21
English
(If operated with a thermistor, sensor or similar parts removed, the
compressor may be broken down.)
• Never connect the power supply in reverse-phase.
• Make sure the electrical imbalance ratio is no greater than 2%.
If it is larger than this, the unit’s lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an error
code will be displayed on the indoor remote controller.
•
%QPPGEVVJGYKTGUGEWTGN[WUKPIFGUKIPCVGFYKTGCPFƂZKVYKVJ
CVVCEJGFENCORYKVJQWVCRRN[KPIGZVGTPCNRTGUUWTGQPVJGVGTOKPCN
parts (terminal for power wiring, terminal for transmission wiring
and ground terminal).
• If there exists the possibility of reverse-phase, lost phase,
momentary blackout or the power goes on and off while the
product is operating, attach a reverse-phase protection circuit
locally.
Running the product in reverse-phase may break the compres-
sor and other parts.
• The appliance incorporates grounding connections for functional
purpose in addition to protective ground.
9.1. Power circuit, safety device and cable requirements
• Make sure to apply the rated voltage of 208/230V or 460V for the
unit.
• A power circuit (see the following table) must be provided for con-
nection of the unit. This circuit must be protected with the required
safety devices, i.e. a main switch, a slow blow fuse on each phase.
• When using residual current operated circuit breakers, be sure to
use a high-speed type (0.1 seconds or less) 200 mA rated residual
operating current.
• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with
relevant local and national regulations.
Model name
Phase and
frequency
Voltage
Minimum circuit
amp.
/CZKOWO
overcurrent
protective device
Transmission
line selection
REYQ72AATJ*
REYQ96AATJ*
REYQ120AATJ*
REYQ144AATJ*
REYQ168AATJ*
REYQ192AATJ*
REYQ216AATJ*
REYQ240AATJ*
REYQ264AATJ*
REYQ288AATJ*
REYQ312AATJ*
REYQ336AATJ*
REYQ360AATJ*
REYQ384AATJ*
REYQ408AATJ*
REYQ432AATJ*
REYQ456AATJ*
REYQ480AATJ*
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
208/230V
27.3
34.1
36.5
47.8
54.9
59.8
67.2
73.7
36.5+47.8
47.8+47.8
47.8+54.9
54.9+54.9
54.9+59.8
59.8+59.8
59.8+67.2
67.2+67.2
67.2+73.7
73.7+73.7
35
40
45
60
70
70
80
90
45+60
60+60
60+70
70+70
70+70
70+70
70+80
80+80
80+90
90+90
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
REYQ72AAYD*
REYQ96AAYD*
REYQ120AAYD*
REYQ144AAYD*
REYQ168AAYD*
REYQ192AAYD*
REYQ216AAYD*
REYQ240AAYD*
REYQ264AAYD*
REYQ288AAYD*
REYQ312AAYD*
REYQ336AAYD*
REYQ360AAYD*
REYQ384AAYD*
REYQ408AAYD*
REYQ432AAYD*
REYQ456AAYD*
REYQ480AAYD*
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
I
3,
60Hz
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
460V
12.4
16.4
16.6
21.3
24.9
28.3
29.9
33.4
16.6+21.3
21.3+21.3
21.3+24.9
24.9+24.9
24.9+28.3
28.3+28.3
28.3+29.9
29.9+29.9
29.9+33.4
33.4+33.4
15
20
20
25
30
35
35
40
20+25
25+25
25+30
30+30
30+35
35+35
35+35
35+35
35+40
40+40
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
AWG18-16
9.2. Wiring connection example for whole system
1
1
2
3
4
3
7
8
5
6
2
1
2
3
4
5
6
7
8
Power supply
Main switch
Fuse or circuit breaker
Outdoor unit
COOL/HEAT selector
Remote controller
Indoor unit
Branch Selector unit
6JKUKOCIGKUKPVGPFGFCUCPGZCORNGQPN[2NGCUGHQNNQYNQECNCPF
national electrical code.
NOTE
• Make sure the low voltage wiring (i.e. for the remote controller, between
units) and the power wiring do not pass near each other, keeping them
at least 1-15/16 in. (50 mm) apart.
2TQZKOKV[OC[ECWUGGNGEVTKECNKPVGTHGTGPEGOCNHWPEVKQPUCPF
breakage.
• Be sure to connect the power wiring to the power wiring terminal
block and secure it as described in 9.5. Power wiring connection
procedure on page 23.
• Transmission wiring should be secured as described in 9.4. Trans-
mission wiring connection procedure on page 22.
• Secure wiring with clamp such as insulation lock ties to avoid con-
tact with piping.
•
5JCRGVJGYKTGUVQRTGXGPVVJGUVTWEVWTGUWEJCUVJGEQPVTQNDQZ
EQXGTFGHQTOKPI#PFENQUGVJGEQXGTƂTON[
•
#NNƂGNFYKTKPIKUVQDGRTQEWTGFQPUKVG
9.3. Leading wire procedure
• The power wiring and ground wiring are passed out from the power
wiring hole on the front (slit hole).
• The transmission wiring is passed out from the wiring hole (slit hole)
on the front of the unit.
1
2
3
4
1
2
3
4
9KTKPIFKCITCORTKPVGFQPVJGDCEMQHVJGEQPVTQNDQZEQXGT
Slit hole
Power line
Transmission line
B(1B0DLQB959B,0LQGG