background image

16

FA ROTEX Solaris RPS4 - 

04/2016

x

 Start-up and decommissioning

5 Start-up and decommissioning

5.1 Start-up

All the following work must be carried out in the specified se-
quence.

1. Filling the storage cylinder:

Ɣ

Filling the heat exchanger for domestic water.

Ɣ

Fill the buffer storage volume via the filling and draining
hose (

KFE BA, 16 52 15

) on the regulation and pump 

unit RPS4 until water comes out of the safety overflow.

Ɣ

Close the filling and drain valve (

KFE BA, 16 52 15

).

2. Switch on the Solaris R4 regulator.

Î

The initialisation phase begins.

3. When the initialisation phase is finished (temperature

display), fill and vent the solar system by simultaneously
pressing both arrow keys (starting manual mode).

Î

The solar operating pump P

S

 now runs at full power and

the solar system is exposed to the maximum possible 
operating pressure. The solar system fills, the air escapes 
through the flow line into the air compartment of the stor-
age tank. 

4. Check the entire system for leaky joints (in the building and

on the roof). Seal any leaks that occur in a professional
manner.

5. Switch off the Solaris R4 regulator.

6. Check the filling level in the hot water storage tank.

7. Adjusting the filling time:

Ɣ

Switch the Solaris R4 regulator on again (initialisation
phase starts).

Ɣ

When the initialising phase is finished (temperature
display), you can start the manual operating mode by
simultaneously pressing both arrow keys.

Ɣ

Measure the time it takes to fill the solar system
completely. The system is fully filled when you can no
longer hear any air noises and a steady value for the flow
rate is displayed (activate the measuring point [Flow rate]
using the arrow keys).

Ɣ

Set the measured time plus 20 seconds in the
parameter [time P2] (see section 6.3.6).

8. Switch the Solaris R4 regulator to the automatic mode by

pressing the two arrow keys simultaneously or by switching
off and on again.

Î

The solar system is now ready for operation.

9. Only when connecting a RPS4 regulating and pump unit to

several solar storage tanks:
– The entire flow rate, measured with the FlowSensor in the 

solar flow line must be distributed evenly to all the con-
nected solar storage tanks. We recommend using a
FlowGuard (FLG) at each storage tank for regulation pur-
poses.

10. Instruct the user, fill out the acceptance report, and send it to

the address indicated on the rear cover of this manual.

WARNING!

The solar system cannot be started until all 
hydraulic and electrical connections have been 
completed.
Incorrect commissioning will impair the system's 
function, and can lead to damage to the entire 
installation. Installation and start-up must 
therefore must conducted by ROTEX-au-
thorised and trained heating experts.
The protective conductor resistance and correct 
wiring must be checked before start-up.

CAUTION!

Commissioning in frosty conditions can result in 
damage to the entire heating system.

Ɣ

Commissioning with outside temperatures
below 0°C should only be undertaken if a
water temperature of at least 5°C in the solar
circuit can be guaranteed (e.g. by previous
heating of the DHW cylinder).

ROTEX recommends that you avoid operating 
the system in extremely frosty conditions.

UK only!

CAUTION!

If filling or topping up the storage tank is done by 
means of the boiler filling and drain valve, a 
temporary filling loop must be used with the 
appropriate backflow prevention device in 
accordance with clause G24.2, Guidance to the 
Water Supply (Water Fittings) Regulations 
1999.

The domestic water quality must comply with the 
EU Guideline 98/83 EC and the regionaly-applica-
ble regulations.

Within a few minutes after switching off and emptying of 
the solar system, the fill level indicator in the hot water 
storage tank once again reach almost to the fill level.

– The reason for a slightly lower fill level is the remaining of a

small volume of water in the lower collection pipes in the pan-
els. If the solar panels are correctly aligned, this volume of
water is not dangerous for the panel, even under the effects
of frost, since there is adequate space for expansion.

– If the fill level remains considerably below the fill level, this

can be an indication of undiscovered leaks or faulty line rout-
ing (water pockets). In this case the installation must be
checked very closely once more.

The correct flow rate in the solar circuit is set automati-
cally by regulating the speed of the solar operation 
pump P

S

.

Summary of Contents for Rotex EKSRPS4A

Page 1: ...ller ROTEX RPS4 Operating and installation instructions Regulation and pump unit for Solaris Solar Systems Valid for the following components ROTEX Solaris RPS4 Solaris R4 Differential temperature con...

