background image

technical data

RXS-G2V1B

Outdoor units

air conditioning systems

Split -
Sky Air

EEDEN0

9

-100

Summary of Contents for R-410A

Page 1: ...technical data RXS G2V1B Outdoor units air conditioning systems Split Sky Air EEDEN09 100...

Page 2: ...RXS G2V1B Outdoor units EEDEN08 100 technical data air conditioning systems Split Sky Air...

Page 3: ...l Input 3 Technical Specifications 6 Electrical Specifications 7 3 Electrical data 8 4 Capacity tables 13 Cooling Heating capacity tables 13 5 Dimensional drawing centre of gravity 25 Dimensional draw...

Page 4: ...l i t S k y R X S G 2 V 1 B R 4 1 0 A Outdoor units for pair application Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wal...

Page 5: ...4 040 4 470 5 160 5 590 Power Input Cooling Minimum kW 0 32 0 32 0 35 0 44 0 44 Standard kW 0 47 0 55 0 87 1 22 1 52 Maximum kW 0 91 0 81 1 19 2 23 1 81 Heating Minimum kW 0 31 0 31 0 34 0 40 0 40 St...

Page 6: ...970 Power Input Cooling Minimum kW 0 30 0 30 0 50 Standard kW 0 57 1 02 1 55 Maximum kW 0 92 1 25 2 00 Heating Minimum kW 0 29 0 31 0 50 Standard kW 0 79 1 22 1 60 Maximum kW 1 39 1 88 2 60 For combin...

Page 7: ...onsumption kWh 365 550 900 Indoor Units FCQ35C7VEB FCQ50C7VEB Cooling capacity Standard kW 3 40 5 00 Heating capacity Standard kW 4 20 6 00 Power Input Cooling Standard kW 0 95 1 41 Heating Standard k...

Page 8: ...Rows 1 2 2 2 2 Fin Pitch mm 1 4 1 4 1 4 1 5 1 8 Nr of Stages 24 24 24 24 32 Tube type Hi Xa 7 Hi Xa 7 Hi Xa 7 Hi Xa 8 Hi Xa 8 Fin Type Waffle fin Treatment Anti corrosion treatment PE Fan Type Propel...

Page 9: ...ssories Item Installation manual Quantity 1 1 1 1 1 Item Drain plug Quantity 1 Notes Nominal cooling capacities are based on indoor temperature 27 CDB 19 0 CWB outdoor temperature 35 CDB 24 CWB refr p...

Page 10: ...LA Rated Load Amps A OFM Outdoor Fan Motor IFM Indoor Fan Motor FLA Full Load Amps A W Fan Motor Rated Output W RHz Rated Operated Frequency Hz 3D055008B Representative Unit Combination Power Supply C...

Page 11: ...ased on the larger value of MCA 4 Instead of fuse use circuit breaker 5 For more details concerning conditional connections see http extranet daikineurope com select E Data Books Finally click on the...

Page 12: ...Data Books Finally click on the document title of your choice SYMBOLS MCA Min Circuit Amps A MFA Max Fuse Amps A see note 4 A RHZ Rated Operating Frequency Hz RLA Rated Load Amps A OFM Outdoor Fan Mot...

Page 13: ...based on the larger value of MCA 4 Instead of fuse use circuit breaker 5 For more details concerning conditional connections see http extranet daikineurope com select E Data Books Finally click on the...

Page 14: ...98V 19 75 20 70 6 6 53 0 27 23 0 15 50 230 6 2 SIMBOLS NOTES MCA Min circuit amps A 1 RLA is based on the following conditions Indoor temp 27C DB 19 CWB Outdoor Temp 35 CDB 2 Maximum allowable voltage...

Page 15: ...0 6 10 C TC PI TC PI TC PI TC PI TC PI 15 0 1 82 0 53 2 12 0 56 2 43 0 58 2 79 0 62 3 04 0 64 20 0 1 72 0 55 2 03 0 57 2 33 0 60 2 70 0 63 2 94 0 65 22 0 1 69 0 55 1 99 0 58 2 30 0 60 2 66 0 64 2 91 0...

Page 16: ...0 6 10 C TC PI TC PI TC PI TC PI TC PI 15 0 2 29 0 63 2 67 0 67 3 06 0 70 3 52 0 73 3 82 0 76 20 0 2 17 0 65 2 56 0 68 2 94 0 71 3 40 0 75 3 71 0 77 22 0 2 12 0 66 2 51 0 69 2 89 0 72 3 35 0 76 3 66 0...

Page 17: ...PI TC SHC PI Heating 50Hz 220 240V AFR 9 Indoor Outdoor temperature CWB EDB 10 5 0 6 10 C TC PI TC PI TC PI TC PI TC PI 3D055487 SYMBOLS AFR Air flow rate m3 min BF Bypass factor EWB Entering wet bul...

Page 18: ...6 10 C TC PI TC PI TC PI TC PI TC PI 15 0 2 69 0 81 3 14 0 85 3 60 0 89 4 14 0 94 4 50 0 97 20 0 2 55 0 83 3 01 0 87 3 46 0 91 4 00 0 96 4 36 0 99 22 0 2 50 0 84 2 95 0 88 3 40 0 92 3 94 0 97 4 31 1...

Page 19: ...PI TC SHC PI Heating 50Hz 220 240V AFR 10 Indoor Outdoor temperature CWB EDB 10 5 0 6 10 C TC PI TC PI TC PI TC PI TC PI 3D055489 SYMBOLS AFR Air flow rate m3 min BF Bypass factor EWB Entering wet bu...

