background image

Daikin

 IM 777-7

19

Operation Guidelines

Operation Guidelines

Startup Checks 

When performing startup and service, always take thorough 
safety precautions. Only trained, experienced personnel should 
perform these functions.

Before Starting the Unit:

Before entering fan section, make sure that fan electrical 
power source is disconnected and locked in the OFF position.

1

Check that the unit is completely and properly installed 

with ductwork connected. 

2

Check that construction debris is removed/filters are 
clean.

3

Check that all electrical work is complete and properly 
terminated.

4

Check that all electrical connections are tight and that the 
proper voltage is connected. Phase imbalance must not 
exceed 2%.

5

Check that ball bearings on the fan shaft and motor are 
prelubricated and do not need grease before startup. 

6

Check tightness of setscrews in bearings and fan 
wheel(s). If retightening is needed, position the fan 
wheel(s) per 

Table 6

 through 

Table 9

 and 

Table 11

 

through 

Table 13, page 22

. Torque set screws per 

Table 10

 and 

Table 14, page 22

.

.

7

Check alignment of fan and motor sheaves and belt 
tension. Adjust if necessary. Check tightness of sheave 
setscrews and/or capscrews. See 

Table 10, page 22

.

8

Leak test the thermal system to verify that connections 
are tight.

9

Check that the condensate drain is trapped.

10

Rotate the shaft by hand to be sure it is free.

11

If multiple fans are supplied with a block off plate and it 
is installed on one of the fans, make sure to only start the 
fans without the block off plate.  Do not start any fan that 
has the block off plate installed on it.  

WARNING

Rotating fan. 

Can cause severe injury or death. Before 

servicing fans, lockout and tag out power.

AVERTISSEMENT

Ventilateur en rotation.

 Peut causer des blessures sévères 

ou même la mort. Avant d’effectuer l’entretien des ventilateurs, 

bloquer et couper la tension.

WARNING

Fire/electric shock hazard

. Can cause property damage, 

personal injury or death. Wire fan power supply and ground 

motor frame in accordance with local electric codes.

AVERTISSEMENT

Risques d´incendie et d’électrocution pouvant causer des 

dommages matériels, des blessures et même la mort.

 

L’alimentation électrique du moteur du ventilateur de même 

que la mise à la terre du chàssis du moteur doivent être faits 

conformément aux codes d’installations électriques en 

vigueur.

WARNING

Fan motor requires overload protection. 

Failure to provide 

motor overload protection can result in fire, property damage, 

electric shock, personal injury, or death. Connect motor to an 

overload protective device rated in compliance with local 

electric codes.

AVERTISSEMENT

Risques d’incendie et d’électrocution pouvant causer des 

dommages matériels, des blessures et même la mort. 

Connecter au moteur du ventilateur électrique un dispositif de 

protection contre les surcharges conforme aux codes 

d’installations électriques en vigueur.

CAUTION

Do not overheat fan motor. 

High air temperatures in the fan 

section can cause the fan motor to burnout. On draw-through 

air handlers or air handlers with the fan section down the air 

stream from the heating section, the discharge air temperature 

of the heating section must not exceed 104°F (40°C).

ATTENTION

Risques de dommages dans le moteur du ventilateur 

électrique.

 Si Ia température de l’air a proximité du 

ventilateurest élevée, le moteurdu ventilateur électrique peut 

chauffer et brûler. Sur les transmetteurs d’air à circulation 

transversale ou les transmetteurs dont le ventilateur est en 

aval de l’unité de chauffage, régler la température de l’air 

sortant de l’unité de chauffage à 40°C (104°F).

CAUTION

Equipment damage due to loose fasteners represents 

improper start-up and equipment abuse. It is not covered by 

the warranty.

ADVERTISSEMENT

Les dommages dus à des attaches installées de façon 

inappropriée représentent un démarrage inadéquat et un 

abus d’équipement. Ceci n’est pas couvert par la garantie.

Summary of Contents for OAH 003G

Page 1: ...Installation and Maintenance Manual IM 777 7 Skyline Air Handler Group Applied Air Systems Part Number IM 777 Date November 2011 2011 Daikin Models OAC OAH 003G 090G...

Page 2: ...eating Coils 14 Drain Pan Traps 14 Internal Isolation Assembly Adjustment 15 Electrical Installation 17 Wiring 17 Operation Guidelines 19 Startup Checks 19 Before Starting the Unit 19 VFD Setup 20 Fan...

Page 3: ...before leaving the factory Rough handling can cause misalignment or a damaged bearings or shaft Carefully inspect fans and shaft before unit installation to verify this has not happened Note Screws bo...

Page 4: ...rfaces Belt driven fans Reduce belt tension by at least 50 or remove the belts Remove belts if they will be subjected to temperatures exceeding 85 F to avoid deterioration Remove belt guard when adjus...

Page 5: ...nits are provided with a factory installed base rail and can be lifted using the 2 diameter lifting holes located in the corners of each shipping section To prevent damage to the unit cabinetry use sp...

Page 6: ...lodged during shipping restore it to its designed position Shipping Sections 1 Caulk all assembly joints of the unit Before joining the sections apply at least 1 4 inch diameter bead of sealant to the...

Page 7: ...ng included in the assembly kit Figure 8 Frame Channel Stiffener Plates Skyline Plus Units Only Figure 9 Internal Fastening Figure 10 D Gasket Placement Detail Skyline Plus Units Only 1 Check that the...

Page 8: ...on one side of the unit If requested on order doors can be provided on both sides of the unit Optional service doors are available for most section types and are provided based on customer request Fa...

Page 9: ...age can occur If larger heavier components require mounting on unit panels use through bolts with flat washers through both outer and inner panels To maintain panel integrity seal both ends with an in...

Page 10: ...ions are made for the location of these actuators due to the number of options and arrangements available and the variety of specific applications Typically actuators are mounted inside the cabinet Pr...

Page 11: ...r units that include a piping vestibule cut the openings for routing the field piping as required in the field Carefully seal passages cut through the panels to prevent air leakage A single metal thic...

Page 12: ...pen to the atmosphere and the trap design should allow venting of large quantities of air Traps Note Do not place steam traps outdoors Size traps in accordance with the manufacturers recommendations M...

Page 13: ...eturn main 12 min Vacuum breaker 1 2 check valve Steam main Return main 12 min Full size of return conn Check Valve Strainer Gate Valve Control valve modulating two position Float and thermostatic tra...

Page 14: ...l drain pan trap to allow condensate to drain freely On both blow through and draw through units the trap depth and the distance between the trap outlet and the drain pan outlet must be twice the stat...

Page 15: ...t panel opening If adjustment is required loosen the cap screw on top of the isolator assembly Turn the adjustment nut below the fan frame to lower or raise the fan motor and frame assembly Retighten...

Page 16: ...l t o r p o t o n n u m b e r D m H S p r n g h e g h t d j u t m e n t c r e w S p r n g h e g h t d j u t m e n t c r e w S h p p n g h o l d d o w n c r e w S h p p n g b r c k e t D e t l A S h p...

Page 17: ...gy storing components that have been furnished and mounted by either Daikin or by others refer to the specific manufacturer s literature for allowable waiting periods for discharge of capacitors Verif...

Page 18: ...n the exterior of the fan section When multiple fan sections are provided with multiple VFDs they must be set up so that the fans always start simultaneously and are set to ramp up and down together D...

Page 19: ...et couper la tension WARNING Fire electric shock hazard Can cause property damage personal injury or death Wire fan power supply and ground motor frame in accordance with local electric codes AVERTIS...

Page 20: ...rtain to retain sheave alignment Fan Wheel Alignment Figure 29 Wheel to Inlet Tunnel Relationship Airfoil Type Fan Wheels Housed Note 1 To obtain rated air performance dimensional relationship must be...

Page 21: ...lenum Fan Wheel Funnel Parameters Size A B C 13 0 25 0 91 3 50 15 0 25 0 91 3 50 16 0 25 0 91 3 50 18 0 38 0 86 3 88 20 0 42 1 11 3 88 22 0 45 1 11 3 88 24 0 51 1 11 3 88 27 0 55 1 36 4 50 30 0 62 1 3...

Page 22: ...Size Setscrew Size Torque ft lb Aluminum Steel 11 12 13 3 8 19 2 N A 15 3 8 19 2 N A 16 3 8 19 2 N A 18 3 8 19 2 N A 20 3 8 19 2 N A 22 3 8 19 2 N A 24 3 8 19 2 N A 27 3 8 19 2 22 30 1 2 41 7 55 33 1...

Page 23: ...1875 1691 1479 1328 1209 1073 Maximum rpm Class Il 2703 2413 2199 1928 1730 1579 1401 Table 17 Operating Limits Belt Drive Plenum Fans Fan Operating Limits Belt Drive Plenum Fans Size 13 15 16 18 20 2...

Page 24: ...on of potential trouble Vibration Causes 1 Wheel imbalance a Dirt or debris on wheel blades b Loose set screws in wheel hub or bearing to shaft c Wheel distorted from overspeed 2 Bent shaft 3 Drive fa...

Page 25: ...s are supplied with grease fittings or zerks for ease of lubrication with hand or automatic grease guns Always wipe the fitting and grease nozzle clean CAUTION Bearing overheating potential Can damage...

Page 26: ...g or decreasing the pitch diameter of the sheave by half or full turns as required Readjust belt tension before starting drive 6 To provide the same pitch diameter adjust both halves of the two groove...

Page 27: ...lts over grooves See Fan Drive Belt Adjustment page 30 10 Before starting the drive ensure that all keys are in place and all setscrews and all capscrews are tight Check and retighten all screws and r...

Page 28: ...a Do not open B sheaves more than 4 3 4 turns for the A belts or 6 turns for the B belts b Do not open C sheaves more than 9 1 2 turns c Do not open 5V sheaves more than 6 turns d Do not open 8V sheav...

Page 29: ...parallel A d j u t a b l e C e n t e r F l a n g e F x e d C e n t e r F l a n g e S t a t o n a r y E n d F l a n g e C a p c r e w D o N o t R e m o v e 2 L o c k n g S e t c r e w A F l a t h e a d...

Page 30: ...ter the filter compartment until the fan is completely stopped Use approved equipment for reaching filters located above normal reach Do not step on filter frames or unit components Floor surfaces mus...

Page 31: ...the final filters Figure 41 Filter Gauge F l t e r F r a m e R o t a t e W r e C l p P r e f l t e r F n a l F l t e r Table 27 Filter Pressure Drops Bag filters DriPak 2000 Efficiency 45 65 85 95 Rat...

Page 32: ...not responsible for the freezing of coils Removing and Replacing Components See Access Doors and Panels page 8 for instructions on removing panels and opening fan access doors to remove or replace co...

Page 33: ...ocated in the connections 2 Remove all screws and remove the access panel 3 Remove the screws holding the coil in place 4 Lift and pull the coil out the side Installing Single Coils 1 Slide the coil t...

Page 34: ...ce bolt the coil to the section 4 Caulk the mounting surface of the steel plate and install the plate on the coils 5 Caulk the mounting surface of the drain trough and install the drain trough on the...

Page 35: ...s refer to the model number and serial number of the unit stamped on the serial plate attached to the unit If replacement parts are required mention the date of installation of the unit and date of fa...

Page 36: ...rned material Enter the required information to expedite handling and prompt issuance of credits All parts must be returned to the appropriate Daikin facility designated on the Return Goods tag Transp...

Page 37: ...Yes No N A D Have the hold down bolts been backed off on spring mounted fan isolators Yes No N A E With power off do fans turn freely by hand Yes No N A F Electrical service corresponds to unit namepl...

Page 38: ...N A VII HEAT RECOVERY A Heat wheel rotates freely Yes No N A B Heat wheel VFD operates properly Yes No N A C Heat wheel VFD model _____________________ serial _____________________ N A D Check for ai...

Page 39: ...binet have any air leakage Yes No N A Location on unit ___________________________________________________________________________ 5 Were there any refrigerant leaks Yes No N A Shipping Workmanship De...

Page 40: ...tions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin Representative go to www DaikinApplie...

Reviews: