IM 1017-1 • MT 168 0-10 VDC/4-20mA THERMOSTAT 2 

www.DaikinApplied.com

 

Figure 1: Mounting    

Figure 2: Typical Wiring*    

NOTE: 

Note: * Specific models may have fewer connections. 

Electrical Ratings

Table 1: Fan switch (terminals 1-4) line voltage 

connections 

Voltage 

Rating

Inductive

Resistive 

Amps

Pilot  

Duty

Thermostatic 

Switching

FLA

LRA

24 VAC

N.A.

N.A.

N.A.

24 VA

10 VA

120 VAC

5.8

 34.8

6.0

125 VA

NA

240 VAC

2.9

17.4

5.0

125 VA

NA

277 VAC

2.4

14.4

4.2

125 VA

NA

Application Notes 

1.  When no changeover pipe sensor is used, the main 

output controls cooling and the secondary output controls 

heating. 

2.  The fan output, terminal 12, is energized whenever there 

is a demand for heating or cooling. This output can be 

connected to a relay that can be used to provide fan 

cycling to terminal 1. 

3.  The changeover pipe sensor should be mounted on the 

main coil input for water system operation and in the 

main duct system for forced air operation. 

4.  The set point and operating mode will be retained on a 

loss of power. 

5.  When using either a remote probe or pipe sensor, run 

wiring away from any electrical motors or power wiring. 

6.  The auxiliary heat output supplies a 24 VAC signal with 

call for heat. This output is shipped configured for staged 

heat. 

7.  The thermostat is shipped with all dip switches in the 

“ON” (closed) position. 

8.  The damper output is ON when mode is AUTO, HEAT or 

COOL. Damper is OFF in set back. 

Thermostat Operation 

These thermostats are designed to control 0-10 VDC/4-0 mA 

valves. These units may include a fan switch with one or more 

fan speed selections. 

Mode Button Operation 

OFF:

 All thermostat outputs are off, fan is still operational if 

connected to a manual fan switch. 

AUTO:

 The thermostat automatically selects heating or cooling 

mode depending upon the relationship of the setpoint and the 

room temperature. The appropriate HEAT or COOL indicator 

is enabled in addition to AUTO. A 3°F dead band is provided 

to prevent short cycling between heating and cooling modes. 

After changeover, the control points automatically shift so that 

the heating OFF-point equals the set point temperature or the 

cooling OFF-point equals the set point temperature. 

COOL:

 The thermostat operates as a cooling only thermostat. 

The heating outputs are disabled. 

HEAT:

 The thermostat operates as a heating-only thermostat. 

The cooling outputs are disabled. 

LO

VO

LT

AG

E

CO

N

NE

C

TI

ON

S

LI

NE 

VOL

TA

GE

CO

N

N

ECTI

ON

S

FAN

L2 OR NEUTRAL

OPTIONAL REMOTE PROBE

OPTIONAL PIPE SENSOR

L1 (HOT)

LO FAN

MED FAN 

HIGH FAN 

OR SINGLE SPEED 

24 VAC 1  

24 VAC 2 

SETBACK

24 VAC

XFMR

MAIN 1

0-10 VDC

OUTPUT

SECONDARY

0-10 VDC

 1 OUTPUT

FAN

OUTPUT

AUXILIARY

HEAT

OUTPUT

DAMPER 

OUTPUT

10

11

12
13
14
15
16
17

1

2
3
4

5
6
7

       

Reviews: