8 Finishing the indoor unit installation

Installation manual

11

CVXM-A, FVXM-A, CVXM-A9, FVXM-A9, FVXTM-A
Split system air conditioners
3P477070-2P – 2022.09

3

Match  wire  colours  with  terminal  numbers  on  indoor  and
outdoor  unit’s  terminal  blocks  and  firmly  screw  wires  to  the
corresponding terminals.

4

Connect the earth wires to the corresponding terminals.

a
b

c

a

Terminal block

b

Electrical component block

c

Cable clamp

5

Pull  the  wires  to  make  sure  that  they  are  securely  attached,
then retain the wires with the cable clamp.

6

Make sure that the wires do not come in contact with the metal
parts of the heat exchanger.

7

In  case  of  connecting  to  an  optional  adapter,  see 

"7.3  To

connect optional accessories (wired user interface, central user
interface, wireless adapter, etc.)"

 [

4

 11].

7.3

To connect optional accessories
(wired user interface, central user
interface, wireless adapter, etc.)

1

Remove the electrical wiring box cover.

2

Connect  the  optional  adapter  wire  to  the  S21  connector.  To
connect  the  optional  adapter  wire  to  the  option,  refer  to  the
installation manual of the optional adapter.

3

Lead the wire as shown in the figure below.

a

b

a

S21connector

B

Optional adapter wire

4

Close the electrical wiring box cover.

8

Finishing the indoor unit
installation

8.1

To finish the indoor unit
installation

1

After the drain piping, refrigerant piping and the electrical wiring
are finished. Wrap the refrigerant pipes and the interconnection
cable with insulation tape. Overlap at least half the width of the
tape with each turn.

a

b

c

d

e

f

a

Interconnection cable

b

Gas pipe

c

Gas pipe insulation

d

Insulation tape

e

Liquid pipe

f

Liquid pipe insulation

2

Pass  the  pipes  through  the  wall  hole  and  seal  the  gaps  with
putty.

9

Configuration

INFORMATION

In case 2 indoor units are installed in 1 room, set different
addresses for 2 user interfaces. For procedure refer to the
installer  reference  guide,  for  location  see 

"1.1  About  this

document"

 [

4

 2].

10

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during commissioning and
hand-over to the user.

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

10.1

To perform a test run

Prerequisite: 

Power supply MUST be in the specified range.

Prerequisite: 

Test  run  may  be  performed  in  cooling  or  heating

mode.

Prerequisite: 

Test run should be performed in accordance with the

operation  manual  of  the  indoor  unit  to  make  sure  that  all  functions
and parts are working properly.

Summary of Contents for Perfera CVXM20A3V1B

Page 1: ...on manual Split system air conditioners English Installation manual Split system air conditioners CVXM20A3V1B FVXM25A3V1B FVXM35A3V1B FVXM50A3V1B CVXM20A3V1B9 FVXM25A3V1B9 FVXM35A3V1B9 FVXM50A3V1B9 FV...

Page 2: ...wiring diagram legend 12 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin includ...

Page 3: ...y connecting the piping to the indoor units DANGER RISK OF BURNING SCALDING CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas...

Page 4: ...Industries Czech Republic s r o declares that the radio equipment type inside of this unit is in compliance with Directive 2014 53 EU and S I 2017 1206 Radio Equipment Regulations 2017 This unit is c...

Page 5: ...m m is not listed below use the closest higher value The total refrigerant charge m the minimum floor area is Amin limitation depends also on room height H and if the unit is installed ABOVE or UNDER...

Page 6: ...ole location f Right bottom piping hole location 1 Drill a wall hole depending on which side piping is taken out See 5 2 2 To drill a wall hole 48 2 Open the front panel and remove the front grille 3...

Page 7: ...4 30 f 734 740 170 350 70 200 593 595 170 350 d e c c a A B mm a a 75 5 4 60 60 5 4 75 C 159 238 689 159 b b 0 6 75 75 5 4 h g 627 5 115 285 b b b b 300 5 3 Indoor unit installation drawing Half conce...

Page 8: ...ont grille same on the other side c Slit portion for side piping on the bottom frame same of the other side d Slit portion for the bottom piping 1 Cut off the slit portion using nippers 2 Remove an bu...

Page 9: ...ic acid deoxidised seamless copper for refrigerant piping INFORMATION Additional refrigerant charge is NOT allowed in case of combination of the outdoor unit 3MXM40 or 3MXM52 with the indoor units CVX...

Page 10: ...tact point gaps that provides full disconnection under overvoltage category III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified p...

Page 11: ...n 1 After the drain piping refrigerant piping and the electrical wiring are finished Wrap the refrigerant pipes and the interconnection cable with insulation tape Overlap at least half the width of th...

Page 12: ...atically Caution When the main power is turned OFF and then back on again operation will resume automatically Notice Applicable for units with refrigerant leakage sensor only Notice Applicable for uni...

Page 13: ...S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidi...

Page 14: ......

Page 15: ......

Page 16: ...3P477070 2P 2022 09 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: