• Outdoor Units • R-410A • REQ-B7
• Split Sky Air • Outdoor Units
30
37
9
9
Installation
9 - 1
Installation method
4TW25149-8
REQ71
∼
125B7
Oil trap
Indoor unit
Oil trap
Gas piping
Liquid piping
Outdoor unit
Install
trap
at
each
difference
in
eight
of
15m
NOTE:
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid
compression phenomenon, or cases of deterioration of oil return, it well be necessary to provide a trap at an appropriate
place in the riser gas piping.
A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.