Page 20: ...HC PI TC SHC PI Heating 50Hz 220 240V AFR 12 5 Indoor Outdoor temperature CWB EDB 10 5 0 6 10 C TC PI TC PI TC PI TC PI TC PI 3D057246 SYMBOLS AFR Air flow rate m3 min BF Bypass factor EWB Entering we...

Page 21: ...0 91 3 79 3 33 0 98 3 73 3 31 1 02 3 63 3 28 1 06 3 48 3 22 1 14 24 0 32 4 27 3 37 0 83 4 11 3 32 0 91 3 95 3 27 0 99 3 89 3 25 1 02 3 79 3 22 1 07 3 63 3 18 1 15 Indoor Outdoor temperature CWB EDB 1...

Page 22: ...00 1 42 5 58 3 92 1 54 5 49 3 88 1 59 5 35 3 83 1 66 5 11 3 75 1 78 24 0 32 6 27 3 98 1 30 6 04 3 90 1 42 5 81 3 83 1 55 5 72 3 80 1 60 5 58 3 75 1 67 5 34 3 68 1 79 Indoor Outdoor temperature CWB EDB...

Page 23: ...6 10 C TC PI TC PI TC PI TC PI TC PI 15 0 3 64 1 24 4 24 1 30 4 85 1 36 5 59 1 44 6 07 1 49 20 0 3 45 1 28 4 06 1 34 4 67 1 40 5 40 1 47 5 89 1 52 22 0 3 37 1 29 3 98 1 35 4 59 1 41 5 33 1 48 5 81 1 5...

Page 24: ...0 6 10 C TC PI TC PI TC PI TC PI TC PI 15 0 3 90 1 33 4 56 1 39 5 21 1 46 6 00 1 53 6 52 1 59 20 0 3 70 1 36 4 36 1 43 5 01 1 49 5 80 1 57 6 32 1 62 22 0 3 62 1 38 4 28 1 44 4 93 1 51 5 72 1 58 6 24 1...

Page 25: ...b temp C EDB Entering dry bulb temp C TC Total capacity kW SHC Sensible heating capacity kW PI Power input kW NOTES 1 Ratings shown are net capacities which include a deduction for indoor fan motor he...

Page 26: ...HC PI TC SHC PI Heating 50Hz 220 240V AFR 12 5 Indoor Outdoor temperature CWB EDB 10 5 0 6 10 C TC PI TC PI TC PI TC PI TC PI 3D057248 SYMBOLS AFR Air flow rate m3 min BF Bypass factor EWB Entering we...

Page 27: ...Of Removing Stop Valve Cover Gas Stop Valve 9 5 CuT Outdoor Air Thermistor Wall Height On Air Outlet Side Less Than 1200 MINIMUM SPACE FOR AIR PASSAGE RXS50G 4 Holes for anchor bolts M8 or M10 Drain...

Page 28: ...Outdoor Units R 410A RXS G2V1B Split Sky Air Outdoor Units 26 5 Dimensional drawing centre of gravity 5 2 Centre of gravity 3 24 5 RXS42G 4D059009B RXS50G The position of foundation bolt 4D051638L...

Page 29: ...6 4 CuT 6 4 CuT 7 0CuT Heat exchanger Thermistor 9 5 CuT 9 5 CuT 7 9 CuT 7 5 CuT Discharge pipe Thermistor Accumulator 4 0 x ID 2 OCuT RXS25 35G 6 4 CuT 6 4 CuT 9 5 CuT 9 5 CuT 9 5 CuT Propeller Fan...

Page 30: ...CuT 12 5 CuT Muffler With Filter 9 5 CuT 4 0 x ID 2 OCuT 7 5 CuT 7 5 CuT 3D059590A RXS50G 7 9 CuT 7 9 CuT 7 9 CuT 7 9 CuT 7 9 CuT 7 9 CuT 7 9 CuT 7 9 CuT 7 9 CuT 7 9 CuT 4 0 CuT 4 0 CuT 6 4 CuT 6 4 C...

Page 31: ...er Field wiring Indoor In case of cooling only type WIRING DIAGRAM In case of heat pump type RXS42G 3D059601 NOTES 1 Refer to purchasing specification AS303002 unless otherwise specified 2 This drawin...

Page 32: ...al Strip MRC W Magnetic Relay N Neutral M1F Fan Motor Y1E Electrionic Expansion Valve Coil R1T R3T Thermistor SW1 Forced Operation On Off SW SW1 L1R Reactor V2 V3 V5 V6 V 11 Varistor S2 S102 Connector...

Page 33: ...Octave band sound pressure level dB 0dB 0 0002 bar Approximate threshold hearing for continuous noise RXS20 25G HEATING Octave band center frequency Hz 1m 3D059593A NOTES 1 Operating conditons 50 Hz...

Page 34: ...itions Octave band sound pressure level dB 0dB 0 0002 bar Approximate threshold hearing for continuous noise RXS42G HEATING Octave band center frequency Hz 1m 3D059740A NOTES 1 Operating conditons 50...

Page 35: ...gh COOLING HEATING Indoor temp CWB Indoor temp CWB Outdoor temp CWB Outdoor temp CWB Continuous operation Continuous operation Pull down period RXS50G 3D028318M NOTES 1 The graphs are based on the fol...

Page 36: ......

Page 37: ...change without prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this...

Reviews: