never operate the unit without the thermistor (R3T), burning of
the compressor may result.

 

 

Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.

 

 

When closing the service panels, take care that the tightening
torque does not exceed 4.1 Nm.

 

Handling

 

As shown in the figure, bring the unit slowly by grabbing the left and
right grips. 

Place your hands on the corner instead of holding the suction inlet in
the side of the casing, otherwise the casing could be deformed.

 

S

 

ELECTING

 

 

 

INSTALLATION

 

 

 

SITE

 

 

 

1

 

Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.

-

Places which are well-ventilated.

-

Places where the unit does not bother next-door neighbours.

-

Safe places which can withstand the unit's weight and 
vibration and where the unit can be installed level.

-

Places where there is no possibility of flammable gas or 
product leak.

-

Places where servicing space can be well ensured.

-

Places where the indoor and outdoor units' piping and wiring 
lengths come within the allowable ranges.

-

Places where water leaking from the unit cannot cause 
damage to the location (e.g. in case of a blocked drain pipe).

-

Places where the rain can be avoided as much as possible.

 

CAUTION

 

 

Ground the air conditioner.
Grounding resistance should be according to national
regulations
Do not connect the earth wire to gas or
water pipes, lightning conductor or
telephone earth wire.
Incomplete grounding may cause electric
shocks.

 

 

Gas pipe.
Ignition or explosion may occur if the gas leaks.

 

 

Water pipe.
Hard vinyl tubes are not effective grounds.

 

 

Lightning conductor or telephone ground wire.
Electric potential may rise abnormally if struck by a
lightning bolt.

 

 

Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may cause
electric shocks.

 

 

Install drain piping according to this installation
manual to ensure good drainage, and insulate the
pipe to prevent condensation.
Improper drain piping may cause water leakage, and
make the furnitures get wet.

 

 

Install the indoor and outdoor units, power wire and
connecting wire at least 1 meter away from televisions
or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter
may not be sufficient to eliminate the noise.)

 

 

Do not install the air conditioner in places such as the
following:

 

 

Where there is mist of mineral oil, oil spray or
vapor for example a kitchen.
Plastic parts may deteriorate, and cause them to
fall out or water to leak.

 

 

Where corrosive gas, such as sulfurous acid gas,
is produced.
Corrosion of copper pipes or soldered parts may
cause the refrigerant to leak.

 

 

Where there is machinery which emits
electromagnetic waves.
Electromagnetic waves may disturb the control
system, and cause malfunction of the equipment.

 

 

Where flammable gases may leak, where carbon
fiber or ignitable dust is suspended in the air or
where volatile flammables, such as thinner or
gasoline, are handled.
Such gases may cause a fire.

 

 

Where the air contains high levels of salt such as
that near the ocean.

 

 

Where voltage fluctuates a lot, such as that in
factories.

 

 

In vehicles or vessels.

 

 

Where acidic or alkaline vapoure is present.

 

Take care not to let hands or objects come in contact with
rear fins.

Summary of Contents for RP100L7V1

Page 1: ...INSTALLATION MANUAL RP71L7V1 RP100L7V1 RP71L7W1 RP100L7W1 RP125L7W1 RYP71L7V1 RYP100L7V1 RYP71L7W1 RYP100L7W1 RYP125L7W1 Split System air conditioners...

Page 2: ...C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2 2 2 H1 L1 3 3 H1 H2 L3 L1 L2 4 4 H1 H2 L4 L1 L3 L2 5 5...

Page 3: ...7 7 8 8 NOTES...

Page 4: ...se med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standard er eller andre normgivende dokument er under forutssetning av at disse brukes i henhold til v re instrukser vast...

Page 5: ...eakage electric shocks or fire When a unit is installed in a small room it is necessary to take measures so that the leaked refrigerant amount does not exceed the limit even if it leaks As for the mea...

Page 6: ...d Places where the indoor and outdoor units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location e g in case of a blo...

Page 7: ...following Elevate the foundation as high as possible Remove the rear suction grille to prevent snow from accumulating on the rear fins 7 If you install the unit on a building frame please install a w...

Page 8: ...tween the branch and the indoor units L2 L4 should have the same size as the indoor connections Branch see marking on figures 3 4 Suction side obstacle Obstacle is present Discharge side obstacle 1 In...

Page 9: ...equal When using existing refrigerant piping Pay attention to the following points when using existing refrigerant piping In the following situations the existing piping should not be re used and new...

Page 10: ...torque 19 6 24 5 N m Check for refrigerant leakage after tighten the cap Cautions for handling service port After the work tighten the valve cover in place Tightening torque 10 8 14 7 N m Precautions...

Page 11: ...installer Confirm that the valves are firmly closed before leak test or vacuuming Set up for vacuuming and leak test see figure 7 Procedure for leak test Leak test must satisfy EN378 2 Piping size Fl...

Page 12: ...90 kg 3 Refrigerant charge amount R R1 R2 0 0 0 9 0 9 kg Complete charging of the refrigerant after a leak etc When the entire refrigerant pipe length is within 30 meters charge the refrigerant in ac...

Page 13: ...ure the ground wire to the shut off valve attachment plate so that it does not slide 2 Secure the ground wire to the shut off valve attachment plate one more time along with the electric wiring and th...

Page 14: ...are open Be sure to close the frontside panel before operation as not doing so can cause electric shock The refrigerant pressure may not rise even if the shut off valve is opened after an air purge i...

Page 15: ...l check for voltage imbalance If the error code UF is displayed on the remote contol check the inter unit branch wiring connection Diagnosis On the remote control LCD If the machine stops due to some...

Page 16: ...PRC W1 MODEL Phase reverse circuit Q1M Q2M Thermo switch M1F M2F Q3E Earth leak detector R1T Thermistor air R2T Thermistor coil R3T Thermistor discharche R4C V1 MODEL Resistor RC Signal receiver circu...

Page 17: ...NOTES NOTES...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN14486 1B...

Reviews: