12
3-33
5 Alarm display and back-up function
5.1 Alarm list
Alarm
Alarm
Alarm content
Action with alarm
grouping code
F101
HPS activated within 30 seconds after operation start or protection device
Unit stops
activated 5 times at start-up operation or Fuse 1 brown (Refer Page 7-7).
F109
Low- pressure drops to–85kPa or lower within 2 seconds after operation start.
Unit stops
F111
HPS does not activate when it reaches to the set value.
Unit stops
F301
Temperature setting required (SRAM failure)
Unit stops
F401
Return/Supply air sensor malfunction (at chilled mode)
Unit stops
F403
Return/Supply air sensor malfunction (at partial frozen mode)
Unit stops
F603
Suction modulating valve (SMV) does not fully close contrary to the designation
or initial setting of the controller is wrong.
Unit stops
F701
Abnormal high voltage (over 600V)
Unit stops
F705
S phase became open phase
Unit stops
F803
Abnormalities, which make it impossible to continue operation (Note2.)
Unit stops
E101
High-pressure switch activated during normal operation.
Restart after 3-minute
E103
CTP or electronic OC activated during normal operation.
Restart after 3-minute
E105
Micro processor OC activated during normal operation.
Restart after 3-minute
E107
DCHS became abnormal high temperature during operation.
Restart after 3-minute
In the event the refrigerant circulation rate is low, the unit
If this error occurs two times, F803
will stand by for three minutes to restart then.
error will be detected to stop the unit.
E109
Low pressure drops to–90kPa or lower for 2 seconds
Restart after 3-minute
or longer successively during normal operaton.
E201
Pump down is not completed within 90 seconds.
Only alarm display
E203
Overcool protection activates in the chilled or partial frozen mode.
Restart after 3-minutes
(Control temperature
≦
SP–3˚C or for 3 minutes)
E205
Evaporator for motor failure
Only alarm display
E207
Defrosting is not completed within 90 minutes
Only alarm display
E303
Humidity setting required (SRAM failure)
Only alarm display
E305
Defrost timer setting required (SRAM failure)
Only alarm display
E307
Calendar setting required (SRAM failure)
Only alarm display
E311
Trip-start setting required (SRAM failure)
Only alarm display
E315
PT/CT board failure
Restart after 3-minutes
E401
Supply air temperature sensor (SS) malfunction
Back-up operation
E402
Data recorder supply air temperature sensor (DSS) malfunction
Back-up operation
E403
Return air temperature sensor (RS) malfunction
Back-up operation
E404
Data recorder return air temperature sensor (DRS) malfunction
Back-up operation
E405
Discharge air temperature sensor (DCHS) malfunction
Only alarm display
E406
Suction gas temperature sensor (SGS) malfunction
Back-up operation
E407
Evaporator inlet temperature sensor (EIS) malfunction
Back-up operation
E409
Evaporator outlet sensor (EOS) malfunction
Back-up operation
E411
Ambient sensor (AMBS) malfunction
Only alarm display
E413
Low pressure transducer (LPT) malfunction
Back-up operation
E415
High pressure transducer (HPT) malfunction
Back-up operation
E417
Voltage sensor (PT1) malfunction
Only alarm display
E421
Current sensor (CT1) malfunction
Only alarm display
E423
Current sensor (CT2) malfunction
Restart after 3-minutes
E425
Pulp temperature sensor (USDA1) malfunction
Only alarm display
E427
Pulp temperature sensor (USDA2) malfunction
Only alarm display
E429
Pulp temperature sensor (USDA3) malfunction
Only alarm display
E431
Humidity sensor (HuS) malfunction
Only alarm display
E433
Cargo temperature sensor (CTS) or box temperature sensor
Only alarm display
(CBS) malfunction
E603
Suction modulating valve (SMV) malfunction or driver malfunction
Back-up operation
E607
MDS (sheet key) malfunction
Only alarm display
E707
Momentary power failure
Restart after 3-minutes
E801
Backup battery replacement date exceeded
Only alarm display
Permanent
stop
Display
a
lone
or
restartable
a
larm
Protection
device
activation
Control
error
Printed-circuit
board
failure
Sensor
alarm
Electronic functional part
alarm
Power supply alarm
Ohter alarm
Note 1) The alarm LED does not blink when E code alarm is generated.
To check if any alarm generates, use alarm indication function in the section "1. Current indication
mode" of "3.3.2 Mode operation procedure.
2) In the event error E101, E103, E107, or E109 occurs 10 times, the system will go to 4-hour standby
mode.
3) In case of sensor malfunction, the judgment for sensor malfunction does not perform for 3 minutes
before the pressure or temperature reaches to the specified value.
https://daikin-p.ru