IM 926-3 • ROOFPAK APPLIED SYSTEMS 24 www.DaikinApplied.com
Mechanical Installation
Figure 35: Typical Power Wire Entrance, Curb View (RPS/RFS 015C - 040C Shown, Refer to Submittal Drawings)
Post and Rail Mounting
CAUTION
The unit must be level side to side and over the entire length.
Equipment damage can result if the unit is not level.
When mounting by post and rail, run the structural support the
full length of the unit. Locate the structural member at the base
of the unit as shown in
supported by the structural member.
If resilient material is placed between the unit and the rail, insert
a heavy steel plate between the unit and the resilient material to
distribute the load. Seal cabinet penetrations (electrical, piping,
etc.) properly to protect against moisture and weather.
Table 7: “W” Dimension (
)
Unit Dimension
“W”
in . (mm)
015C-040C
94 (2388)
045C-135C
99 (2538)
Figure 36: Post and Rail Mounting
Unit length minus 6.4
12.1
See Detail A
Detail A
3.4
5.1
0.9 Dia.
K.O.
3.0 Dia.
K.O.
4.6
4.8
2.0
2.1
4.3
3.1
9.7
E
8.0
97.0
76.0
6.0
7.5
20.0
1.5
6.0
6.8
OPNG
B
2 Typ
A
A
D
C
D
4 Typ
A
B
B
OPNG
RPS only
RA
SA
W
* Maximum recommended width for structural member is 5" (127 mm)
to allow for adequate space for duct connections and electrical entry