Page 2: ...aris RPS4 04 2016 1 x Guarantee 1 Guarantee 1 1 Warranty conditions The legal guarantee conditions fundamentally apply Our war ranty conditions beyond that can be found online on your sales representa...

Page 3: ...Manual operation 21 6 2 7 FlowSensor 21 6 2 8 Output calculation maximum values and yield count 22 6 2 9 Speed regulation of the solar operating pump PS 22 6 2 10 Total Reset Function 23 6 2 11 Frost...

Page 4: ...documentation of the ROTEX solar system and therefore must be observed The documents are included in the scope of supply of the individual components ROTEX high performance flat solar panels Solaris...

Page 5: ...trained persons heating technicians roofers etc under observance of the relevant Accident Prevention Regulations Material and tools must be secured against falling Barriers must be erected to prevent...

Page 6: ...panel 10 Solar panel array 11 Solar flow line at the top on the solar panel 12 Thermal mixing valve scalding protection provided by customer 13 Convection brake accessory 14 Solar flow layering pipe 1...

Page 7: ...er heat pump Electronic control The fully electronic ROTEX Solaris R4 regulator ensures op timum utilisation of the solar heat hot water generation heating support and that all safety relevant aspects...

Page 8: ...adequate you can interconnect several Sanicube HybridCube as modules The following components are offered Solar storage tank extension kit CON SX 16 01 20 Solar storage tank kit 2 CON SXE 16 01 21 Flo...

Page 9: ...els can be mounted one above the other Solar panels or solar panel fields mounted one above the other must be connected in series fig 4 3 Fig 4 1 Solar panel field with a connection at each end recomm...

Page 10: ...regulations DANGER Leaking gas in the immediate proximity of electrical components can cause an explosion The RPS4 regulating and pump unit and electrical components should not be installed in locatio...

Page 11: ...of the FlowSensors c 4 Cut the flow pipe g 15 mm to the required length and insert it in the push in fitting f 5 Route the FlowSensor cable between the FlowSensor c and the Solaris R4 regulator 6 Plu...

Page 12: ...sensor and insert into the sensor tube 2 Position the return flow temperature sensor in the sensor tube at approx 130 cm insertion depth cable tie 3 Position the storage cylinder temperature sensor in...

Page 13: ...lti core with wire end sleeves with insulating collar 1 5 mm2 Multi core with wire end sleeves without insulating collar 2 5 mm2 Electrical connection 1 Plug in the supplied cables using the PCB edge...

Page 14: ...as shown in fig 4 28 and fig 4 29 point downwards 6 Cabling of the solar operating pump PS Connect the pump cable to the solar operating pump PS 7 Run the control cables along the return pipe and fix...

Page 15: ...control unit 2 Fix the cover to the control unit on both sides with countersunk screws 3 Fasten the cover to the cylinder connecting bracket underneath To do this carefully screw in the self tapping...

Page 16: ...distributed evenly to all the con nected solar storage tanks We recommend using a FlowGuard FLG at each storage tank for regulation pur poses 10 Instruct the user fill out the acceptance report and se...

Page 17: ...frost and may suffer damage Drain the heating system that is shut down if there is danger of frost CAUTION CAUTION Pumps that are switched off for a long time can seize With temporarily shut down sol...

Page 18: ...5 3 Fig 5 3 Assembling the KFE fill ing connection in the connecting angle Thanks to the environmentally friendly design of the solar system ROTEX has complied with requirements for environmentally so...

Page 19: ...r moving the temperature or pa rameter display up by one setting increas ing parameter settings 9 Down arrow for moving the temperature or parameter display down by one setting de creasing parameter s...

Page 20: ...ly switched off TS light flashes pump operation with activated intensified frost protection function star symbol flashes in the display see section 6 2 11 pump operation if the solar panel temperature...

Page 21: ...TV TR If the system has detected the FlowSensor once the display shows an error message if a sensor is faulty or is disconnected see section 7 1 Display of events The system then works in the emergen...

Page 22: ...ing pump PS then takes place between the determined minimum and maximum outputs The spread of TV and TR TV TR is measured continuously and compared with the target spread DT If the temperature spread...

Page 23: ...unction As soon as the Solaris R4 regulator detects a solar panel temper ature TK below 5 C non adjustable parameter T frost off the enhanced frost protection function becomes active This com pletely...

Page 24: ...tem perature 30 to 250 C 1 K TK min Min measured collector tem perature 30 to 250 C 1 K V max Maximum flow rate 0 0 to 12 0 l min 0 1 l min Maximum flow measured during filling 0 0 to 20 0 l min 0 0...

Page 25: ...he 3rd line burner block contact active see section 6 3 10 or a fault status see section 7 2 Trouble shooting H in the 4th line manual operating mode 6 3 3 Setup menu The Solaris R4 regulator paramete...

Page 26: ...26 FA ROTEX Solaris RPS4 04 2016 6 x FlowSensor Fig 6 7 Setup menu...

Page 27: ...h Enter choice 1 2 under Code 0000 It activates all important systems parameters in the settings menu for technicians see fig 6 7 6 3 5 Language selection During initial commissioning or after a total...

Page 28: ...ce P min or if the storage tank has heated up to the adjustable minimum storage tank temperature set by the heating expert operating pa rameter TS min see tab 6 5 the burner is deactivated via a conta...

Page 29: ...12 20 100 FLS 20 20 FLS 100 100 FR active Status frost protection function Yes No No H A Automatic return from manual to auto matic operation 1 to 900 min 30 min 1 min P min Min output for burner stop...

Page 30: ...em runs without evaporation in the collector However on a cloudless day this can lead to a situation where the system only switches on again in the late afternoon although the storage cylinder tempera...

Page 31: ...VBSK in such a way that the external heat generator does not heat see section 6 3 10 if a a minimum heating output is provided by the solar pan els or the storage cylinder has reached a sufficiently h...

Page 32: ...equipment fault of the supply voltage G 7 Reference Internal equipment fault of the refer ence voltage G 8 RESET Overall reset was carried out Parameters to factory settings calculated values and eve...

Page 33: ...ration is enabled automat ically Failures Sensor Cause of the fault Status blinks Display Lamp flashing Light flashes Collector temp Interruption K uuuu TK Long term switch off of PS Short circuit TK...

Page 34: ...aling cap and loosen it if necessary do not remove 2 Check the installation for leaks Check the installation for leaks and rectify if necessary Follow instructions in section 5 Start up and decommis s...

Page 35: ...atures up to 95 C If a heat exchanger is oper ated at temperatures greater than 95 C another gravity brake must be installed in the building A selection of diagrams of the most common installed syste...

Page 36: ...36 FA ROTEX Solaris RPS4 04 2016 8 x Hydraulic system connection Fig 8 2 Standard Solaris incorporation with GCU compact 1 Fig 8 3 Standard Solaris incorporation with Air Water Heat Pump HPSU compact1...

Page 37: ...laris RPS4 04 2016 37 1 The displayed plant schematics do not claim to be complete and do not replace careful indoor planning Fig 8 4 Standard Solaris incorporation with Air Water Heat Pump HPSU Bi Bl...

Page 38: ...ain regulator heat pump HPSU com pact HPSU compact series solar storage tank with integrated heat pump unit MAG Diaphragm expansion vessel MIX 3 way mixer with drive motor MK1 Mixer group with high ef...

Page 39: ...anel and the storage tank you cannot use the depressurised ROTEX solar system DrainBack and thus the regulation and pump unit RPS4 Instead the heating system can be executed with the ROTEX solar press...

Page 40: ...x D 230 x 815 x142 mm Operating voltage 230 V 50 Hz Solar operating pump Grundfos UPM3 15 145 Maximum electrical power consumptionRPS4 During start 65 W 115 W In normal mode 15 65 W modulated 30 115...

Page 41: ...characteristic curve RS Sensor resistance PTC Pt 1000 t Temperature Fig 9 1 Resistance characteristic lines of the Solaris sensor L Flow rate U Sensor output voltage t Temperature Fig 9 2 Characterist...

Page 42: ...42 FA ROTEX Solaris RPS4 04 2016 10 x Notes 10 Notes...

Page 43: ...n 20 29 34 Instantaneous output 35 M Malfunctions Manual 32 Rectification 33 Manual operation 6 21 22 23 25 27 28 Minimum pump output 22 23 Momentary output 24 Mounting position solar panel temperatur...

Page 44: ...ROTEX FA ROTEX Solaris RPS4 Subject to change and correction 008 1627444_01 04 2016...

Reviews: