SERVICING

40

Adjust manifold pressure using the Manifold Gas 

Pressure table shown below.

Manifold Gas Pressure 

Gas

Range

Nominal

Natural

Low Stage 

1.7 -2.3” W.C.

2.0” W.C.

High Stage  3.2 - 3.8” W.C. 

3.5” W.C.

Propane

Low Stage 

5.7 - 6.3” W.C. 

6.0” W.C.

High Stage  9.7 - 10.3” W.C.  10.0” W.C.

8.  Remove regulator cover screw from the low (LO) 

outlet pressure regulator adjust tower and turn screw 

clockwise to increase pressure, or counterclockwise 

to decrease pressure.

9.  Energize main (M) solenoid as well as the HI terminal

10. Remove regulator cover screw from the HI outlet 

pressure regulator adjust tower and turn screw clock-

wise to increase pressure, or counterclockwise to 

decrease pressure.

11. 

Turn off all electrical power and gas supply to the 

system.

12. Remove manometer hose from outlet pressure boss.

13. Turn outlet pressure test screw in to seal pressure 

port (clockwise, 7 in-lb minimum).

14. Turn on electrical power and gas supply to the sys-

tem.

15. Turn on system power and energize valve.

16. Using a leak detection solution or soap suds, check 

for leaks at pressure boss screw.  Bubbles form-

ing indicate a leak. SHUT OFF GAS AND FIX ALL 

LEAKS IMMEDIATELY.

NOTE: Use adapter kit #0151K00000S to measure gas 

pressure on White-Rodgers 36G54 gas valves.

WARNING

Line voltage now present 

Checking For Delayed Ignition

Delayed ignition is a delay in lighting a combustible mixture 

of gas and air which has accumulated in the combustion 

chamber.

When the mixture does ignite, it may explode and/or rollout 

causing burning in the burner venturi.

If delayed ignition should occur, the following should be 

checked:

1.    Improper gas pressure - adjust to proper pressure.

2.    Improper burner positioning - burners should be in 

locating slots, level front to rear and left to right.

3.    Carry over (lighter tube or cross lighter) obstructed - 

clean.

4. 

  Main burner orifice(s) deformed, or out of alignment 

to burner - replace.

Checking For Flashback

Flashback will also cause burning in the burner venturi, but 

is caused by the burning speed being greater than the gas-

air flow velocity coming from a burner port.

Flashback may occur at the moment of ignition, after a 

burner heats up or when the burner turns off.  The latter is 

known as extinction pop.

Since the end results of flashback and delayed ignition 

can be the same (burning in the burner venturi) a definite 

attempt should be made to determine which has occurred.

If flashback should occur, check for the following:

1.    Improper gas pressure - adjust to proper pressure.

2.    Check burner for proper alignment and/or replace 

burner.

3. 

  Improper orifice size - check orifice for obstruction.

Checking Pressure Control

A pressure control device is used to measure negative 

pressure at the induced draft blower motor inlet to detect a 

partial or blocked flue.

Pressure Switch Operation 

 

(DSI Direct Spark System)

The pressure switch is ignored unless there is a call for 

heat.  When the control receives a call for heat, the control 

checks to see that the pressure switch is open.  If the 

control sees that the pressure switch is closed before the 

induced draft blower is energized, the LED will flash a code 

of “2” (to indicate the pressure switch is stuck closed) and 

the inducer will remain off until the pressure switch opens.

If the pressure switch opens before the ignition period, the 

induced draft blower will remain on and the control will stay 

in pre-purge until the pressure switch is closed for an entire 

15 second pre-purge period.  The LED will flash a code of 

“3” to indicate open pressure switch.

If the pressure switch opens after the gas valve has been 

energized, the control will de-energize the gas valve and 

run the indoor blower through the heat off delay.  The 

inducer stays on until the pressure switch re-closes.  Then 

the control makes another ignition attempt.

