58
RELQ-TATJA / TAYDA / TAYCA
EDUS371705C-D
Capacity table of indoor unit
Cooling Capacity
Model
Capacity
indication
Indoor air temp.°FWB (Te: 43°F (6°C))
61
64
67
70
72
75
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
FXMQ07PBVJU
07
5.7
5.5
6.4
5.9
7.2
6.1
7.3
6.5
7.4
5.8
7.6
5.8
FXMQ09PBVJU
09
7.5
6.9
8.5
7.3
9.5
7.8
9.7
8.1
9.8
7.1
10.0
7.2
FXMQ12PBVJU
12
9.5
8.5
10.7
9.1
12.0
9.7
12.2
10.0
12.4
9.2
12.6
9.2
FXMQ15PBVJU
15
11.2
10.2
12.7
10.7
14.2
11.4
14.5
11.6
14.7
11.5
14.9
9.6
FXMQ18PBVJU
18
14.2
13.9
16.1
14.7
18.0
15.6
18.4
16.1
18.6
14.6
18.9
12.1
FXMQ24PBVJU
24
19.0
16.5
21.5
17.7
24.0
18.8
24.5
19.2
24.8
17.9
25.3
20.1
FXMQ30PBVJU
30
23.7
20.8
26.8
22.3
30.0
23.8
30.6
24.4
31.0
22.5
31.6
22.5
FXMQ36PBVJU
36
28.4
25.0
32.2
26.9
36.0
28.8
36.7
30.0
37.2
27.7
37.9
27.7
FXMQ48PBVJU
48
37.9
31.3
43.0
33.6
48.0
35.8
49.0
36.9
49.6
34.7
50.5
33.2
FXMQ54PBVJU
54
42.6
35.2
48.3
37.8
54.0
40.3
55.1
41.5
55.8
39.0
56.8
37.4
TC : Total capacity: MBH
SHC : Sensible heat capacity: MBH
Selection results of indoor units
Room A
Room B
Room C
Room D
Room E
Room F
Room G
Room H
Max. heat load
(MBH)
36.1
36.4
17.3
17.3
30.9
30.8
14.1
14.1
Selected IDU
FXMQ48PBVJU FXMQ48PBVJU FXMQ18PBVJU FXMQ18PBVJU FXMQ36PBVJU FXMQ36PBVJU FXMQ15PBVJU FXMQ15PBVJU
Corrected TC
(MBH)
48.0
48.0
18.0
18.0
36.0
36.0
14.2
14.2
*
In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total Heat Load but
also the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for indoor air temperature. If the
design temperature of indoor air falls between temperatures listed in table, calculate sensible heat capacity by using the bypass factor
calculated by interpolation for each indoor air temperature.
[3] Selection of outdoor unit
[3] –1 Define the required total heat load from the indoor units to the outdoor unit
Define the required total heat load (A) based on (1) the sum of the peak load of each room or (2) the system peak load.
In this example, select an outdoor unit by (2).
Therefore, (A) = 173.0 MBH
Summary of Contents for RELQ-TATJA Series
Page 2: ......
Page 32: ...30 RELQ TATJA TAYDA TAYCA EDUS371705C D 12 Center of Gravity RELQ72TATJA TAYDA TAYCA 4D107384 ...
Page 33: ...31 RELQ TATJA TAYDA TAYCA EDUS371705C D RELQ96 120TATJA TAYDA TAYCA 4D107385 ...
Page 35: ...33 RELQ TATJA TAYDA TAYCA EDUS371705C D 14 Piping Diagrams RELQ72TATJA TAYDA TAYCA 3D107166 ...
Page 36: ...34 RELQ TATJA TAYDA TAYCA EDUS371705C D RELQ96 120TATJA TAYDA TAYCA 3D107167 ...
Page 55: ...53 RELQ TATJA TAYDA TAYCA EDUS371705C D RELQ96TATJA TAYDA TAYCA 4D107377A ...
Page 56: ...54 RELQ TATJA TAYDA TAYCA EDUS371705C D RELQ120TATJA TAYDA TAYCA 4D107378A ...
Page 65: ...63 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Page 66: ...64 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Page 67: ...65 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Page 68: ...66 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Page 69: ...67 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Page 70: ...68 RELQ TATJA TAYDA TAYCA EDUS371705C D 1P385984 1A ...
Page 71: ...69 RELQ TATJA TAYDA TAYCA EDUS371705C D 3P385987 1A ...
Page 72: ...70 RELQ TATJA TAYDA TAYCA EDUS371705C D 3P385987 1A ...
Page 83: ......