14
|
Configuration
Installer and user reference guide
82
BK+S
Madoka wired remote controller
4P596268-1A – 2022.02
External input interlock settings overview
Parameter
Description
Possible values
Default value
B2
Delay Timer
Timer that starts as soon as
the key card is removed.
The unit continues normal
operation until the timer
expires.
0-10 minutes
"1 min"
B2
Reset Timer
Timer that starts as soon as
the Delay Timer expires.
When this timer expires,
the previous state (i.e.
regular setpoint) changes
to the
"Default Reset
Setting"
state.
0-20 hours
"20 hours"
Reset ON/OFF
"Default Reset Setting"
on/off state
"ON", "OFF", "--"
"OFF"
Reset Mode
"Default Reset Setting"
operation mode
Auto, Cooling, Heating, Fan
only, --
"--"
Reset Cool SP
"Default Reset Setting"
cooling setpoint
See indoor unit's setpoint
range and setpoint range
limitation, "--"
"22°C"
Reset Heat SP
"Default Reset Setting"
heating setpoint
See indoor unit's setpoint
range and setpoint range
limitation, "--"
"22°C"
INFORMATION
When the value for a parameter is "- -", this means that when the timers expires,
nothing changes for that parameter and the current active value is kept.
Window contact logic
Window contact B1
Key card contact B2
Time
Action
Contact closed (window
closed)
Contact closed (key card
IN)
—
▪
Normal
indoor
unit
operation.
▪
The unit returns to the
previous state before
opening the contact.