• Outdoor Units • R410A • MXS-FV1B_F2V1B
1
2
• Split Sky Air • Outdoor Units
7
2
Specifications
Piping
connections
Liquid (OD)
Quantity
2
4
2
Diameter
(OD)
mm
6.35
6.35
6.35
Gas
Quantity
2
2
1
Diameter
(OD)
mm
9.5
9.5
9.5
Quantity
2
1
Diameter
(OD)
mm
12.7
12.7
Drain
Quantity
1
1
Diameter
(OD)
mm
18
18
18
Piping Length
Minimum m
3
3 (for one room)
Maximum m
30 (for total of each room)20 (for one
room)
60 (for total of each room)/ 25 (for one
room)
30 (for total of each room)20 (for one
room)
Chargele
ss
m
20
Additional Refrigerant
Charge
kg/m
0.02/>20
0.02/>30m
0.02/>20m
Installation
height
difference
Maximum m
15
15.0 (between indoor unit and
outdoor unit)
15 (between indoor and outdoor)7.5
(between indoors)
Max. internunit level
difference
m
7.5
7.5 (between indoor units)
Heat Insulation
Both liquid and gas pipes
Standard
Accessories
Item
Installation manual
Quantity
1
1
1
Item
Screw bag
Drain plug
Screw bag
Quantity
1
1
1
Item
Drain plug
Reducer assembly
Reducer assembly
Quantity
1
1
1
Notes
Nominal cooling capacities are based
on : indoor temperature : 270CDB,
190CWB, outdoor temperature :
350CDB, equivalent refrigerant
piping : 5m, level difference : 0m.
Nominal cooling capacities are based
on : indoor temperature : 270CDB,
190CWB, outdoor temperature :
350CDB, equivalent refrigerant
piping : 7.5m, level difference : 0m.
Nominal cooling capacities are based
on : indoor temperature : 270CDB,
190CWB, outdoor temperature :
350CDB, equivalent refrigerant
piping : 5m, level difference : 0m.
Nominal heating capacities are based
on : indoor temperature : 200CDB,
outdoor temperature : 70CDB,
60CWB, equivalent refrigerant piping
: 5m, level difference : 0m
Nominal heating capacities are based
on : indoor temperature : 200CDB,
outdoor temperature : 70CDB,
60CWB, equivalent refrigerant piping
: 7.5m, level difference : 0m
Nominal heating capacities are based
on : indoor temperature : 200CDB,
outdoor temperature : 70CDB,
60CWB, equivalent refrigerant piping
: 5m, level difference : 0m
2-2 ELECTRICAL SPECIFICATIONS
2MXS40FV1B
4MXS68F2V1B
2MXS50FV1B
Power Supply
Name
V1
Phase
1
1
1
Frequency
Hz
50
50
Voltage
V
220-240
230
Current
Starting current
(cooling/heating)
A
5.9
6.2
9.8
Recomended fuses
A
16
Wiring
connections
For Power
Supply
Quantity
3
3
3
For connection
with indoor
Quantity
4
4
4
Power Supply Intake
Outdoor unit only
Notes
RLA is based on following conditions: indoor temperature: 27
°
CDB/19
°
CWB, outdoor temperature: 35
°
CDB
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or
above listed range limits
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the value of MCA or TOCA
MFA is used to select the circuit breaker and the ground fault circuit interrupter
2-1 TECHNICAL SPECIFICATIONS
2MXS40FV1B
4MXS68F2V1B
2MXS50FV1B