Troubleshooting by Error Code
SiUS371901EB
349
Part 6 Service Diagnosis
Reference
3.41 Refrigerant Overcharged
Applicable
Models
All outdoor unit models
Error Code
F6
Method of Error
Detection
Detect overcharged refrigerant according to outdoor air temperature, heat exchanger deicer
temperature, and liquid pipe temperature during check operation.
Error Decision
Conditions
When the amount of refrigerant, which is calculated using outdoor air temperature, heat exchanger
deicer temperature, and liquid pipe temperature during check operation, exceeds the regular
charge amount by 30% or more
(If refrigerant is charged slightly over the regular charge amount,
F6
may be displayed on the
remote controller.)
Supposed
Causes
Refrigerant overcharged
Disconnection of outdoor air thermistor
Disconnection of heat exchanger deicer thermistor
Disconnection of liquid pipe temperature thermistor
Troubleshooting
CHECK 11
Refer to page 429.
Check for the conditions of
mounting of the temperature
sensors of the outdoor air
thermistor, the heat exchanger
thermistor, and liquid pipe
thermistor to the piping.
Disconnect the outdoor air
thermistor, the heat exchanger
thermistor, and liquid pipe
thermistor from the outdoor
unit main PCB, and then make
measurement of resistance
using a multimeter.
Normal?
Remedy refrigerant overcharging.
YES
NO
NO
Replace the abnormal thermistors,
and then operate the system.
Properly connect the thermistors,
and then operate the system.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
CHECK 11
Are the temperature
sensors properly
mounted?
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...