WARNING

High Voltage!

Disconnect all power before servicing or 

installing.  Multiple power sources may be present.  

Failure to do so may cause property damage, 

personal injury or death.

1.    Remove wires from the electrical terminals.

2.    Using a VOM check from Common to NO (Normally 

Open) - should read open. 

If switch reads as noted proceed to Step 3, otherwise 

replace control.

Summary of Contents for M Series

Page 1: ...WINDINGS PSC MOTORS 21 CHECKING EEM MOTORS 21 CHECKING COMPRESSOR 22 RESISTANCE TEST 22 GROUND TEST 23 OPERATION TEST 23 LOCKED ROTOR TEST 24 TESTING CRANKCASE HEATER OPTIONAL ITEM 24 CHECKING REVERS...

Page 2: ...AL INJURY OR DEATH OUTSIDE THE U S call 1 713 861 2500 Not a technical assistance line for dealers Your telephone company will bill you for the call REFRIGERANT CHARGE CHECK 28 CHECKING SUPERHEAT 28 C...

Page 3: ...f refrigerants WARNING The compressor POE oil for R 410A units is extremely susceptible to moisture absorption and could cause compressor failure Do not leave system open to atmosphere any longer than...

Page 4: ...tre effectu s par un installateur ou une entreprise d entretien qualifi ou le fournisseur de gaz WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow instructions could result in severe persona...

Page 5: ...single phase 60 Hz Unit Type Refrigerant D Dual Fuel 4 R 410A Heat Input Airflow 060 60 MBTU H 080 80 MBTU H 100 100 MBTU H M Multi position Efficiency Tonnage Nominal 3 13 4 SEER2 24 2 tons 42 3 tons...

Page 6: ...1AA Goodman Brand Package Dual Fuel Units 14SEER with R410A Initial release of 81 AFUE models A GPD1436080M41AB Amana Brand Goodman Brand Package Dual Fuel units 14 SEER with R410A Compressor Change S...

Page 7: ...to give up heat until it condenses to a liquid alone Once the vapor is fully liquefied it continues to give up heat which subcools the liquid and it is ready to repeat the cycle Heat Pump Models Any t...

Page 8: ...es are energized along with the igniter for trial for ignition period Igniter is de energized when flame is detected 5 Flame is achieved and detected during trial for ignition period Flame stabilizati...

Page 9: ...blower on delay 4 The unit is now operating the heat pump in the heating mode 5 If the thermostat cannot be satisfied or the outdoor thermostat changes to gas heating operations W1 is energized and Y...

Page 10: ...selected by setting the circuit board jumper to 30 60 and 90 respectively Accumulation of time for the timing period selected starts when the sensor closes approximately 30 F and when the wall thermo...

Page 11: ...RATION 11 Indoor Coil Accumulator Outdoor Coil Reversing Valve Energized Indoor Coil Accumulator Outdoor Coil Reversing Valve De Energized Typical Heat Pump System in Cooling Typical Heat Pump System...

Page 12: ...s used to monitor the flame The board has the option of using a single or two stage thermostat The board also controls the indoor blower and has an adjustable heat fan off delay There is also a fault...

Page 13: ...sed 5 24VAC 24VAC Common 6 24VAC Pressure Switch Output 7 24VAC Main Valve High Output 8 24VAC Pressure Switch Input 9 Unused Main Valve Low Output Table 2 Circuit Definitions and Voltage Ratings for...

Page 14: ...OFF Delay 0 Seconds Ignition Attempts 3 Recycles Infinite Automatic Restart 60 Minutes Pressure Switch Lockout Delay 5 Minutes Factory Test Mode Active Time 2 Minutes Maximum Flame Failure Response Ti...

Page 15: ...ner flame and microamp signal Adjust if necessary 10 Start the system and run a Heating Performance Test If the results of the test are not satisfactory see the Service Problem Analysis Guide for the...

Page 16: ...your natural gas BTU HR input 8 Should the figure you calculated not fall within five 5 percent of the nameplate rating of the unit adjust the gas valve pressure regulator or resize orifices To adjust...

Page 17: ...so may cause property damage personal injury or death 1 Check wiring visually for signs of overheating damaged insulation and loose connections 2 Use an ohmmeter to check continuity of any suspected o...

Page 18: ...Relays WARNING High Voltage Disconnect all power before servicing or installing Multiple power sources may be present Failure to do so may cause property damage personal injury or death The compresso...

Page 19: ...auses for high head pressure in Service Problem Analysis Guide If it cuts out below this pressure range replace the control The control should reset at 420 PSIG 25 PSIG Checking Low Pressure Control T...

Page 20: ...nce of shock to the servicer See the Servicing Section for specific information concerning capacitors Relay Start A potential or voltage type relay is used to take the start capacitor out of the circu...

Page 21: ...he continuity between each of the motor leads 3 Touch one probe of the ohmmeter to the motor frame ground and the other probe in turn to each lead If the windings do not test continuous or a reading i...

Page 22: ...occur at the venting terminal without the presence of contaminant air and cannot occur externally from the venting terminal without the presence of an external ignition source Therefore proper evacuat...

Page 23: ...tely between each of the three terminals and ground such as an unpainted tube on the compressor If there is any reading of continuity to ground on the meter the compressor should be considered defecti...

Page 24: ...pound gages will give the same symptoms as bad compressor valves or broken scroll flanks The temperature between true suction and the suction line after the valve should not be greater than 4 degrees...

Page 25: ...remove jumper from test pins 5 Using VOM check for voltage across terminals C O Meter should read 24 volts 6 Using VOM check for voltage across fan terminals DF1 and DF2 on the board You should read l...

Page 26: ...and a pressure relief valve The pressure relief valve must be set to open at no more than 450 psig Leak test the system using dry nitrogen and soapy water to identify leaks If you prefer to use an ele...

Page 27: ...nutes Break the vacuum with dry nitrogen again bring the system pressure back to 2 3 PSIG and hold for 20 minutes 3 Evacuate the system to 500 microns and hold for 60 minutes 4 If the pressure rises t...

Page 28: ...4 Record the gauge pressure corresponding temperature and the temperature of the suction line 5 Refer to the superheat table for proper system superheat Add charge to lower superheat recover charge t...

Page 29: ...t enter the compressor Due to their design Scroll compressors are inherently more tolerant of liquid refrigerant NOTE Even though the compressor section of a Scroll compressor is more tolerant of liqu...

Page 30: ...60 8 6 162 0 57 0 264 0 87 4 366 0 110 4 468 0 129 0 600 0 149 0 62 10 0 164 0 57 7 266 0 87 9 368 0 110 8 470 0 129 3 604 0 149 5 64 11 3 166 0 58 4 268 0 88 4 370 0 111 2 472 0 129 7 608 0 150 1 66...

Page 31: ...88 86 84 82 80 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96 94 92 90 88 86 345 98 96 94 92 90 88 354 100 98 96 94 92 90 364 102 100 98 96 94 92 374 104 102 100 98 96 94...

Page 32: ...be noticed at the point of restriction In severe cases frost will form at the restriction and extend down the line in the direction of the flow Discharge and suction pressures will be low giving the a...

Page 33: ...ossible The filter must be accessible and be rechecked for a pressure drop after the system has operated for a time It may be necessary to use new tubing and form as required NOTE At least twelve 12 i...

Page 34: ...EEM motors EEM motors are constant torque motors with very low power consumption This motor is energized by 24VAC Adjust the CFM for the unit by changing the 24VAC leads to the speed terminal block on...

Page 35: ...n the combustion chamber is sufficiently lowered WARNING High Voltage Disconnect all power before servicing or installing Multiple power sources may be present Failure to do so may cause property dama...

Page 36: ...l is designed to open should a flame roll out occur An over firing condition or flame impingement on the heat shield can also cause the control to open If the rollout control has opened the circuit be...

Page 37: ...blower running all flames are not drawn into the tubes either the collector box combustion blower or flue outlet is obstructed If the combustion blower or flue outlet is obstructed the pressure switc...

Page 38: ...into consideration such as inlet manifold gas pressure alignment and positioning specific gravity and BTU content of the gas being consumed The only time resizing is required is when a reduction in fi...

Page 39: ...es 2 Connect a water manometer or adequate gauge to the inlet pressure tap of the gas valve or hose barb fitting on predrilled cap With Power And Gas On 3 Put unit into heating cycle and turn on all o...

Page 40: ...used by the burning speed being greater than the gas air flow velocity coming from a burner port Flashback may occur at the moment of ignition after a burner heats up or when the burner turns off The...

Page 41: ...fuel the air temperature rise must be within the range listed on the unit nameplate Refer to the Installation Manual provided with the LP kit for conversion from natural gas to propane gas and for alt...

Page 42: ...d replace ignition control E Voltage present at gas valve replace gas valve 2 Board set for 1 stage thermostat A Wait the selected delay time either 5 or 10 minutes depending on jumper setting B Check...

Page 43: ...ntrol will de energize the gas valve and retry for ignition or lockout DSI Direct Spark Ignition Systems WARNING High Voltage Disconnect all power before servicing or installing Multiple power sources...

Page 44: ...6 173 51 1164 302 52 908 158 1118 260 1249 333 0 5 835 182 54 1131 314 53 857 166 1071 268 1211 345 0 6 781 188 58 1086 319 55 784 175 1023 275 1168 348 0 7 731 200 62 1038 319 58 732 180 973 283 1126...

Page 45: ...e Range 35 65 E S P T1 1ST Stage Heating Speed T2 2 nd Stage Heating Speed T3 Cooling Speed T4 Cooling Speed T5 Cooling Speed CFM WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS 0 1 1098 167 5...

Page 46: ...OR GAS VALVE CHECK PRESSURE SWITCH 3 FLASHES 2 FLASHES 4 FLASHES 5 FLASHES FALSE FLAME DETECTED OPEN LIMIT SWITCH WITHOUT INDUCER ON PRESSURE SWITCH OPEN CHECK FOR SHORTS IN FLAME SENSOR WIRING NORMAL...

Page 47: ...uck Open 3 Flashes Pressure Switch Stuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only 7 Flashes Li...

Page 48: ...RS VM ALS PS GV IGN H C F LO HEAT 6 3 1 2 4 5 OR BL PU YL OR BR OR P1 PIN 3 P1 PIN 5 P1 PIN 9 P1 PIN 2 BR YL P1 PIN 6 P1 PIN 7 YL P1 PIN 8 RD P1 PIN 1 BL P1 PIN 5 BK BL PK BL OR OR OR OR RD RD RD BL B...

Page 49: ...IRING LOW VOLTAGE LOW VOLTAGE BK BLACK WIRE CODE PK PINK OR ORANGE GR GREEN BR BROWN BL BLUE RD RED WH WHITE YL YELLOW PU PURPLE COOL HI HEAT LO HEAT P2 2 6 3 1 2 8 6 3 1 2 L1 L1 HI LO HI DR C R W Y O...

Page 50: ...3597706 500 48926 002 ORANGE 1 X 78 GROUND 1 X 50 COLOR CODES FOR PLUG 1 8 O ORANGE GROUND G GREEN WIRE LENGTHS FOR PLUG 1 9 8 7 3 2 1 G Y2 TSTAT Y1 CONTACTOR COMMON Y1 TSTAT O 6 5 4 CC1 Y Y2 CONTACT...

Page 51: ...us Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN BRAND AMA...

Reviews: