background image

6

Daikin

 IM 777-7

Mechanical Installation

If the unit is supported on rails they must be placed around the 
entire perimeter. Additional Supports must be placed 
perpendicular to airflow spanning the full width of the unit at 
all shipping splits. If the unit is over 107” wide these supports 
must also be placed at the entering and leaving edges of fan 
and cooling coil sections. The perimeter rails must be at least 
2” wide at the top and capable of carrying the entire weight of 
the unit. The cross supports must be 4” wide at the top and 
capable of carrying the weight of the two sections it spans. The 
cross supports shall be placed such that 2” of the top is 
supporting each section. The perimeter rails shall be placed so 
that they are fully supporting the outer 2” of the unit. If shims 
are required they must be placed such that the unit is fully 
supported. 

Figure 4: Leveling the Unit

Assembling Sections

If the unit is shipped in more than one shipping section, rig 
each section into position separately. Shipping sections are 
provided with a connection splice joint attached on the leaving 
air side of the shipping section that seals against the frame 
channel on the entering-air side of the adjoining. The splice 
joint is insulated and provides an air-tight seal between two 
sections once they are assembled together. Align the splice 
joint to seat into the mating gasket to provide an air seal. If the 
splice joint was bent during shipping or rigging, restore it to its 
original position (

Figure 9

)

For Skyline 

Plus

 units, ensure that 

the D-gasket is attached to the entering air side frame channel 
(

Figure 7

 and 

Figure 10

).If it dislodged during shipping, 

restore it to its designed position.

Shipping Sections

1

Caulk all assembly joints of the unit—Before joining the 

sections, apply at least 1/4 inch diameter bead of sealant 
to the mating faces of the cabinet. Use the splice joint as 
a guide for applying the sealant (

Figure 5

).

Figure 5: Apply Sealant to Mating Faces

2

Pull sections together to fasten. Use straps and a ratchet 
to help pull the sections together securely.

 

Apply sealant 

to any gaps that may admit moisture.

3

Fasten base rails together first using the 3/8"-16 × 5" 
bolts located in the splice kit provided with the unit 
(

Figure 7

).

a

To fasten two shipping sections together, four bolts 
are needed (two on each side of the unit). The bolts 
are run from one base rail into the other and fastened 
with a nut. Complete each section bottom and top 
before attaching additional sections.

b

If desired, shipping sections for non curb-ready units 
can be fastened together internally. To fasten 
internally, run field-provided #10 sheet metal screws 
or drill screws (4" long, maximum) through the 
interior frame channel of one unit into the splice joint 
of the neighboring section.

c

Handle units with curb-ready bases and vestibules so 
the lifting bracket can be removed after the unit is 
placed on the curbing. 

Note: 

Remove the lifting bracket that projects inward over 

the curbing. Save the self tapping screws. When the 

adjacent section is placed in position, use self 

tapping screw to secure the bases together.

Figure 6: Remove Vestibule Lifting Bracket

Figure 7: Fasten Bottom of Section

S h m   t o   p r e v e n t  

d t o r t o n   f   w d t h  

  o v e r   1 0 8 "

S h m   e c t o n   u n t l  

t h e y   r e   t r g h t

n d   l e v e l

1 / 4 "   d

m e t e r

b e d   c e n t e r e d  

n   f c e   o f

c l e r n c e

U e   S p l c e  

J o n t  

   

g u d e

R e m o v b l e

L f t n g   B r c k e t

3/8" x 1" Bolt and Nut

“D”

    Gasket

Summary of Contents for OAH 003G

Page 1: ...Installation and Maintenance Manual IM 777 7 Skyline Air Handler Group Applied Air Systems Part Number IM 777 Date November 2011 2011 Daikin Models OAC OAH 003G 090G...

Page 2: ...eating Coils 14 Drain Pan Traps 14 Internal Isolation Assembly Adjustment 15 Electrical Installation 17 Wiring 17 Operation Guidelines 19 Startup Checks 19 Before Starting the Unit 19 VFD Setup 20 Fan...

Page 3: ...before leaving the factory Rough handling can cause misalignment or a damaged bearings or shaft Carefully inspect fans and shaft before unit installation to verify this has not happened Note Screws bo...

Page 4: ...rfaces Belt driven fans Reduce belt tension by at least 50 or remove the belts Remove belts if they will be subjected to temperatures exceeding 85 F to avoid deterioration Remove belt guard when adjus...

Page 5: ...nits are provided with a factory installed base rail and can be lifted using the 2 diameter lifting holes located in the corners of each shipping section To prevent damage to the unit cabinetry use sp...

Page 6: ...lodged during shipping restore it to its designed position Shipping Sections 1 Caulk all assembly joints of the unit Before joining the sections apply at least 1 4 inch diameter bead of sealant to the...

Page 7: ...ng included in the assembly kit Figure 8 Frame Channel Stiffener Plates Skyline Plus Units Only Figure 9 Internal Fastening Figure 10 D Gasket Placement Detail Skyline Plus Units Only 1 Check that the...

Page 8: ...on one side of the unit If requested on order doors can be provided on both sides of the unit Optional service doors are available for most section types and are provided based on customer request Fa...

Page 9: ...age can occur If larger heavier components require mounting on unit panels use through bolts with flat washers through both outer and inner panels To maintain panel integrity seal both ends with an in...

Page 10: ...ions are made for the location of these actuators due to the number of options and arrangements available and the variety of specific applications Typically actuators are mounted inside the cabinet Pr...

Page 11: ...r units that include a piping vestibule cut the openings for routing the field piping as required in the field Carefully seal passages cut through the panels to prevent air leakage A single metal thic...

Page 12: ...pen to the atmosphere and the trap design should allow venting of large quantities of air Traps Note Do not place steam traps outdoors Size traps in accordance with the manufacturers recommendations M...

Page 13: ...eturn main 12 min Vacuum breaker 1 2 check valve Steam main Return main 12 min Full size of return conn Check Valve Strainer Gate Valve Control valve modulating two position Float and thermostatic tra...

Page 14: ...l drain pan trap to allow condensate to drain freely On both blow through and draw through units the trap depth and the distance between the trap outlet and the drain pan outlet must be twice the stat...

Page 15: ...t panel opening If adjustment is required loosen the cap screw on top of the isolator assembly Turn the adjustment nut below the fan frame to lower or raise the fan motor and frame assembly Retighten...

Page 16: ...l t o r p o t o n n u m b e r D m H S p r n g h e g h t d j u t m e n t c r e w S p r n g h e g h t d j u t m e n t c r e w S h p p n g h o l d d o w n c r e w S h p p n g b r c k e t D e t l A S h p...

Page 17: ...gy storing components that have been furnished and mounted by either Daikin or by others refer to the specific manufacturer s literature for allowable waiting periods for discharge of capacitors Verif...

Page 18: ...n the exterior of the fan section When multiple fan sections are provided with multiple VFDs they must be set up so that the fans always start simultaneously and are set to ramp up and down together D...

Page 19: ...et couper la tension WARNING Fire electric shock hazard Can cause property damage personal injury or death Wire fan power supply and ground motor frame in accordance with local electric codes AVERTIS...

Page 20: ...rtain to retain sheave alignment Fan Wheel Alignment Figure 29 Wheel to Inlet Tunnel Relationship Airfoil Type Fan Wheels Housed Note 1 To obtain rated air performance dimensional relationship must be...

Page 21: ...lenum Fan Wheel Funnel Parameters Size A B C 13 0 25 0 91 3 50 15 0 25 0 91 3 50 16 0 25 0 91 3 50 18 0 38 0 86 3 88 20 0 42 1 11 3 88 22 0 45 1 11 3 88 24 0 51 1 11 3 88 27 0 55 1 36 4 50 30 0 62 1 3...

Page 22: ...Size Setscrew Size Torque ft lb Aluminum Steel 11 12 13 3 8 19 2 N A 15 3 8 19 2 N A 16 3 8 19 2 N A 18 3 8 19 2 N A 20 3 8 19 2 N A 22 3 8 19 2 N A 24 3 8 19 2 N A 27 3 8 19 2 22 30 1 2 41 7 55 33 1...

Page 23: ...1875 1691 1479 1328 1209 1073 Maximum rpm Class Il 2703 2413 2199 1928 1730 1579 1401 Table 17 Operating Limits Belt Drive Plenum Fans Fan Operating Limits Belt Drive Plenum Fans Size 13 15 16 18 20 2...

Page 24: ...on of potential trouble Vibration Causes 1 Wheel imbalance a Dirt or debris on wheel blades b Loose set screws in wheel hub or bearing to shaft c Wheel distorted from overspeed 2 Bent shaft 3 Drive fa...

Page 25: ...s are supplied with grease fittings or zerks for ease of lubrication with hand or automatic grease guns Always wipe the fitting and grease nozzle clean CAUTION Bearing overheating potential Can damage...

Page 26: ...g or decreasing the pitch diameter of the sheave by half or full turns as required Readjust belt tension before starting drive 6 To provide the same pitch diameter adjust both halves of the two groove...

Page 27: ...lts over grooves See Fan Drive Belt Adjustment page 30 10 Before starting the drive ensure that all keys are in place and all setscrews and all capscrews are tight Check and retighten all screws and r...

Page 28: ...a Do not open B sheaves more than 4 3 4 turns for the A belts or 6 turns for the B belts b Do not open C sheaves more than 9 1 2 turns c Do not open 5V sheaves more than 6 turns d Do not open 8V sheav...

Page 29: ...parallel A d j u t a b l e C e n t e r F l a n g e F x e d C e n t e r F l a n g e S t a t o n a r y E n d F l a n g e C a p c r e w D o N o t R e m o v e 2 L o c k n g S e t c r e w A F l a t h e a d...

Page 30: ...ter the filter compartment until the fan is completely stopped Use approved equipment for reaching filters located above normal reach Do not step on filter frames or unit components Floor surfaces mus...

Page 31: ...the final filters Figure 41 Filter Gauge F l t e r F r a m e R o t a t e W r e C l p P r e f l t e r F n a l F l t e r Table 27 Filter Pressure Drops Bag filters DriPak 2000 Efficiency 45 65 85 95 Rat...

Page 32: ...not responsible for the freezing of coils Removing and Replacing Components See Access Doors and Panels page 8 for instructions on removing panels and opening fan access doors to remove or replace co...

Page 33: ...ocated in the connections 2 Remove all screws and remove the access panel 3 Remove the screws holding the coil in place 4 Lift and pull the coil out the side Installing Single Coils 1 Slide the coil t...

Page 34: ...ce bolt the coil to the section 4 Caulk the mounting surface of the steel plate and install the plate on the coils 5 Caulk the mounting surface of the drain trough and install the drain trough on the...

Page 35: ...s refer to the model number and serial number of the unit stamped on the serial plate attached to the unit If replacement parts are required mention the date of installation of the unit and date of fa...

Page 36: ...rned material Enter the required information to expedite handling and prompt issuance of credits All parts must be returned to the appropriate Daikin facility designated on the Return Goods tag Transp...

Page 37: ...Yes No N A D Have the hold down bolts been backed off on spring mounted fan isolators Yes No N A E With power off do fans turn freely by hand Yes No N A F Electrical service corresponds to unit namepl...

Page 38: ...N A VII HEAT RECOVERY A Heat wheel rotates freely Yes No N A B Heat wheel VFD operates properly Yes No N A C Heat wheel VFD model _____________________ serial _____________________ N A D Check for ai...

Page 39: ...binet have any air leakage Yes No N A Location on unit ___________________________________________________________________________ 5 Were there any refrigerant leaks Yes No N A Shipping Workmanship De...

Page 40: ...tions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin Representative go to www DaikinApplie...

Reviews: