• Split Sky Air • Outdoor Units
7
• Outdoor Units • R-410A • REQ-B7
2
Specifications
2 - 3
Electrical data
REQ100B7
Unit combination
Power supply
Compressor
OFM
IFM
Indoor unit
Outdoor unit
Hz-Volts
Voltage range
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
FCQ100
REQ100B7V3B
50-230
Max. 50Hz-253V
Min. 50Hz-207V
23.8
34.8
40
98.5
17.6
0.090
0.8
0.090
1.0
FHQ100
REQ100B7V3B
50-230
25.3
34.5
40
98.5
19.0
0.090
0.8
0.130
0.7
FBQ100
REQ100B7V3B
50-230
23.2
34.8
40
98.5
17.1
0.090
0.8
0.135
1.0
FDEQ100
REQ100B7V3B
50-230
24.2
34.8
40
98.5
17.9
0.090
0.8
0.135
1.0
FCQ100
REQ100B7W1B
50-400/230
Max. 50Hz-440/253V
Min. 50Hz-360/207V
9.2
11.8
16
48.2
5.9
0.090
0.8
0.090
1.0
FHQ100
REQ100B7W1B
50-400/230
9.4
11.5
16
48.2
6.3
0.090
0.8
0.130
0.7
FBQ100
REQ100B7W1B
50-400/230
8.9
11.8
16
48.2
5.7
0.090
0.8
0.135
1.0
FDEQ100
REQ100B7W1B
50-400/230
9.6
11.8
16
48.2
6.2
0.090
0.8
0.135
1.0
3TW26619-9
SYMBOLS
MCA
: Min. Circuit Amps
TOCA
: Total Over Current Amps
MFA
: Max. Fuse Amps (see note 7)
LRA
: Locked Rotor Amps
RLA
: Rated Load Amps
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
kW
: Rated motor output
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.5°CWB
Outdoor temp. : 35°CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed
operation range limits
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 x RLA + all FLA, MFA = < 2.25 x RLA + all FLA
(next lower standard fuse rating Min. 16A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker
8. For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select ’’Daikin
Documentation’’ and select ’’conditional connection’’, ’’the
requested product type’’ and ’’English’’ from the drop down
lists, click the search button.
Finally, click on the document title of your choice.