Si001658EA
Compressor
Removal Procedure
21
2
3
Remove the protection
bushing.
Disconnect the
compressor lead wires
(U, V, W) and the
overload protector.
4
5
6
7
8
9
Cut the clamp.
Remove the putties.
Heat up the brazed part
of the discharge side
pipe and disconnect it.
Heat up the brazed part
of the suction side pipe
and disconnect it.
Remove the 3 nuts of
the compressor.
Lift up the compressor
and remove it.
Step
Procedure
Points
Protection bushing
U (red)
Overload
protector
V (yellow)
W (blue)
(R23738)
Brazed part of the
discharge side pipe
Brazed part of the
suction side pipe
Clamp
Putty
Compressor
Nut
(R23743)