14
|
Configuration
Installer and user reference guide
73
BK+S
Madoka wired remote controller
4P596268-1A – 2022.02
Indoor unit field settings
The setting procedure is different depending on whether you want to make
settings for individual indoor units, or for groups of indoor units.
Individual indoor units
▪
Define a mode by setting a Mode number (number between brackets)
▪
Define the unit to which the setting will apply by setting a Unit number
▪
Define the setting by setting a SW number
▪
Define a value for that setting
Groups of indoor units
▪
Define a mode by setting a Mode number (number NOT between brackets)
▪
Do NOT set a Unit number (setting applies to all the units in the group)
▪
Define the setting by setting a SW number
▪
Define a value for that setting
Mode
SW
Setting (SW) description
—
01
02
03
04
10 (20)
00
Filter contamination timer
: set the timer for the
appearance of the "Time to clean filter" sreen.
Ultra long life filter
Light
±10000 hrs.
Heavy
±5000 hrs
—
—
Long life filter
±2500 hrs
±1250 hrs
Standard filter
±200 hrs
±100 hrs
01
Long life filter
: if applicable, set which type of long life filter is used.
Long life filter
Ultra long life filter
—
—
02
Controller thermostat sensor
: set how the controller thermostat sensor is
used.
Used in combination with indoor unit
thermistor
Not used
Used
exclusively
—
03
Disable filter sign
: set whether or not the filter sign can be displayed.
Display
Do not display
—
—
11 (21)
00
Simultaneous operation
: set the simultaneous indoor unit operation mode
(Sky Air)
Pair
Twin
Triple
Double twin
12 (22)
01
External On/OFF input
: set the operation of voltage free contacts T1/T2
(indoor unit contacts)
Forced OFF
On/OFF operation
Emergency
Forced OFF
(multi-tenant)
02
Thermostat differential
: if the system contains a remote sensor, set the
increase/decrease increments.
1°C
0.5°C
—
—
13 (23)
00
High air outlet velocity
: set in case of high-ceiling applications.
h≤2.7 m
2.7 m<h≤3 m
3 m<h≤3.5 m
01
Airflow direction
: set in case an indoor unit is equipped with an option kit that
blocks the airflow.
4-way flow
3-way flow
2-way flow
—
03
Airflow function
: set whether the indoor unit is equipped with a decoration
panel at its air outlet.
Equipped
Not equipped
04
Airflow direction range
Upper
Normal
Lower
—
06
External static pressure
: set the external static pressure (according to the
resistance of the connected ducts).
Normal
High static pressure
Low static
pressure
—
FHYK: follow the high-ceiling setting.
Normal
High ceiling
—
—
15 (25)
03
Humidification drain pump
Not equipped
Heating operation: continuous
Heating operation: 3 minutes
ON/5 minutes OFF
(a)
1c
01
Thermostat sensor
: set which thermostat sensor you want to use.
Indoor unit thermistor
Controller thermistor
—
—
1c
12
Window contact
B1 (external input)
Do not use
Use
1c
13
Key card contact
B2 (external input)
Do not use
Use
1e
02
Setback function
: set Setback operation.
No Setback
Heating only
Cooling only
Heating and
Cooling
1e
07
Rotation overlap time
. Set the Rotation overlap time.
30 minutes
15 minutes
10 minutes
5 minutes
1B
08
Daylight saving time
.
Set how the system controls daylight saving time.
Disable
Automatic changeover
Manual
changeover
Centralised
control
(a)
This is applicable for codes 02-06. Codes 05 and 06 are not shown in the table. See the service manual for more detailed
information.