IM 926-3 • ROOFPAK APPLIED SYSTEMS 18 www.DaikinApplied.com
Mechanical Installation
Figure 26: Service Clearances
Overhead Clearance
1.
Unit(s) surrounded by screens or solid walls must have
no overhead obstructions over any part of the unit.
2. The area above the condenser must be installed
unobstructed to allow vertical air discharge.
3.
The following restrictions must be observed for overhead
obstructions above the air handler section (see
a. There must be no overhead obstructions above the
furnace flue, or within 9" (229 mm) of the flue box.
b. Overhead obstructions must be no less than 96"
(2438 mm) above the top of the unit.
c. There must be no overhead obstructions in the
areas above the outside air and exhaust dampers
that are farther than 24" (610 mm) from the side of
the unit.
Figure 27: Overhead Clearance
Roof walkway
To roof
access
location
Varies with unit arrangement
Refer to certified drawing & note.
60"
(1524 mm)
96"
(2438 mm)
60"
(1524 mm)
60"
(1524 mm)
72"
(1829 mm)
A
B C
D
E
C
F
Legend:
A = Return air section
B = Filter section
C = Cooling section
D = Cooling/supply fan section
E = Heat section
F = Discharge plenum section
G
G = Condensing section