![background image](http://html1.mh-extra.com/html/daikin/req100b8v3b/req100b8v3b_technical-data-manual_2459805012.webp)
1
4
• Split Sky Air • Outdoor Units
12
• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B
4
Safety device settings
REQ71
∼
125B
Model
Safety device
REQ71BV3
REQ100BV3
REQ125BW1
REQ71BW1
REQ100BW1
Fan motor thermal protector
Off 135 ±5°C
On 95 ±15°C
HPS
Off 4,15
Mpa
On 3.2
Mpa
LPS
Off -0.03
Mpa
On 0.05
Mpa
Max discharge temperature
By thermistor and software control
Overcurrent relay
By overcurrent sensor and software control
4TW26321-2B
+0
- 0,10
+0,15
- 0,15
+0,02
- 0,02
+0,03
- 0,03