Troubleshooting by Error Code
SiUS371901EB
347
Part 6 Service Diagnosis
3.40 Wet Alarm
Applicable
Models
All outdoor unit models
Error Code
F4
Method of Error
Detection
In cooling operation, detect the condition under which liquid refrigerant returns to the compressor,
according to the temperature and pressure of each part.
Error Decision
Conditions
When the following wet state continues for a period of 90 minutes, an alert is issued.
An error is defined for 120 minutes.
Wet state in outdoor units
When the following wet state continues for a period of 45 minutes, an alert is issued.
Wet state in some of indoor units
Supposed
Causes
Defective suction pipe thermistor
Defective compressor suction thermistor
Defective discharge pipe thermistor
Defective high pressure sensor
Defective indoor unit electronic expansion valve
Dirty air filter
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...