![Daikin RD50FV1K Service Manual Download Page 5](http://html.mh-extra.com/html/daikin/rd50fv1k/rd50fv1k_service-manual_2459783005.webp)
Si01-779
Removal of Electrical Components ASSY
Removal Procedure
3
2. Removal of Electrical Components ASSY
Procedure
Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1
Disconnect the relay
connector for the fan
motor.
2
Detach the outdoor air
thermistor and the
outdoor heat
exchanger.
(R3177)
Attach it to the 3rd row of
the outdoor heat exchanger
at 30 mm from the left end
when reassembling.
Thermistor retaining spring
Thermistor
(R2354)
Route thermistor wire
through the specified
section to prevent wire
pinching.