Si01-779

Removal of Electrical Components ASSY

Removal Procedure

5

6

Remove the screw.

7

Lift up and remove the 
electrical components 
ASSY.

Step

Procedure

Points

(R2360)

(R2361)

Summary of Contents for RD50FV1K

Page 1: ...REMOVAL PROCEDURE S E R V I C E M A N U A L 5 0 6 0 kW Class Outdoor Unit Non Inverter Pair Type Si01 779 ...

Page 2: ...Service Manual Removal Procedure Outdoor Unit zCooling Only R50BV1 R60BV1 R60BVL R50CV1A R60CV1A RD50FV1K ...

Page 3: ...79 Removal Procedure 1 Table of Contents 1 Removal of Outer Panels 2 2 Removal of Electrical Components ASSY 3 3 Removal of Compressor 6 Note The illustrations may be slightly different depending on the model ...

Page 4: ...ure Points 1 Remove the 4 screws A and remove the top panel 2 Remove the 6 screws B and remove the front panel 3 Remove the 2 screws and remove the service cover 4 Remove the 6 screws C and remove the side panel R2307 B B B A A A A B B B Front panel Top panel Service cover Side panel R2292 Earth terminal Interconnecting wire terminal Power supply terminal Screw with washer R2291 R2295 C C C C C Si...

Page 5: ...es before disassembling work Step Procedure Points 1 Disconnect the relay connector for the fan motor 2 Detach the outdoor air thermistor and the outdoor heat exchanger R3177 Attach it to the 3rd row of the outdoor heat exchanger at 30 mm from the left end when reassembling Thermistor retaining spring Thermistor R2354 Route thermistor wire through the specified section to prevent wire pinching ...

Page 6: ...et top 4 Remove the terminal cover The designs of terminal cover and compressor terminal vary depending on the model 5 Remove the overload protector and the 3 lead wires for the compressor together with mounting plate Step Procedure Points R2355 R2356 S yellow M red C blue R12920 R2359 R12891 ...

Page 7: ...Si01 779 Removal of Electrical Components ASSY Removal Procedure 5 6 Remove the screw 7 Lift up and remove the electrical components ASSY Step Procedure Points R2360 R2361 ...

Page 8: ...oth so as to extinguish fire immediately Caution From the viewpoint of global environment protection do not discharge the refrigerant gas in the atmosphere Make sure to collect all the refrigerant gas Cautions for restoration 1 Restore the piping by non oxidation brazing 2 It is required to prevent the carbonization of the oil inside the four way valve and the deterioration of the gaskets affected...

Page 9: ...nto the circuit When withdrawing the pipes be careful not to pinch them firmly with pliers The pipes may get deformed Provide a protective sheet or a steel plate so that the brazing flame cannot influence peripheries Be careful so as not to burn the compressor terminals the name plate the heat exchanger fin 4 Lift the compressor up and remove it Step Procedure Points R12806 ...

Page 10: ...Revision History Month Year Version Revised contents 07 2013 Si01 779 First edition ...

Page 11: ...sories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage electrical shock fire or explosion z Read the User s Manual carefully before using this product The User s Manual provides important safety instruc...

Reviews: