INSTALLATION OF THE INDOOR UNIT
The indoor unit must be installed such that there is no short
circuit of the cool discharge. Respect the installation clearance.
Do not put the indoor unit where there is direct sunlight on unit.
The location is suitable for piping and drainage and it must have
a large distance between a door and unit.
Ceiling Concealed Mounting
Use the hanger supplied with the unit.
Make sure that the ceiling is suf
Þ
ciently strong to withstand
the weight.
•
•
Field supply
Washer for hanger bracket
(attached)
Tighten
Detail A
See Detail A
Air inlet side
Air outlet side
Aluminium tape
(
Þ
eld supply)
Insulation material
(
Þ
eld supply)
Center distance of axle (see drawing below)
Provide clearance for servicing ease and optimal air
ß
ow as
shown in the diagram.
10m
m
300mm* or more
* Can be smaller than 300mm if ceiling is removable.
Aluminium tape
(
Þ
eld supply)
Model
A mm (inch)
L mm (inch)
FDM20JEV1K
1041(41.0)
225(8.9)
FDM25JEV1K
1176(46.3)
225(8.9)
FDM30JEV1K
1262 (49.7)
284 (11.2)
FDM40JEV1K
1262 (49.7)
284 (11.2)
FDM50JEV1K
1326 (52.2)
256 (10.1)
FDM60JEV1K
1526 (60.1)
256 (10.1)
Ceiling
2300mm or more
Floor
300mm
or more
A
L