background image

9

English

Outdoor Unit Installation

4. 

Pressure test and evacuating system

WARNING

•  Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
• 

If refrigerant gas leaks should occur, ventilate the room as soon and as much as possible.

• 

R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.

•  Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum 

pump or the unit.

• 

When piping work is complete, it is necessary to perform a pressure test 
and evacuate system with a vacuum pump.

• 

If using additional refrigerant, perform air purging of the refrigerant pipes 
and indoor unit using a vacuum pump, then charge additional refrigerant.

•  Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.
• 

All refrigerant pipe joints should be tightened with a torque wrench to the 

specified tightening torque.

Compound 
pressure gauge

Pressure 
meter

High-pressure 
valve

Low-pressure 
valve

Vacuum pump

Service port

Liquid 
stop 
valve

Valve caps

Gas stop valve

Charging 
hoses

Gauge 
manifold

1) Pressurize the liquid pipe and gas pipe from the service ports of each stop valve to 550psi (3.8MPa) (do not pressurize 

more than 550psi (3.8MPa)) for 1 hour minimum, 24 hours recommended. If there is a pressure drop, check for leaks, 
make repairs and perform the pressure test again. 

2) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.
3) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi). 

(High-pressure valve subsequently requires no operation.)

4) 

Evacuate system using vacuum pump to below 500 microns for 1 hour minimum.

5) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump. 

(Leave as is for 4-5 minutes and make sure the coupling meter needle does not go back. 
If it does go back, this may indicate the presence of moisture or leaking from connecting parts. After inspecting all the 
connection and loosening then retightening the nuts, repeat steps 3-5.)

6) Remove covers from liquid stop value and gas stop valve.
7) 

Turn the liquid stop valve’s rod 90° counter-clockwise with a hexagonal wrench to open the valve.

 

Close it after 5 seconds, and check for gas leakage. 

Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.

 

After the check is complete, wipe all soapy water off.

8) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves. 

(Do not attempt to turn valve rod beyond its stop.)

9) 

Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench to the specified torques.

 

Refer to 

“3. Refrigerant Piping”

 on page 8 for details.

01_EN_3P379970-9C.indd   9

10/17/2019   4:42:18 PM

Summary of Contents for R-410A

Page 1: ...ish Fran ais Espa ol MODELS 2MXS18NMVJU 2MXS18NMVJUA DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel dinstallat...

Page 2: ...oxygen A massive leak can lead to oxygen depletion especially in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes teleph...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...d radio sets This is to prevent interference to images and sounds Noise may be experienced even if they are more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places...

Page 5: ...t for one room only Be sure to connect at least 2 rooms Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line Wra...

Page 6: ...u The line set piping size is determined by the size of the indoor unit fittings Reducers are used at the outdoor unit to accommodate the correct gas line pipe size 3MXS24 4MXS36 Port 2MXS18 B 07 09 1...

Page 7: ...oor unit Connection port of outdoor unit Connection port of outdoor unit Be sure to attach the gasket No 5 No 6 Flare nut for 3 8 inch 9 5mm Be sure to attach the gasket No 4 No 2 Flare nut for 1 2 in...

Page 8: ...ecting a Location for Installation of the Indoor Units The maximum allowable length of refrigerant piping and the maximum allowable height difference between the outdoor and indoor units are listed be...

Page 9: ...nuts to prevent damage to the flare nuts and gas leakage Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with a spanner and a torque wrench Do...

Page 10: ...hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect projection side of charging hose which comes from gauge manifold to gas stop v...

Page 11: ...hen lling There is a siphon pipe inside so the cylinder need not be upside down to ll with liquid Filling other cylinders Turn the cylinder upside down when lling Be sure to use the R410A tools to ens...

Page 12: ...m I D 9 16 5 8 inch 14 16mm I D 5 8 13 16 inch 16 20mm I D 5 16 13 32 inch 8 10mm 13 32 inch 10mm Min Minimum bend radius Piping thickness Thermal insulation size Thermal insulation thickness Liquid s...

Page 13: ...rcuit interrupter itself Use an all pole disconnection type circuit breaker with at least 1 8 inch 3mm between the contact point gaps When carrying out wiring connection take care not to pull at the c...

Page 14: ...Shape the wires so that there is no lifting of the service hatch or other structural parts Use the speci ed wires and connect them securely Room A Room C Room D Room B power supply CAUTION Precautions...

Page 15: ...standby mode according to the operation mode of the set indoor unit 2 Priority during powerful operation If the indoor unit which is set for Priority Room Setting is operating at powerful the capabili...

Page 16: ...t Mode is running cooling capacity will be saved Setting procedure Turn the Night Quiet Mode switch SW6 1 to on Service PC board HEAT COOL 4 3 2 1 2 1 E D C B A Night Quiet Mode setting switch SW6 1 2...

Page 17: ...screws 3 Remove the service PC board switch cover 1 screw 4 Switch SW5 and SW6 to off 5 Turn the operation mode switch SW2 to COOL 6 Screw the service PC board switch cover back on 1 screw 7 Switch th...

Page 18: ...e manual If self correction is not possible check the indoor unit wiring and piping in the usual manner Service PC board A 1 2 3 4 5 Wiring error check switch SW3 LED Status 1 2 3 4 All Flashing Autom...

Page 19: ...e extension Is the drainage secure Are the ground wire connections secure Are the electric wires connected correctly Is the wiring in accordance with the speci cations Are the inlets outlets of the in...

Page 20: ...Two dimensional bar code is a manufacturing code 3P379970 9C M19B228 1912 HT...

Reviews: