
EDUS39-802A-R2_a
48
REYQ-P Heat Recovery (208-230V)
REYQ144PTJU
[Explanation of symbols]
Hp : Level difference (ft) between indoor and outdoor units where
indoor unit in inferior position
H
M
: Level difference (ft) between indoor and outdoor units where
indoor unit in superior position
L
: Equivalent pipe length (ft)
α
: Capacity correction factor
[Diameter of pipe (standard size)]
1. Rate of change in cooling capacity
0.97
0.97
0.95
0.95
0.92
0.92
0.90
0.90
1.0
1.0
40
120
120
240
400
80
280
240
360
200
80
0
200
600
280
440
160
520
560
0
40
320
0
160
120
480
40
80
160
Hp
(ft)
H
M
(ft)
L (ft)
1.0
1.0
2. Rate of change in heating capacity
0
80
40
280
0
240
160
200
80
40
160
120
120
80
40
200
240
160
320
280
360
0
120
Hp
(ft)
H
M
(ft)
L (ft)
[Notes]
1. These figures illustrate the rate of change in capacity of a standard indoor unit system at
maximum load (with the thermostat set to maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in
capacity shown in the above figures.
2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing
pressure constant control when heating is carried out.
3. Method of calculating A/C (cooling/heating) capacity:
The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units
obtained from capacity characteristic table or the maximum A/C capacity of outdoor units as
mentioned bellow, whichever smaller.
Calculating A/C capacity of outdoor units
•
Condition: Indoor unit combination ratio does not exceed 100%.
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity
characteristic table at the 100% combination
× Capacity change rate due to piping length to the
farthest indoor unit
•
Condition: Indoor unit combination ratio exceeds 100%.
Maximum A/C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity
characteristic table at the combination
× Capacity change rate due to piping length to the
farthest indoor unit
4. When overall equivalent pipe length is 295.3ft or more, the diameter of the main liquid pipes
(outdoor unit-branch sections) must be increased.
When level difference is 164.0ft or more, the diameter of the main liquid pipe (outdoor unit-branch
sections) must be increased.
[Diameter of above case]
liquid
Model
REYQ144PYDN
REYQ144PTJU
φ
5/8
6. In the combination which does not include cooling only indoor unit, Calculate the
equivalent length pipe by the following when you calculate cooling capacity.
200ft
Indoor unit
100ft
Equivalent length
Outdoor unit
Branch
BS unit
Equivalent length
(Example)
5. When the main sections of the interunit liquid pipe diameters are increased the overall equivalent
length should be calculated as follows. (Heating only)
200ft
Indoor unit
100ft
Equivalent length
Outdoor unit
Branch
BS unit
Liquid pipe :
Size increase
Equivalent length
(Example)
In the above case (Heating)
Overall equivalent length = 200ft × 0.3 + 100ft = 160ft
The correction factor in capacity when Hp = 0ft is thus approximately 1.0.
liquid
Model
REYQ144PYDN
REYQ144PTJU
φ
1/2
In the above case (Cooling)
Overall equivalent length = 200ft × 0.5 + 100ft = 200ft
The correction factor in capacity when Hp = 0ft is thus approximately 0.96.
Overall equivalent length = Equivalent length to main pipe × 0.5 + Equivalent length after branching
Overall equivalent length = Equivalent length to main pipe × 0.3 + Equivalent length after branching
3D058629
Summary of Contents for REMQ120PTJU
Page 1: ...EDUS 39 802A R2_a AMERICAS AMERICAS AMERICAS REYQ_PTJU 3 phase 208 230V 60Hz ...
Page 11: ...EDUS39 802A R2_a 10 REYQ P Heat Recovery 208 230V REYQ144PTJU 3D058640 ...
Page 12: ...EDUS39 802A R2 Piping Diagrams REYQ P Heat Recovery 208 230V 11 REMQ72PTJU 3D058637A ...
Page 13: ...EDUS39 802A R2_a 12 REYQ P Heat Recovery 208 230V REMQ96 120PTJU 3D058638A ...
Page 21: ...EDUS39 802A R2_a 20 REYQ P Heat Recovery 208 230V 3D060213 ...