Troubleshooting by Error Code
SiUS371901EB
277
Part 6 Service Diagnosis
3. Troubleshooting by Error Code
3.1 Error Codes and Descriptions
k
: ON
h
: OFF
l
: Blink
Error
code
Operation
lamp
Error contents
Reference
page
Indoor
Unit
A0
l
External protection device abnormality
A1
l
Indoor unit control PCB abnormality
A3
l
Drain level control system abnormality
A6
l
Indoor fan motor lock, overload
Indoor fan motor abnormality
Overload/overcurrent/lock of indoor fan motor
Blower motor not running
Indoor fan motor status abnormality
Low indoor airflow
A7 (
∗
1)
k
Swing flap motor abnormality
A8
l
Power supply voltage abnormality
Blower motor stops for over/under voltage
A9
l
Electronic expansion valve coil abnormality, dust clogging
AA
l
Gas furnace abnormality
AF (
∗
1)
k
Drain level above limit
AJ
l
Capacity determination device abnormality
C1
l
Transmission abnormality between indoor unit control PCB and fan PCB
Blower motor communication error
Climate Talk communication error
C4
l
Heat exchanger liquid pipe thermistor abnormality
C5
l
Heat exchanger gas pipe thermistor abnormality
C6
l
Combination error between indoor unit control PCB and fan PCB
Blower motor HP mismatch
Indoor blower does not have required parameters to function
C9 (
∗
2)
l
Suction air thermistor abnormality
Remote sensor abnormality
CA
l
Discharge air thermistor abnormality
CC
k
Humidity sensor system abnormality
CE (
∗
1)
k
Infrared presence/floor sensor error
CJ (
∗
2)
k
Remote controller thermistor abnormality
Outdoor
Unit
E1
l
Outdoor unit main PCB abnormality
E2
l
Detection of ground leakage by leak detection circuit
Missing of ground leakage detection core
E3
l
Activation of high pressure switch
E4
l
Activation of low pressure sensor
E5
l
Compressor motor lock
E6
l
Compressor damage alarm
E7
l
Outdoor fan motor abnormality
E9
l
Electronic expansion valve coil abnormality
F3
l
Discharge pipe temperature abnormality
F4
Kk
/
l
Wet alarm
F6
l
Refrigerant overcharged
Branch
Selector
Unit
F9
l
Branch Selector unit electronic expansion valve abnormality
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...