background image

English

14

9-12 THE DISPLAY SHOWS 

• This is the case immediately after the main 

power supply switch is turned on and means 
that the remote controller is in normal condi-
tion. This continues for 1 minute.

9-13 THE COMPRESSOR OR FAN IN THE 

OUTSIDE UNIT DOES NOT STOP 

• This is to prevent oil and refrigerant from 

remaining in the compressor. The unit will 
stop after 5 to 10 minutes.

9-14 THE INSIDE OF OUTSIDE UNIT IS 

WARM EVEN WHEN THE UNIT HAS 
STOPPED

• This is because the crankcase heater is warm-

ing the compressor so that the compressor 
can start smoothly.

9-15 HOT AIR IS EMITTED EVEN THOUGH 

THE UNIT IS STOPPED

• Hot air can be felt when the unit is stopped.

Several different indoor units are being run on the 
same system, so if another unit is running, some 
refrigerant will still flow through the unit.

9-16 DOES NOT COOL VERY WELL

• Program dry operation.

Program dry operation is designed to lower the 
room temperature as little as possible. 
Refer to page 8.

10. TROUBLE SHOOTING

If one of the following malfunctions occur, take 
the measures shown below and contact your 
Daikin dealer.

WARNING

Stop operation and shut off the power if any-
thing unusual occurs (burning smells, etc.)

Leaving the unit running under such circumstances 
may cause breakage, electrical shock, or fire.
Contact your dealer.

• If a safety device such as a fuse, a breaker or an 

earth leakage breaker frequently actuates; 
Measure : Do not turn on the main power switch.

• If the ON/OFF switch does not properly work;

Measure: Turn off the main power switch.

• If water leaks from unit;

Measure: Stop the operation.

• The operation mode selector button does not 

work well.
Turn off the power.

• If the display “

”, the unit number and the 

operation lamp flash and the malfunction code 
appears; 

(Refer to figure 12)

1. Inspection display

2. Indoor unit number in which a malfunction occurs

3. Operation lamp
4. Malfunction code

Measure: Notify your Daikin dealer and report the 
malfunction code.

If the system does not properly operate except for 
the above mentioned cases and none of the above 
mentioned malfunctions is evident, investigate the 
system according to the following procedures.
If it is impossible to fix the problem after checking 
all the above items, contact your dealer.
Let him know the symptoms, system name, and 
model name.

1. If the system does not operate at all;

• Check if there is no power failure.

Wait until power is restored. If power failure occurs 
during operation, the system automatically restarts 
immediately after the power supply is recovered.

• Check if no fuse has blown;

Turn off the power supply.

• Check if the breaker is 

blown.
Turn the power on with 
the breaker switch in the 
off position.
Do not turn the power on 
with the breaker switch in 
the trip position.
(Contact your dealer.)

2. If the system stops soon after starting the operation;

• Check if air inlet or outlet of outside or indoor unit 

is not blocked by obstacles.
Remove any obstacle and make it well-ventilated.

• Check if the remote controller display shows 

” (time to clean the air filter);

Refer to the operation manual of the indoor unit. 
And clean the air filter.

3. The system operates but cooling or heating is 

insufficient;

• Check if air inlet or outlet of outside or indoor unit 

is not blocked by obstacles.
Remove any obstacle and make it well-ventilated.

TEST

Switch

ON

OFF

Trip position

Breaker

01_EN_3P215731-1D.fm  Page 14  Tuesday, February 5, 2008  6:35 PM

Summary of Contents for REYQ120PTJU

Page 1: ...2PTJU RXYQ216PTJU RXYQ240PTJU Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner English F...

Page 2: ...1 RXYQ REYQ F 2 3 F F 4 5 6 7 1 7 3 7 2...

Page 3: ...F 8 9 F F 10 11 12 Ceiling Suspended Wall Mounted Double flow Multi flow Corner Ceiling Suspended Wall Mounted Double flow Multi flow Corner 13 1 13 2 15 14...

Page 4: ...or moderate injury It may also be sued to alert against unsafe practices NOTE Indicates a situation that may result in the unit or property damage only accidents Keep these warning sheets handy so tha...

Page 5: ...will cause injury Operating the air conditioner with wet hands could result in a shock hazard Check the unit stand for damage on a contin uous basis especially if it has been in use for a long time If...

Page 6: ...etergent squeeze it well and wipe the panel clean And wipe it with another dry cloth Dismantling of the unit treatment of the refrig erant oil and eventual other parts should be done in accordance wit...

Page 7: ...0 1 20 1 20 1 Design pressure High side psig 478 478 Low side psig 320 320 Model name RXYQ72PTJU RXYQ96PTJU RXYQ120PTJU Power supply Phase 3 3 3 Frequency Hz 60 60 60 Voltage V 208 230 208 230 208 230...

Page 8: ...eating capacity MBh 243 270 66 1 8 36 5 8 30 1 8 66 1 8 36 5 8 30 1 8 Dimensions H W D inch 66 1 8 36 5 8 30 1 8 66 1 8 36 5 8 30 1 8 Mass Ib 573 573 573 573 Refrigerant type R410A R410A charge 1 Ib 1...

Page 9: ...he chapter 6 4 PROGRAMMING START AND STOP OF THE SYSTEM WITH TIMER 18 Temperature setting button Use this button for setting the desired temperature Refer to the chapter 6 1 COOLING HEATING AUTOMATIC...

Page 10: ...n REYQ only In this operation mode cool heat changeover is automatically conducted The operation mode cannot be changed with the remote controller whose display shows changeover under control Change t...

Page 11: ...r will return to the previous state in approximately 5 to 15 minutes Hot start In order to prevent cold air from blowing out of an indoor unit at the start of heating oper ation the indoor fan is auto...

Page 12: ...LOW DIREC TION Refer to figure 6 only for Dou ble flow Multi flow Corner Ceiling suspended and Wall mounted Press the air flow direction adjust but ton to select the air direction The air flow flap di...

Page 13: ...3 hours and start the system after 4 hours the system will stop after 3 hours and start 1 hour later 6 5 SETTING THE MASTER REMOTE CON TROLLER In the case of the system as shown in figure 14 only the...

Page 14: ...setting of group control and two remote controller control systems 7 OPTIMUM OPERATION Observe the following precautions to ensure the system operates properly Prevent direct sunlight from entering a...

Page 15: ...to conserve energy Clean the exterior See the operation manual included with the indoor unit for details on how to clean it 9 FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROUBLES 9 1 THE SYSTEM DOES NO...

Page 16: ...on Moisture generated by defrost becomes steam and is exhausted 9 8 NOISE OF AIR CONDITIONERS Indoor unit A zeen sound is heard immediately after the power supply is turned on The electronic expansion...

Page 17: ...operation The operation mode selector button does not work well Turn off the power If the display the unit number and the operation lamp flash and the malfunction code appears Refer to figure 12 1 In...

Page 18: ...on the remote controller Name address telephone number Repair after the warranty term is expired Contact your dealer If necessary to repair pay service is available Minimum storage period of important...

Page 19: ...ended lengths of time until the need arises for maintenance work in order to ensure the product is operational as long as possible Use for appropriate maintenance design budgeting maintenance and insp...

Page 20: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 1D EM07A037A 0803 HT...

Reviews: